READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE
®
This fixtur
regulations. To assure full compliance with local codes and regulations, check with your local electrical
inspector before installation. To prevent electrical shock, turn off electricity at fuse box before proceeding.
e is intended for installation in accordance with the National Electrical Code and local
Retain these instructions for maintenance reference.
I
NSTRUCTION SHEET NO.
IS:FAEM3
C0506Page 1of 4
Installation of Compact Fluorescent Emergency Ballast Accessory FAEM3E to
Standard Calculite Four-Pin Electronic Compact Fluorescent Lamp Frame-In Kit
IMPORTANT SAFEGUARDS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD BE FOLLOWED INCLUDING THE FOLLOWING:
1. TURN OFF AC POWER BEFORE PROCEEDING.
2. DO NOT INSTALL INSULATION WITHIN 3 INCHES OF FIXTURE SIDES OR WIRING COMPARTMENT, NOR ABOVE FIXTURE IN SUCH A MANNER AS TO ENTRAP HEAT.
3. BE SURE ALL ELECTRICAL CONNECTIONS ARE COMPLETE AND THE JUNCTION BOX IS CLOSED BEFORE INVERTER
CONNECTORS (LOCATED IN THE SWITCH/INDICATOR LIGHT BOX) ARE CONNECTED.
4. DO NOT USE OUTDOORS.
5. DO NOT LET POWER SUPPLY CORDS TOUCH HOT SURFACES.
6. DO NOT MOUNT NEAR GAS OR ELECTRICAL HEATERS.
7. USE CAUTION WHEN SERVICING BATTERIES. CONTAINS NICKEL-CADMIUM RECHARGEABLE BATTERY. MUST BE
RECYCLED OR DISPOSED OF PROPERLY. DO NOT SHORT CIRCUIT; MAY CAUSE BURNS.
8. EQUIPMENT SHOULD BE MOUNTED IN LOCATIONS AND AT A HEIGHT WHERE IT WILL NOT READILY BE SUBJECT TO
TAMPERING BY UNAUTHORIZED PERSONNEL.
9. THE USE OF ACCESSORY EQUIPMENT NOT RECOMMENDED BY THE MANUFACTURER MAY CAUSE AN UNSAFE
CONDITION.
10. DO NOT USE THIS EQUIPMENT FOR OTHER THAN INTENDED USE.
11. THIS UNIT HAS MORE THAN ONE POWER SUPPLY CONNECTION POINT. TO REDUCE THE RISK OF ELECTRICAL SHOCK,
DISCONNECT BOTH NORMAL AND EMERGENCY POWER SUPPLIES BEFORE SERVICING.
12. BEFORE SERVICING TO PREVENT ELECTRICAL SHOCK, DISCONNECT THE INVERTER CONNECTORS OF THE EMERGENCY BATTERY PACK (LOCATED IN THE SWITCH/INDICATOR LIGHT BOX). MAKE CERTAIN THAT THE SWITCHED (IF
THE FIXTURE IS SWITCHED) AND THE UNSWITCHED LINE TO THE EMERGENCY BATTERY PACK ARE TURNED OFF AT
THE FUSE BOX. SER
13. BEFORE ANY INSTALLATION, MAKE SURE TO CHECK THE COMPATIBILITY MATRIX BELOW BEFORE INSTALLATION.
INCORRECT MATCHING MAY CAUSE ELECTRICAL SHOCK AND DAMAGE TO BALLASTS AND LAMPS. FOR USE WITH
NON-DIMMING (U SERIES) AND DIMMING (J-SERIES) FRAME-IN KITS.
VICING SHOULD BE PERFORMED BY QUALIFIED SER
VICE PERSONNEL ONLY.
Emergency BallastLampWattageCompatible Ballast
13W
Electroninc Non-Dimming
Advance Mark 7 and Mark 10 (Dimming)
Lutron compact SE, Hi-Lume,
TU-Wire (Dimming)
A-EM3E
F
Quad Tube 4-Pin
Triple Tube 4-Pin
18W
26W
18W
26W
32W
42W
SAVE THESE INSTRUCTIONS
LIGHTOLIER a GENLYTE THOMAS company.
631 Airport Road, Fall River, MA 02720
INSTRUCTION SHEET NO.
