Lightolier H9S2GLR214, H9S2GLR224 User Manual

Features
• 77.1% efficient (2 lamp, 14W).
• 76.5% efficient (2 lamp, 24W).
• Direct/indirect appearance with soft contoured interior.
• Lens encloses lamp compartment.
• Translucent DR acrylic linear prismatic lens.
• Tension screws secure ends to body.
• Fits flush to face of slot grid (T) ceiling types.
• Lamp shield opens from either side.
• 95% reflective specular aluminum reflector.
• Ballast accessible from room side.
• Built-in earthquake clips.
• Can be continuous row mounted.
• Wiring access plate standard.
• Optional DALI ballast i GEN TECHNOLOGY accepts digital dimming controllers, scene controllers and automatic control devices.
• Construction to meet NYC Code or Chicago Plenum available.
Mounting Methods Dimensions
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Volts/Ballast:
11/06
HP90 Recessed Fluorescent H9S2GLR214 or 224
Page 1 of 2 Direct/Indirect – 2' x 2' with Acrylic Linear Prismatic Lens
Static, 2 Lamp T5
24" (610mm)
5"
(127mm)
Lightolier a Genlyte company www.lightolier.com
Technical Information: (978) 657-7600 • Fax (978) 658-0595 631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2006 a Genlyte company
Section 5/Folio M32-15
2-1/2"
(64mm)
2" x 2-1/2" Access Plate with (2) 7/8" dia. K.O.
24" (610mm)
exposed t-grid ceiling
exposed slot t-grid ceiling
Acoustical material by others
Exposed T-bar by others
1-1/2"
max.
Acoustical material by others
15/16"
24"
1-7/8"
max.
Exposed T-bar by others
9/16"
24"
built-in earthquake clips
5" (127mm)
fully enclosed lamp compartment
HP90 Recessed Fluorescent H9S2GLR214 or 224
Page 2 of 2 Direct/Indirect – 2' x 2' with Acrylic Linear Prismatic Lens
Static, 2 Lamp T5
Model No. H9S2GLR214120PG
LER = FP - 58.9 IW - 31.9 BF - 1.0 Comparative yearly lighting energy cost per
1000 lumens = $4.07
Report Number: G2006122 Catalog Number: H9S2GLR214120PG Lamps: F14T5 Luminaire: HP90 2' x 2' with linear
prismatic lens. Ballast: B228PUNV-C Report is based on 1220 Lumens per lamp.
Efficiency: 77.1% CIE Type-Direct-Indirect
Plane: 0-Deg 90-Deg Spacing Criteria: 1.3 1.4 Shielding Angles: 90 90 Plane: 0-Deg 90-Deg Luminous Length: 22.800 22.800
COEFFICIENTS OF UTILIZATION –
ZONAL CAVITY METHOD. EFFECTIVE FLOOR CAVITY REFLECTANCE 0.20
RC 80 50 30
RW 70 50 30 50 30 10 50 30 10
01848077757370727068 02767064656158635956 03696155585248555147 04635447514641494441 05584841464035443935 06544336413531403531 07503933373227363127 08463629342924332824 09433326322622312622
10 41 30 24 29 24 20 28 23 20
LUMINANCE DATA IN CANDELA/SQ. METER
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. 0-DEG. 45-DEG. 90-DEG.
45 1657. 1888. 1922. 55 1517. 1710. 1845. 65 1298. 1629. 1954. 75 1025. 1670. 2050. 85 581. 787. 650.
0
CANDELA DISTRIBUTION
0.0 45.0 90.0 FLUX
0 602 602 602
5 599 604 609 58
15 577 613 642 173
25 535 612 633 275
35 474 548 562 336
45 393 448 456 339
55 292 329 355 295
65 184 231 277 231
75 89 145 178 145
85 17 23 19 29
90 222
ZONAL LUMEN SUMMARY
ZONE LUMENS % LAMP % FIXT
00-030 506 20.7 26.9 00-040 842 34.5 44.7 00-060 1476 60.5 78.5 00-090 1881 77.1 100.0
90-180 0000 0.0 000.0
00-180 1881 77.1 100.0
0
Model No. HP9S2GLR224120PG
LER = FP - 66.5 IW - 47.0 BF - 1.0 Comparative yearly lighting energy cost per
1000 lumens = $3.61
Report Number: G2006116 Catalog Number: HP9S2GLR224120PG Lamps: F24T5 HO Luminaire: HP90 2' x 2' with linear
prismatic lens. Ballast: B224PUNV-C Report is based on 2000 Lumens per lamp.
