Lightolier IS-4X4 User Manual

READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE
INSTALLATION PROCEDURE FOR: 4X4, 4X9, AND 9X9
INSTRUCTION SHEET NO.
Page 1 of 2
°°
A. FRAME-IN AND WIRE-IN
CAUTION: (RISK OF FIRE) DO NOT INSTALL INSULATION ABOVE NOR WITHIN 3 INCHES (76mm) OF ANY
CAUTION: USE ONLY REFLECTOR TRIMS PROVIDED BY LIGHTOLIER. USE OF OTHER MANUFACTURERS’ REFLECTOR
ANCHOR CLIP
T-BAR
FIG. 4
FIG. 5
For suspended T-bar ceilings: T-bar ANCHOR CLIPS
For wood joist construction: Mounting bars may be
SCREW
ADJUSTMENT
FIK. HOUSING
ADJUSTABLE BRACKET
MOUNTING
1/2” EMT ADJUSTABLE
BRACKET
ADJUSTABLE BRACKET
FIG. 1
FIG. 2
FIG. 3
FIK. HOUSING
FIK. HOUSING
BALLAST
MOUNTING BAR
J-BOX
NAILS
JOISTS
MOUNTING BAR ordering information:
Note: If FIK is to be used with a WALL-WASH LOUVER TRIM
This fixture is intended for installation in accordance with the National Electrical Code and local regulations. To
assure full compliance with local codes and regulations, check with your local electrical inspector before
installation. To prevent electric shock, turn off electricity at fuse box before proceeding.
IS:4X4
B0502
PART OF THE LUMINAIRE (FIXTURE)
TRIMS MAY VOID THE UNDERWRITERS LABRATORIES LISTING AND COULD CONSTITUTE A FIRE HAZARD.
Install FRAME-IN KIT (FIK) using ADJUSTABLE MOUNTING BRACKETS (Fig.’s 1-3). Fixture must be secured to structural ceiling members. Connect to supply leads; white fixture lead to neutral (white) supply lead, black fixture lead to hot supply lead, bare copper and/or green insulated wire(s) must be connected to supply ground. Use wirenuts (local hardware items). Place all electrical connections in the J-BOX and close cover.
3/4” OR 1-1/2” CHANNEL (BY OTHERS)
BAR
(11/16” OD) (BY OTHERS)
ADJUSTMENT
MOUNTING
accessory No. 1956 (order separately) may be used with 18” or 27” MOUNTING BARS (Fig. 4), or simply wire MOUNTING BARS, EMT TUBING, or CHANNELS to ceiling members (Fig. 5). FIK must be securely attached to and unable to lift from
ceiling members after installation is complete.
WIRE
MOUNTING BAR
used to secure FIK. to joists (Fig. 6). MOUNTING BARS may be bent where required to allow precise placement
of FIK between joists. Use nails to secure to joists.
90
MOUNTING
SCREW
MOUNTING
18” long: Cat. No. 1950 27” long: Cat. No. 1951
(Fig. 7), FIK must be installed with either J-BOX side or BALLAST side parallel to wall to be washed.
Direction of wall to be washed
ADJUSTMENT SCREW
FIG. 6
FIG. 7
631 Airport Road, Fall River, MA 02720
A COMPANY
READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE
This fixture is intended for installation in accordance with the National Electrical Code and local regulations. To
INSTRUCTION SHEET NO.
Page 2 of 2
°°
B. ADJUST FIK
D. INSTALLATION OF REFLECTOR TRIM
E. RE-LAMPING
F. BALLAST REPLACEMENT
BALLAST
FIG. 12
FIG. 11
UPPER NUTS
HOUSING
TORSION EMBOSSED
SLOT
REFLECTOR
FIG. 10
BALLAST
FINISHED CEILING
FLUSH TO CEILING OR
ADJUSTMENT
FIG. 8
Base of FIK is provided with a
FIG. 9
assure full compliance with local codes and regulations, check with your local electrical inspector before
installation. To prevent electric shock, turn off electricity at fuse box before proceeding.
Retain these instructions for maintenance reference.
ADJUSTABLE
Set FIK so that bottom edge is flush to, or
SCREWS
recessed 1/8” above finished ceiling (Fig. 8).
FIK
Final vertical adjustment may be made by means of ADJUSTMENT SCREWS on inside of FIK.
C. CLOSE-IN
UP TO 1/8” RECESSED
Close-in and finish ceiling as required.
1. Squeeze both TORSION SPRINGS and insert ends into EMBOSSED SLOTS.
2. Push REFLECTOR TRIM up into FIK until flange is seated firmly against ceiling surface.
**Care and Maintenance of “Alzak” REFLECTOR TRIM finish:** If handling of REFLECTOR TRIM with anodized or Alzak finish is required, the use of clean white or plastic film gloves is recommended to avoid fingerprints.
MOUNTING BRACKET
IS:4X4
B0502
hole pattern (Fig. 9) to assist with the alignment of multiple FIK’s. This hole pattern will facilitate the use of laser
beams, plumb lines, etc.
Anodized or Alzak surfaces can be cleaned by the following methods:
1. Wipe off with a soft, clean, dry, lint-free cloth.
2. Wipe off with a soft clean cloth dampened in mild detergent solution.
Rinse, then wipe dry with lint-free cloth or paper towel.
3. Wipe off with a clean cloth dampened with a solution of wetting agent and
water (such as 2 oz. Per gallon “Pluronic L62-LF” by Wyandotte Products). Wipe dry.
4. Use a liquid wax such as Glass Wax . Avoid gritty cleaning agents.
1. Turn off power
2. Pull REFLECTOR TRIM down until ends of TORSION SPRINGS reach EMBOSSED SLOTS.
3. Squeeze TORSION SPRINGS to disengage from EMBOSSED SLOTS, and remove REFLECTOR TRIM.
4. Replace lamp (Do not exceed maximum wattage marking).
5. Replace REFLECTOR TRIM.
1. Make sure AC power is OFF at fuse-box.
2. Remove REFLECTOR TRIM & lamp(s) (See E.).
3. Undo WINGNUT(s) and remove UPPER REFLECTOR.
4. Remove NUTS that secure BALLAST PLATE to HOUSING.
5. Partially remove BALLAST PLATE from HOUSING.
6. Disconnect wire leads from BALLAST push-in terminals. (Insert pin or paper clip in RELEASE SLOT, Fig. 11)
7. Remove BALLAST from BALLAST PLATE, and install new BALLAST.
8. Insert wire leads into BALLAST. Follow wiring diagram on BALLAST.
9. Reattach BALLAST PLATE, UPPER REFLECTOR, lamp(s),
90
and REFLECTOR TRIM .
WINGNUT
SPRING
TRIM
PLATE
PLATE
REFLECTOR
RELEASE SLOT
BALLAST
631 Airport Road, Fall River, MA 02720
A COMPANY
Loading...