®
VIOLET
TAN
Y
Y
WHT /
BLK
ELECTRONIC
A.C. BALLAST
LAMPHOLDER
BLK 120V
WHITE
ORG / BLK
WHITE*
W
B
G
B
B
R
R
RED
BLUE**
WHT / RED
WHT/BLK
RED*
RED
YEL/BLK
BLUE/WHT
WHITE
RED
YEL
TEST
ORG/BLK
ORG 277V
VIOLET +
INVERTER
LIGHT
CHARGE
CONNECTOR
RED
WHITE
BROWN -
BLACK
SWITCH
EMERGENCY
BALLAST
RED**
BLUE**
BLUE
BLACK
FLEX
"B"
FLEX
"A"
GROUND
UNSWITCHED
120V OR
277V
GREEN
WALL
SWIT
CH
COMMON
(NETURAL)
STAB-IN CONNECTOR (2 CONDUCTORS)
STAB-IN CONNECTOR (3 CONDUCTORS)
* WHITE AND RED JUMPERS PROVIDED
** (2) BLUE AND (1) RED LEADS REMOVED
FROM ELECTRONIC BALLAST
JUNCTION
BOX
For di
mming ballast, connect
dimming leads to dimmer
SWITCH BOX
COMMON
(NETURAL)
WALL
SWITCH
GREEN
UNSWITCHED
120V OR
277V
GROUND
FLEX
"A"
FLEX
"B"
BLACK
BLUE / WHT
BLUE**
RED
BALLAST
EMERGENCY
SWITCH
BLACK
BROWN -
WHITE
RED
CONNECTOR
CHARGE
LIGHT
INVERTER
VIOLET +
ORG
277V
ORG/BLK
TEST
YEL
BLUE / WHT
WHITE
BLUE
YEL/BLK
RED
BLUE
WHT/BLK
WHT / RED
BLUE**
RED
R
R
B
B
G
B
W
WHITE*
ORG / BLK
WHITE
BLK 120V
LAMPHOLDER 2
ELECTRONIC
A.C. BALLAST
WHT / BLK
Y
Y
YELLOW*
YELLOW
RED
RED
YEL**
YEL
* WHITE AND YELLOW JUMPERS PROVIDED
** (2) BLUE AND (1) RED LEADS REMOVED
FROM ELECTRONIC BALLAST
STAB-IN CONNECTOR (3 CONDUCTORS)
STAB-IN CONNECTOR (2 CONDUCTORS)
LAMPHOLDER 1
(EMERGENCY)
For di
mming ballast, connect
dimming leads to dimmer
JUNCTION
BOX
SWITCH BOX
READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE
This fixture is intended for installation in accordance with the National Electrical Code and local
regulations. To assure full compliance with local codes and regulations, check with your local electrical
IS:FAEM3
C0506Page 2of 4
inspector before installation. To prevent electrical shock, turn off electricity at fuse box before proceeding.
Retain these instructions for maintenance reference.
NEW INSTALLATION
A. INSTALLING EMERGENCY BALLAST TO STANDARD FRAME-IN KIT (Fig. 1 and 8).
1. Before placing FRAME-IN KIT in the ceiling, install EMERGENCY BALLAST to the center
of MOUNTING FRAME BRACKET as shown.
2. Tighten SCREW to secure two units together.
3. Remove JUNCTION BOX COVER and appropriate J-Box K.O., then attach
EMERGENCY BALLAST BX CONNECTOR.
WIRING - Read and understand all instructions before proceeding.
• Make sure AC power is off at the fuse box.
• Regular ballast and emergency ballast must be fed from the same branch circuit.
• Be sure all electrical connections are made and junction box is closed before
connecting inverter connectors in switch/indicator light box.
In switched fixtur
•
• Emergency ballast is shipped from the factory ready for 120V or 277V supply connection.
Line Voltage selecton is made at switch box. For 120V, remove wire nut from 120V
lead (black) and connect to black lead of test switch, then cap the 277V lead (orange).
B. INSTRUCTIONS FOR WIRING EMERGENCY BALLAST FOR (1)
OR (2) 4-PIN LAMPS ELECTRONIC A.C. BALLAST FRAME-IN KIT
1. Before converting to emergency lighting, please identify no. of lamps and wattage of
frame-in kit, then select appropriate Wiring Diagram A, B or C for rewiring. There is a
requirement to remove lamp leads from A.C. ballast, and reconnect to emergency ballast.
2. Disconnect either BLUE LAMP LEAD from BALLAST by inserting conductor of RED JUMPER
(provided) into open terminal of QUICK CONNECTOR of BALLAST as shown in Fig. 2.
Gently pull BLUE LAMP LEAD out. Then remove RED JUMPER for later use.
3. Repeat step 2 (above) to remove other BLUE LAMP LEAD, and one appropriate RED OR
YELLOW LAMP LEAD from BALLAST (Fig. 2) and wiring diagrams.