Efficiency: 76.5% CIE Type-Direct-Indirect
Plane: 0-Deg 90-Deg Spacing Criteria: 1.3 1.4 Shielding Angles: 90 90 Plane: 0-Deg 90-Deg Luminous Length: 22.800 22.800
COEFFICIENTS OF UTILIZATION –
ZONAL CAVITY METHOD. EFFECTIVE FLOOR CAVITY REFLECTANCE 0.20
RC 80 50 30
RW 70 50 30 50 30 10 50 30 10
01837976747269716967 02756964656157625956 03696054575248555047 04635346504540494440 05584841453935443834 06534336413530393430 07493932373127363127 08463529342824332824 09433226312522302521
10 40 30 24 29 23 20 28 23 19
LUMINANCE DATA IN CANDELA/SQ. METER
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. 0-DEG. 45-DEG. 90-DEG.
45 2731. 3035. 3069. 55 2520. 2775. 2957. 65 2285. 2687. 3146. 75 2038. 2810. 3351. 85 1163. 1471. 1197.
0
CANDELA DISTRIBUTION
0.0 45.0 90.0 FLUX
0 955 955 955
5 953 958 966 92
15 934 976 1019 277
25 886 980 1008 443
35 786 878 895 539
45 648 720 728 546
55 485 534 569 479
65 324 381 446 382
75 177 244 291 248
85 34 43 35 53
90 333
ZONAL LUMEN SUMMARY
ZONE LUMENS % LAMP % FIXT
00-030 811 20.3 26.5 00-040 1350 33.8 44.1 00-060 2376 59.4 77.7 00-090 3060 76.5 100.0
90-180 0000 00.0 000.0
00-180 3060 76.5 100.0
0
Ordering Information
Explanation of Catalog Number. Example: H9S2GLR224120PGGLR
HP90
Direct/Indirect
Recessed
H9
HY
HN
S
Body Style:
S = Static
Standard HP90
For NYC Code – I.B.E.W. Manufactured
For NYC Code – Local 3 Manufactured
2
Fixture
Width
G
Ceiling Type:
Fits both
Standard Grid
and
Slot Grid
L
Acrylic Lens Lamp:
Options/Accessories
Fusing: Internal fast blow fusing: SUFFIX: GLR.
Internal slow blow fusing: SUFFIX: GMF. Drywall Kit: Order Catalog Number: FK92X2 . Electrical Wiring Options: Consult factory. For motion or light sensor. See Folio OA20-10..
Specifications
Performance: In an installation of 2 lamp 14W luminaires in a room cavity
ratio of 1, with reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .80. To reduce glare the average brightness at 65° shall not exceed 1954 candelas per square meter. To control veiling reflections, luminaire output in the 30°-90° zone shall not be less than 73.1%.
Materials: Chassis parts are die-formed code gauge steel. Lamp Shield: Linear prismatic translucent DR acrylic lens. Finish: Chassis exterior – baked white acrylic enamel. Cavity – baked flat
white acrylic enamel. Phosphate undercoating. Reflector – low iridescence specular aluminum .95% reflectance.
R
Reflector:
Specular
Aluminum
2
Lamp
Quantity 2=2 Lamp
(By Others)
14=T5 14W 24=T5HO 24W
(Nominal 24")
Voltage:
120, 277 or
UNV=120-277
Ballast Type:
2 Lamp Elec. T5 PG ††
(14 Watt)
2 Lamp Elec. T5HO PG ††
(24 Watt)
††Program Rapid Start (UNV only)
<20THD <10THD
Specifications (continued)
Electrical: Thermally protected class “P’ ballast C.B.M. approved, non PCB. If
K.O. is within 3" of ballast, use wire suitable for at least 90°. UL Listed for damp locations. Labels: I.B.E.W./UL and ULc Listed. This product may have a mercury containing lamp. Manage in accord with Disposal Laws. See: www.lamprecycle.org
Job Information Type:
Lightolier a Genlyte company www.lightolier.com
Technical Information: (978) 657-7600 • Fax (978) 658-0595 631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2006 a Genlyte company
Section 5/Folio M32-15
Options:
Add appropriate suffix to catalog
no., ie: (GLR)
Loading...