Lightolier FBP33 User Manual

FBP Series Fluorescent Emergency Ballast FBP33
Page 1 of 1 Three Parallel Lamps Operation 3,400 Lumens
The FBP Series quickly converts standard fluorescent luminaires into emergency luminaires.
16.3”
(41.4 cm)
Nickel Cadmium Battery
Complete Fixture consists of ballast unit. Select options and accessories below.
5.6”
(14.2 cm)
Model # Max. Lumens Lamp Operation
FBP33 3,400 Two or Three
1.7”
(4.3 cm)
Features
1. Lamp Operation: Operates the following lamp types: T8 linear fluorescent,
and T5 long compact fluorescent. See Lamp Operation and Performance
table for specific lamp per formance and operation.
2. Illumination: Provides 90 minutes of emergency illumination, and produces a maximum of 3400 initial lamp lumens when used to power two or three 32W (4’) T8 fluorescent lamps, two or three 39W T4, or two 40 - 55W t4-4 pin long compact fluorescent lamps. Any non-emergency AC ballast used in conjunction with the FPB33 MUST be an instant start, parallel output 2, 3, or 4 lamp regular or dimming type ballast.
3. Housing: Constructed of 20 gauge steel with a white high temperature pow­der coat paint finish. Slim housing allows for wireway channel mounting on most recessed luminaires.
4. Electronics: 120/277 VAC dual voltage input with surge-protected, solid­state circuitry. Charging system is complete with AC indicator lamp and test
switch.
5. Battery: Maintenance free, sealed nickel cadmium battery has an estimated service life of 10 years, and an operating temperature range of 32°F (0°C) to 131°F (55°C).
6. Input Power Requirements: 8 watts max.
7. Warranty: Electronics: 5 years; Bat ter y: 5 years
Code Compliance
UL 924 listing pending.
Options
EX = Special Input Transformer for 220 VAC/50 Hz, 240 VAC/50Hz. Contact fac-
tory for other input voltages and frequencies.
Accessories
CCAPS = Wire bundle cover for mounting external to luminaire.
RTS = Single gang aluminum faceplate pre-drilled to accommodate remote
installation of test switch and pilot.
Lamp Operation and Performance
Non-Emer. Emer. Op.
Max. Max. Emer. Lamp Base Lumen Lumen Lamp Type Watt. Type Output Output Operation
F32T8 32 G13/Med Bi-Pin 2850 3400 Two or Three
F39/36BX 39 2G11/4--Pin 2850 3200 Two or Three
F40/30BX 40 2G11/4--Pin 3150 3200 Two
F50BX/FT55 50-55 2G11/4--Pin 4300-4800 3300 Two
Notes:
1. Maximu m non-emer gency lume n output c an vary ba sed on lamp manufact urer, ambient o perating tempe rature, an d ballast ma nufactur er.
2. Maximu m emergenc y lumen out put is base d on total output of one or two lamps, and c an vary base d on lamp manu facture r and ambien t operatin g temperat ure.
3. Maximu m emergenc y lumen out put is supp orted fo r a full 90 min utes of op eration.
4 Cons ult factor y for com patibility, o peration a nd perfor mance of l amp type s not liste d.