Lightolier L1PH User Manual

Operates incandescent, magnetic and electronic ballast fluorescent, high power factor compact fluorescent, and high intensity discharge (HID) lamp types.
How to Specify:
Unit 14.0 kVA
Battery 2,995 lbs. Cabinet (1,358 kg)
Electronics 465 lbs. Cabinet (211 kg)
Total System 3,460 lbs.
(1,569 kg)
L1PH Series Uninterruptible Power Supplies
L1PH
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
Lightolier
a Genlyte Thomas Company www.lightolier.com 631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2004 Genlyte Thomas Group LLC (Lightolier Division) • D0504
Overall Characteristics
• 86% throughput efficiency
• Operating temperature range 32°F (0°C) to 104°F (40°C)
• Internal maintenance by-pass is standard
• Main load disconnect switch standard
• Double conversion, no interruption
• Standard backup time of 90 minutes, other run times optional
• Output circuit breakers and normally-off loads optional
Housing
• Free standing, NEMA 1 enclosure
• Acid resistant powder coat finish
• Multiple conduit entries
Metering/Controls
Standard
• Alpha-numeric front panel display with 14 metered measurements and 53 messages/alarms
• Normal, caution and alarm indicating LEDs
• Audible failure alarms with silence switch
• Dry contact for remote failure alarm
• “D” type 9-pin computer interface connector (see pin config. on back)
• Programmable battery monitor with alarm
Optional
• Diagnostics software for remote computer (PC) monitoring and control
• Stand-alone remote display mimics all measurements, indications and alarms shown on the front panel display
• Additional RS-232 input/output port for remote monitoring and system control
Electrical
• Sine Wave Output
• Completely solid-state Pulse Width Modulation (PWM) inverter
• 16-bit microprocessor control
• Input power factor correction maintains power factor at 0.99
• Transient response 5%; Recovery time, 10 mS (100% load step)
• 3:1 crest factor capability
• Inverter output distortion 2.5% THD (at unity power factor)
• Output voltage regulation ±6% of nominal at full load
• Frequency within ±0.05% of nominal
• Inverter efficiency 84%
• Load power factor capability is 0.5 leading to 0.5 lagging
(Continued on page 2)
NOTE: Input circuit breaker not available. Input switch is standard.
L1PH I 14.0 S
SERIES INPUT SYSTEM BASE BATTERY OUTPUT OUTPUT # ON 2ND NORMALLY # OF NOL
VOLTAGE TYPE SIZE TYPE VOLTAGE CKT BRKRS1VOLTAGE OFF LOAD NOL VOLTAGE
L1PH = Single Phase Uninterruptible Power Supplies
14.0 = 14.0 kVa
2 = 208 V 3 = 240 V 4 = 277 V Z = Special Voltage
(Consult Factory)
1 = 120 V 2 = 208 V 3 = 240 V 4 = 277 V 5 = 120/208 V 6 = 120/240 V 7 = 120/277 V Z = Special Voltage
(Consult Factory)
Y = Hardwire A = 1 0CB B = 2 0CB C = 3 0CB D = 4 0CB E = 5 0CB F = 6 0CB G = 7 0CB H = 8 0CB J = 9 0CB K = 10 0CB L = 11 0CB M = 12 0CB N = OCBA1 P = OCBA2 R = OCBA3 S = OCBA4 T = OCBA5 U = OCBA6 V = OCBA7 W = OCBA8 X = OCBA9
0 1 2 3 4 5 6 7 8
9 10 11
A = No B = Yes C = Yes w/ Time Delay Timer
0 = No NOL Y = Hardwire Terminal 1 = 1 2 = 2 3 = 3 4 = 4 5 = 5 6 = 6 7 = 7 8 = 8 9 = 9 10 = 10 11 = 11 12 = 12
X = None A = 1st B = 2nd
I = ETL Listed to UL 924 for Emergency Lighting Applications
S = Sealed Lead Calcium
34.0”
86.4 cm
33.0”
83.8 cm
70.0”
177.8 cm
Battery
Cabinet
33.0”
83.8 cm
30.0”
76.2 cm
43.5”
110.5 cm
Electronics
Cabinet
Electrical (continued from page 1)
• Automatic, battery protecting low voltage disconnect (LVD)
• Advanced battery diagnostics and management system
• Temperature compensated battery charger
• 24 hour recharge time
• High frequency, very low ripple current charger
• Input and output disconnect switch
• Battery disconnect switch
NOTES:
1) Continuous Duty
2) Total Load Not to Exceed System Rating
System Input/Output Ratings
Warranty
Standard Warranty Lightolier will provide parts and on-site labor for the first 90 days following shipment of product, and parts only for an additional 270 days.
Extended Warranty (Available with purchase of Factory Start-Up Service) Lightolier will provide parts and on-site labor for the first 12 months following start-up of the product, and parts only for an additional 12 months.
System One-Line Diagram
Pin Description Function
8 Normal System Functioning Normally 6 Load On Reserve Double Conversion Inverter Not Operating 9 Power Failure Load Supplied by Battery 7 End of Discharge Period Unit Will Soon Stop Operating 5 Common Common Connection to Above 4 Signals
Computer Interface Pin Configuration
(AS/400™)
Listed to
UL 924
SYSTEM INPUT INPUT AVAILABLE OUTPUT VOLTAGES/ OCB POLE SPACES
RATING VOLTAGE AMPS
1
MAX. LOAD AMPS
2
AVAILABLE
120 V 208 V 240 V 277 V
14,000 VA 277 63.2 116.5 50.5 12
208/240 80.8/70.0 116.5 67.3 58.3 12
L1PH Series Uninterruptible Power Supplies
L1PH
Lightolier
a Genlyte Thomas Company www.lightolier.com 631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2004 Genlyte Thomas Group LLC (Lightolier Division) • D0504
Battery
Maintenance free, sealed lead calcium battery has an estimated service life of 10 years, and an operating temperature range of 65°F (19°C) to 85°F (30°C).
Options
0 = None 1 = PC Format Diagnostics Software 4 = Remote Display + “5” 5 = Additional RS-232
Job Information Type:
Loading...