4. Insert appropriate RED OR YELLOW JUMPER into the terminal where the RED
OR YELLOW
5. Follow WIRING DIAGRAM A, or B, or C to complete the wiring at FLEX “A”.
es, emergency ballast must be connected ahead of any local switching.
LAMP LEAD was previously removed from QUICK CONNECTOR (Fig. 3).
Fig. 1
FRAME-IN KIT
BX
CONNECTOR
J-BOX
COVER
Fig. 2
RED LAMP
LEADS
Fig. 3
RED
JUMPER
SOCKET
CUP
BLUE LAMP
LEADS
INSERT
INSERT
EMERGENCY
BALLAST
MOUNTING
FRAME
BRACKET
SWITCH/
TOR
INDICA
BRACKET
SCREW
RED
JUMPER
QUICK
CONNECTOR
QUICK
CONNECTOR
WIRING DIAGRAM A
(1 LAMP EMERGENCY)
NOTE: FOR UNSWITCHED CIRCUIT, CONNECT
BOTH WHITE/RED AND ORANGE/BLACK LEADS
IN JUNCTION BOX TO UNSWITHCHED 120V
OR 277V. VOLTAGE SELECTION IS MADE IN
SWITCH BOX.
(1-LAMP FIXTURE)
WIRING DIAGRAM B (2-LAMP FIXTURE) UP TO 2-42W
(1 LAMP EMERGENCY)
NOTE: FOR UNSWITCHED CIRCUIT, CONNECT
BOTH WHITE/RED AND ORANGE/BLACK LEADS
IN JUNCTION BOX TO UNSWITHCHED 120V
OR 277V. VOLTAGE SELECTION IS MADE IN
SWITCH BOX.
LIGHTOLIER a GENLYTE THOMAS company.
631 Airport Road, Fall River, MA 02720
READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE
®
LAMPHOLDER 1
(EMERGENCY)
STAB-IN CONNECTOR (2 CONDUCTORS)
STAB-IN CONNECTOR (3 CONDUCTORS)
* WHITE AND RED JUMPERS PROVIDED
** (2) BLUE AND (1) RED LEADS REMOVED
FROM ELECTRONIC BALLAST
YEL
YEL
RED
RED*
YEL
LOW
YELLOW
Y
Y
WHT / BLK
ELE
CTRONIC
A.C.
BALLAST
LAMPHOLDER 2
BLK 1
20V
WHITE
ORG / BLK
WHITE*
W
B
G
B
B
R
R
RED
BLUE**
WHT / RED
WHT/BLK
BLUE
RED
YEL
/BLK
BLUE
WHITE
BLU
E / WHT
YEL
TEST
ORG/BL
K
ORG 277V
VIOLET +
INVERTER
LIGHT
CHARGE
CON
NECTOR
RED
WHITE
BROWN -
BLACK
SWITCH
EMER
GENCY
BALLAST
RED**
BLUE**
BLU
E / WHT
BLACK
FLE
X
"B"
FLE
X
"A"
GROUND
UNSWIT
CHED
120V
OR
277
V
GREEN
WALL
SWITCH
COMM
ON
(NETURAL)
TAN
VIOLET
For dimming ballast, connect
dimming leads to dimmer
JUNCTION
BOX
SWITCH BOX
This fixture is intended for installation in accordance with the National Electrical Code and local
regulations. To assure full compliance with local codes and regulations, check with your local electrical
inspector befor
e installation. To prevent electrical shock, turn off electricity at fuse box before proceeding.
Retain these instr
uctions for maintenance reference.
WIRING DIAGRAM C (2-LAMP FIXTURE) UP TO 2-26W
(2 LAMP EMERGENCY)
I
NSTRUCTION SHEET NO.
IS:FAEM3
C0506Page 3of 4
NOTE: FOR UNSWITCHED CIRCUIT
BOTH WHITE/RED AND ORANGE/BLACK LEADS
IN JUNCTION BOX TO UNSWITHCHED 120V
OR 277V. VOLTAGE SELECTION IS MADE IN
SWITCH BOX.
, CONNECT
C.
D. WIRE-IN
E. CLOSE-IN
ALL MOUNTING FRAME TO CEILING SUPPOR
INST
(See separate frame-in kit instruction sheet).
Connect supply leads to emergency ballast, electronic
ballast and fixtur
DIAGRAM A, B, or C. Cap unused lead. Close the
junction box cover after wiring is completed.
