Lightolier FBP100, FBP100FE User Manual

FBP Series Fluorescent Emergency Ballast FBP100FE
Page 1 of 1 One Lamp Operation 350 - 450 Lumens
The FBP Series quickly converts standard fluorescent luminaires into emergency luminaires.
9.4”
(23.9 cm)
2.4”
Nickel Cadmium Battery
(6.1 cm)
Complete Fixture consists of ballast unit. Select options and accessories below.
Model # Max. Lumens Lamp Operation
FBP100 450 One
Lamp Operation and Performance
LAMP WATTAGE BASE MAX. LUMEN MAX. LUMEN EMERGENCY TYPE TYPE OUTPUT OUTPUT LAMP OPERATION
F20T12 20 G13/Med Bi-Pin 1275 350 - 450 One
F30T12 30 G13/Med Bi-Pin 2350 350 - 450 One
F40T12 40 G13/Med Bi-Pin 2650 350 - 450 One
F40T12/U 40 G13/Med Bi-Pin 3100 350 - 450 One
F48T10 110 R17D/Recessed 6200 350 - 450 One
F17T8 17 G13/Med Bi-Pin 1350 350 - 450 One
F25T8 25 G13/Med Bi-Pin 2150 350 - 450 One
F32T8 32 G13/Med Bi-Pin 2950 350 - 450 One
F32T8/U 32 G13/Med Bi-Pin 2700 350 - 450 One
F40T8 40 G13/Med Bi-Pin 3725 350 - 450 One
FC6T9 20 G10Q/4 Pin 800 350 - 450 One
FC8T9 22 G10Q/4 Pin 1100 350 - 450 One
FC12T9 32 G10Q/4 Pin 1950 350 - 450 One
FC16T9 40 G10Q/4 Pin 2700 350 - 450 One
F39/36BX 39 2G11/4 Pin 2850 350 - 450 One
F40/30BX 40 2G11/4 Pin 3150 350 - 450 One
NON-EMERGENCY EMERGENCY OP.
1.5”
(3.8 cm)
NOTES:
1. Maxim um non-eme rgency lum en output can vary base d on lamp manu facture r, ambi ent operat ing tempe rature, an d ballast ma nufactur er.
2. Maxim um emergen cy lumen ou tput is ba sed on tot al outp ut of one or two lamps, and can var y based o n lamp ma nufactur er and ambie nt operat ing temper a­ture.
3. Maxim um emergen cy lumen ou tput is sup ported f or a full 9 0 minutes o f operatio n.
4. Consul t factor y for comp atibility, op eration an d perf ormance o f lamp ty pes not list ed.
Features
1. Lamp Operation: Operates the following lamp t ypes: T8 linear fluo-
rescent, T12 linear fluorescent, T9 circline, T12 U-bent, T5 long compact fluorescent. See Lamp Operation and Performance table for specific lamp
performance and operation.
2. Illumination: Provides 90 minutes of emergency illumination, and pro­duces 350-450 lumens initial emergency light output. Can be used with most 17w to 40w (2’ - 4’) T8, T10 or T12 fluorescent lamps without integral starters including U-shaped, HO, VHO, circline, energy saving, and 4 pin compacts. It is also compatible with most 1, 2, 3 and 4-lamp electronic, standard, energy saving and dimming AC ballasts.
3. Housing: Constructed of 20 gauge steel with a white, high temperature powder coat paint finish. Slim housing allows for wireway channel mount­ing on most recessed luminaires.
4. Electronics: 120/277 VAC dual voltage input with surge-protected, solid­state circuitry. Charging system is complete with AC indicator lamp and
test switch.
5. Battery: Maintenance free, sealed nickel cadmium bat tery has an esti­mated service life of 10 years, and an operating temperature range of 32°F (0°C) to 131°F (55°C).
6. Input Power Requirements: 3.5 watts max.
7. Warranty: Electronics: 1 year; Bat tery: 1 year.
Code Compliance
U.L. 924 listed.
Lightolier is a Philips group brand
Options
EX = Special Input Transformer for 220 VAC/50 Hz, 240 VAC/50Hz. Contact
factory for other input voltages and frequencies.
Accessories
CCAPS = Wire bundle cover for mounting external to luminaire.
RTS = Single gang aluminum faceplate pre-drilled to accommodate remote
installation of test switch and pilot light.
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group • B0308