Lytemode Network Powered Hub User’s Guide
© 2008 Philips Controls. All Rights Reserved.
LYTEMODE NETWORK POWERED HUB USERS GUIDE
Important Safeguards
When using electrical equipment, basic safety precautions should always be followed including the following:
a) READ AND FOLLOW ALL SAFETY INSTRUCTIONS. b) Do not use outdoors. c) Do not mount near gas or electric heaters. d) Equi pment should be mounted in locations and at heights where it will not readily be
subjected to tampering by unauthorized personnel.
e) The use of accessory equipment not recommended by the manufacturer may cause an
unsafe condition. f) Do not use this equipment for other than intended use. g) Refer service to qualified personnel.
SAVE THESE INSTRUCTIONS.
Table of Contents
Customer Service .............................................................................................................................2
Lytemode System Overview ............................................................................................................
Ly
temode ILS Network Powered Hub Overvi
Device Power Requirements ........
Operation ...................................................................................................................................5
Installation .......................................................................................................................................6
Installing the Unit ......................................................................................................................6
Specifications ...................................................................................................................................8
.............................................................................................5
ew ...........................................................................
3 4
1
CUSTOMER SERVICE LYTEMODE NETWORK POWERED HUB USERS GUIDE
Customer Service
Technical and Sales assistance for Lytemode products are available worldwide.
Phone: +1-800-526-2731 (In the United States and Canada)
+1-214-647-7880 (Worldwide)
2
LYTEMODE NETWORK POWERED HUB USERS GUIDE LYTEMODE SYSTEM OVERVIEW
Lytemode System Overview
The Lytemode System is designed to control architectural lighting by distributing both power and intelligence. The system provides processing power and control at each respective Master or Remote Station, eliminating the need for a central processor. Lytemode Master Stations provide individual channel control, 13 scenes plus “Off,” adjustable fade times, and a graphic representation of channel intensities. Multiple Master Stations may be linked together for control of up to 128 Channels and 13 preset scenes. By combining Lytemode Master Stations with Lytemode Remote Stations, the system provides remote access to scenes, Master Raise/Lower control, Multi-room partition control, or Master Station Lockout. Lytemode Master Stations are easily programmed using the front panel buttons, without removing the Master Station from the wall, and without the need for a computer. Lytemode Master Stations are compatible with both Lightolier Controls Insulated Gate Bipolar Transi (IGBT) Dimming Cabi
nets as well as Sili
con Controlled Rectifier
(SCR) Dimming Panels.
Lytemode products are controlled by the Intelligent Lytemode System (ILS) protocol. All Lytemode control devices must be connected to the ILS system in order to interact properly, where they are distinguished by a unique ID (or address). The ID identifies the device on the network and allows the device to avoid network collisions when transmitting data.
stor
3
LYTEMODE NETWORK POWERED HUB OVERVIEW LYTEMODE NETWORK POWERED HUB USERS GUIDE
Lytemode Network Powered Hub Overview
The Lytemode Network Powered Hub (ILSLMHUB) provides DC Power across the Lytemode ILS Network for the purpose of powering Master Stations , Remotes, and Interfaces. The Network Powered Hub provides 1.5 amps each for four separate, electrically isolated Lytemode Network circuits. The unit is equipped with separate compartments for Line Voltage wiring connections and Low Voltage wiring connections. Terminal blocks for all connections are included. The Network Powered Hub can be either wall-mounted or rack-mounted using the included reversible mounting brackets.
The L ytemode Network Powered Hub can be used to po wer large networks, to supply additional power for very long cable lengths, or used as a redundant supply to ensure Lytemode Network reliability. Multiple Powered Hubs may be connected to a Lytemode ILS Network.
Network Output Connections - Four terminal strips
Input Power Connections - Terminal strip for
connection of Line, Neutral and Ground wiring.
High Voltage Compartment
for connection of CAT5e cables, which supply power to the Lytemode devices in a daisy-chain configuration.
LINE IN
NEUTRAL
N/A
GROUND
Mounting Bracket (2) - Configurable brackets for wall or rack mounting.
1 GND
2 AC LINE
3 AC NEUTRAL
Output + 4
Output +5
Output - 6
Output - 7
Power Supply
Figure 1: Hub Interior View
Low Voltage
Compartment
INTERIOR VIEW
4
LYTEMODE NETWORK POWERED HUB USERS GUIDE LYTEMODE NETWORK POWERED HUB OVERVIEW
Device Power Requirements
The following chart provides power requirements for Lytemode ILS devices.
Master Stations
ILSCL125ES 103mA Each ILSCL165ES 116mA Each
ILSCL85ES 72mA Each ILSCL45ES 59mA Each
ILSCL6MMES 20mA Each
ILSCLTS 350mA Each ILSDMX45ES 60mA Each ILSDMX85ES 75mA Each
ILSDMX125ES 105mA Each ILSDMX165ES 120mA Each
Remote Stations
ILSCL8RES 20mA Each ILSCL6RES 20mA Each ILSCL2RES 20mA Each
ILSCL8RSPS 20mA Each
Interface Options
ILSCL232 25mA Each
ILSCLIM 10mA Each
Operation
Once connected to the house power service and Lytemode ILS Network, the Network Powered Hub is ready for operation. T o apply power to the ILS network, appl y house power service to the unit. Refer to “Installation” on page 6 for connection instructions.