1. Cut appropriate hole size in ceiling for frame.
2. Cut hole in ceiling for SWITCH/INDICATOR LIGHT BOX
3. Close-in ceiling.
in a convenient location to the side of frame (Fig. 4).
ecommended hole size is 2-5/8” x 3-3/4”.
The r
ound wire as shown in WIRING
e gr
T MEMBERS
Fig. 4
SCREWS
INVERTER
CONNECTORS
SWITCH/INDICATOR
LIGHT BOX
LIGHTOLIER a GENLYTE THOMAS company.
631 Airport Road, Fall River, MA 02720
I
®
NSTRUCTION SHEET NO.
IS:FAEM3
B0500Page 4of 4
CLOSE-IN (CONT.)
E.
READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE
This fixture is intended for installation in accordance with the National Electrical Code and local
egulations. To assure full compliance with local codes and regulations, check with your local electrical
r
inspector befor
e installation. To prevent electrical shock, turn off electricity at fuse box before proceeding.
Retain these instructions for maintenance reference.
4. Pull down SWITCH/INDICATOR LIGHT BOX and clamp onto ceiling by
tightening SCREWS on side of BOX (Fig. 4).
5. Connect INVERTER CONNECTORS in SWITCH/INDICATOR LIGHT BOX
(Fig. 4).
6. Fasten TRIM PLATE to SWITCH/INDICATOR LIGHT BOX with LOCK
NUT (Fig. 5).
F. ADJUST MOUNTING FRAME
1. Set MOUNTING FRAME so the bottom edge is flush with finished ceiling (Fig. 6).
Note: Final vertical adjustment can be made with MOUNTING
BRACKET SCREWS (Fig. 7) on inside of MOUNTING FRAME.
G. OPERATION
When AC power is applied, the charging indicator light is illuminated indicating that the battery is being charged. When the power fails, the emergency lighting ballast automatically switches to emergency operation,
keeping one lamp illuminated at reduced output for 90 minutes.
H. MAINTENANCE
Although no routine maintenance is required to keep emergency lighting
ballast functional, it should be checked periodically to ensure that it is
working. The following schedule is recommended:
1. Visually inspect the charging indicator light monthly. It should be
illuminated.
2. Test the emergency operation of fixture once every 3 months. One
lamp should operate at reduced output.
3. Conduct a 90 minute discharge test once a year. One lamp should
operate at reduced output for 90 minutes.
I. EMERGENCY BALLAST REPLACEMENT
1. Make sure AC power is off at fuse box.
2. Remove REFLECTOR (see reflector trim instruction sheet).
3. Remove TRIM PLATE by removing LOCKNUT (see Fig. 5); disconnect
INVERTER CONNECTORS, loosen SCREW on side of SWITCH BOX
and slip SWITCH BOX onto the ceiling.
Loosen SCREW away from EMERGENCY BALLAST ASSEMBLY (Fig. 8).
4.
5. Pull EMERGENCY BALLAST off MOUNTING BRACKET and down
through the frame opening (Fig. 9).
6. Unscrew and disassemble defective EMERGENCY BALLAST from
SWITCH BOX and JUNCTION BOX.
Replace with new
7.
EMERGENCY BALLAST
. Follow wiring diagram and
instruction procedure as stated in this Instruction Sheet.
EXISTING INSTALLATION
NOTE:
Emergency ballast kit may be installed after the frame-in kits
and ceilings ar
may be easier to install the emergency ballast from above
e finished. If ceiling is accessible fr
om above, it
.
• EMERGENCY BALLAST INSTALLATION FROM ABOVE:
Follow installation instructions in Step A, B, D and E.
• EMERGENCY BALLAST INSTALLATION FROM BELOW:
1. Make sure AC power power is off at fuse box.
eflector trim instruction sheet).
2. Remove REFLECTOR
(see r
3. Install EMERGENCY BALLAST to the center of MOUNTING
FRAME BRACKET as shown in Fig. 1 and 9.
4. Go to step A, B, D and E.
Fig. 5
Fig. 6
Fig. 7
Fig. 8
Fig. 9
MOUNTING BAR,
OR CHANNELS,
EMT
MOUNTING
BRACKET
EMERGENCY
BALLAST
MOUNTING
BRACKET
MOUNTING
FRAME
TRIM PLATE
LOCK NUT
MOUNTING
FRAME
MOUNTING
FRAME
SCREW
SCREW
MOUNTING
FRAME
EMERGENCY
BALLAST
LIGHTOLIER a GENLYTE THOMAS company.
631 Airport Road, Fall River, MA 02720