FBP Series Fluorescent Emergency Ballast FBP30T
Page 1 of 1 One or Two Lamp Operation 3,500 Lumens
The FBP Series quickly converts standard fluorescent luminaires into emergency luminaires.
16.3”
(41.4 cm)
Nickel Cadmium Battery
Complete Fixture consists of ballast unit. Select options and accessories below.
5.6”
(14.2 cm)
Model # Max. Lumens Lamp Operation
FBP30T 3,500 One or Two
1.7”
(4.3 cm)
Features
1. Lamp Operation: Operates the following lamp t ypes: T8 linear fluores-
cent, T12 linear fluorescent, T9 circline, T12 U-bent, T5 long compact fluorescent, compact 4-pin fluorescent. See Lamp Operation and Performance
table for specific lamp per formance and operation.
2. Illumination: Provides 90 minutes of emergency illumination, and produces a maximum of 3,500 lumens initial emergency light output. Can be used
with most 17w to 215w (2’ - 8’) T8, T10 or T12 fluorescent lamps without
integral starters including U-shaped, HO, VHO, circline, energy saving, and
4 pin compacts. It is also compatible with most 1, 2, 3 and 4-lamp electronic, standard, energy saving and dimming AC ballasts, including those
with end of life detection.
3. Housing: Constructed of 20 gauge steel with a white high temperature
powder coat paint finish. Slim housing allows for wireway channel mounting on most recessed luminaires.
4. Electronics: 120/277 VAC dual voltage input with surge-protected, solidstate circuitry. Charging system is complete with AC indicator lamp and
test switch.
5. Battery: Maintenance free, sealed nickel cadmium battery has an estimated service life of 10 years, and an operating temperature range of 32°F
(0°C) to 131°F (55°C).
6. Input Power Requirements: 8 watts max.
7. Warranty: Electronics: 5 years; Bat ter y: 5 years.
Code Compliance
UL 924 listed.
Options
EX = Special Input Transformer for 220 VAC/50 Hz, 240 VAC/50Hz. Contact
factory for other input voltages and frequencies.
DL = UL Damp Location Listing
Lamp Operation and Performance
Non-Emer. Emer. Op.
Op. Max. Max. Emer.
Lamp Watt. Non-Emer. Lumen Lumen Lamp
Type Type Base Output
F40/34T12 34-40 G13/Med Bi-Pin 2900 3000 One or Two
F40T12/U 40 G13/Med Bi-Pin 3100 3000 One or Two
F48T12HO 60 R17D/Recessed 4050 3000 One
F96T12HO/VHO 95-215 R17D/Recessed 8800/15200 3000 One
F25T8 25 G13/Med Bi-Pin 2200 2500 One or Two
F32T8 32 G13/Med Bi-Pin 3000 3000 One or Two
F32T8/U 32 G13/Med Bi-Pin 2700 3000 One or Two
F40T8 40 G13/Med Bi-Pin 3700 2500 One
F96T8 59 FA8/Single-Pin 5700 3000 One
F39/36BX 39 2G11/4--Pin 2900 3000 One or Two
F40/30BX 40 2G11/4--Pin 3200 2000 One
F42TBXT4 42 GX24Q-4P 3200 3200 One or Two
Notes:
1. Maxim um non-eme rgency lum en output can vary b ased on lam p manufac turer, ambien t operatin g
tempe rature, an d ballast ma nufactur er.
2. Maxim um emergen cy lumen ou tput is bas ed on tot al output o f one or tw o lamps, and can vary
base d on lamp manu facture r and ambien t operatin g temperat ure.
3. Maxim um emergen cy lumen ou tput is sup ported f or a full 90 minutes of o peration.
4. Consul t factor y for comp atibility, op eration an d perfor mance of la mp types not listed.
Output
Operation
Accessories
CCAPS = Wire bundle cover for mounting external to luminaire.
RTS = Single gang aluminum faceplate pre-drilled to accommodate remote
installation of test switch and pilot light.
Lightolier is a Philips group brand
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group • D0708