5
INSTALLATION LYTEMODE NETWORK POWERED HUB USERS GUIDE
Installation
The Network Powered Hub can be wall-mounted or rack-mounted using the included mounting brackets. Knock-out holes in the unit’s housing can be used to route power wiring and network cables as required.
Installing the Unit
To install:
Step 1. Unpack unit and inspect for any signs of shipping damage. Step 2. If necessary, reconfigure mounting brackets (supplied) for wall or rack mounting
as shown in Figure 2.
Housing
Low Voltage Compartment Cover
Screw (4)
CONFIGURATION 1
Screw (4)
Mounting Bracket
Mounting Bracket
CONFIGURATION 2
High Voltage Compartment Cover
Screw (9)
Figure 2: Configuring Mounting Brackets & Removing Covers
Step 3. Install unit. Step 4. Remove covers from High Voltage and Low Voltage compartments.
WARNING: Ensure that power is removed from house service before connecting any wiring or cables
to the Network Powered Hub.
Step 5. Remove power from house service.
6
LYTEMODE NETWORK POWERED HUB USERS GUIDE INSTALLATION
Step 6. As required, remove knock-out hole covers and route power input wires and
Lytemode ILS Network cables as shown in Figure
3.
Note: The Lytemode ILS Network consists of a single CAT5e cable connecting all Lytemode ILS
devices in a daisy-chain configuration. All units connect to the network using a 9-pin connector (included).
9-Pin Lytemode Network Connectors
Route Network Cables
Knock-out Hole
Route Power Wires
PIN SIGNAL
1 WH/OR (+ Data) 2 OR (- Data) 3SHIELD 4WH/GN (+ Volts) 5 GN (Ground) 6WH/BL (+ Volts) 7 BL (Ground) 8WH/BR (+ Volts) 9 BR (Ground)
WARNING!
Remove power from house service before connecting any wiring or cables to the Network Powered Hub.
Input Power Connections
LINE IN
NEUTRAL
N/A
GROUND
1 GND
2 AC LINE
3 AC NEUTRAL
Output + 4
Output +5
Output - 6
Output - 7
INTERIOR DETAIL
Figure 3: Power and Lytemode ILS Network Connections
Step 7. Re-install compartment covers (Figure 2). Step 8. Re-apply house power service.
Lytemode Network Connections (4)
7
SPECIFICATIONS LYTEMODE NETWORK POWERED HUB USERS GUIDE
Specifications
Electrical:
• Input Power: 110-240VAC, 50-60Hz, 3.2 A, 1 Phase
• Output Power: 24VDC, 1.5 A per output (x 4 Separate Outputs)
• Number of Outputs: 4
• Temperature:
- Storage: -25° to 85° C
- Operating: 0° to 40° C
- Relative Humidity: 30-90% (non-condensing)
8
THREE YEAR LIMITED WARRANTY
The Philips Controls product, when properly installed and under normal conditions of use (without overload, abuse or alteration), is warranted to you, the original user, for a period of three years form the date of original retail purchase, to be free from defects in materials and workmanship. If during the warranty period you believe the purchased product or any part thereof has such a defect, you must return the product (or part) at your cost during such period, with proof of purchase (or if installed by a third-party a written explanation of installation transaction with proof of date), to Philips Controls, 2828 Trade Center Dr. Ste. 130B, Carrollton, TX 75007, for repair or replacement (or to an authorized Philips Controls supplier which agrees in advance to handle the return and replacement by factory authorization). If the product or part is found by Philips Controls to have been defective in material or workmanship it will be repaired or replaced (as deemed necessary by Philips Controls), and the replacement will be returned to you free of charge. The original user is solely responsible for any costs associated with removal and re-installation of the product and shipping to Philips Controls or its authorized supplier. PHILIPS CONTROLS LIMITS THE DURATION OF THE IMPLIED WARRANTY OF MERCHANTABILITY WITH RESPECT TO THE PRODUCT TO THE LIMITED WARRANTY PERIOD SET FORTH ABOVE, AND OTHERWISE DISCLAIMS ALL IMPLIED WARRANTIES WITH RESPECT TO THE PRODUCT AND ITS PARTS. Some states disallow certain limitations on implied warranties so you should consult your state law if you have a questions regarding this limitation and disclaimer. Philips Controls disclaims any and all liability for incidental, consequential, special or indirect damage arising out of any claimed breach of warranty or otherwise. However, some states do not allow exclusion or limitation of such damages, so this disclaimer may not apply to you. The remedy provided in the Limited Warranty for defective products is the user’s sole and exclusive remedy, subject to your state law. Further, this Warranty gives the user specific legal rights, and the user may also have other rights which may vary from state to state. If you believe warranty claim is warranted, you may contact your nearest authorized Philips Controls supplier. If one does not exist in your area, please contact Philips Controls Customer Service at the above address (or at 1-800-526-2731), or please visit us at www.lolcontrols.com.