Lightolier EC1-5 User Manual

Lighting Systems EC1-5
Coverage Diameter
Sensor Height AFF
Energos Occupancy Sensor
Coverage Zone Chart
16' 0" 14' 5"
12' 10"
11' 3"
7' 0"
8' 0"
9' 0"
10' 0"
Page 1 of 3 Energos Control System 2-Light T5 per 4' (121.92cm) (Nominal) Louver
Feature Specifications – Energos Control System (For standard Energos fixtures consult appropriate EG spec sheets)
Feature Specifications
Electrical
Dedicated low voltage (24 VDC) circuit controls the Energos Control Systems. The line voltage circuits control all the standard ballast functions including A/B switch­ing, Dimming and Emergency Battery Pack operations.
Occupancy Sensors:
• Time delay is factory pre-set to 30 minutes.
• Time delay can be field adjusted from 30 minutes to a minimum of 30 seconds.
• Daylight hold-off is factory pre-set to 120 ft-candles (1291.67m-candles).
• Daylight hold-off is field adjustable from 120 ft-candles (1291.67m-candles) down to 10 ft-candles (107.64m-candles).
• Sensors are designed for a detection area (sensitivity diameter) of 16' (487.68cm) when suspended 10' (304.80cm) AFF. Lowering the sensor produces
a smaller area of detection. See chart and diagram for additional information.
ECS occupancy sensors are available in two variations:
• Mounted in the end cap.
• The middle of an 8" (243.84cm) module.
The ECS system control-center is the Power Pack. The Power Pack, contained in each Master Module, interrupts the circuits when parameters dictate. The Power Pack can control up to 600 watts 120 VAC, and 1300 watts 277 VAC. A maximum of 10 sensors can be used on a single Power Pack. There is no limitation to the number of Power Packs that can be "daisy-chained" to a single ECS circuit.
Emergency battery packs can be used in conjunction with ECS for emergency egress lighting since all listed packs operate for a minimum of 90 minutes. EM Packs can be used as momentary lighting for emergency circuit for power transitions, and smaller packs are recommended for this purpose.
Dimming ballasts can be used in conjunction with ECS. However, the control system will only perform ON or OFF operations and will not affect the level of dim­ming set by the dimming ballasts.
Factory installed ballast disconnect allows the ballast to be disconnected from and reconnected to incoming power under load without turning the entire circuit off.
Serial Row Linking (SRL) provides multiple continuous row communication. For every run that SRL is required, order the appropriate SRL end set from page 2 of this Specification Sheet. Consult Energos Application Guide for more detailed definitions and examples.
Mountings
Cable suspension distances are on 48" (121.92cm) and 96" (243.84cm) centers, and consist of a 4 1/2" (11.43cm) diameter canopy finished white enamel. A 1/16" (0.16cm) diameter stainless steel aircraft cable accomplishes suspension and is adjustable from 12" (30.48cm) to 36" (91.44cm). Power feeds are 18 gauge silver braided cord with clear jacket.
1. End Cap Sensor Mounting 2. Mid-mounted 8' (243.84cm) Sensor Mounting
Height of Sensor Broadcast Diameter Task Diameter
10' 0" (304.80cm) 16' 0" (487.68cm) 8' 0" (243.84cm)
9' 0" (274.32cm) 14' 5" (427.99cm) 7' 3" (214.12cm) 8' 0" (243.84cm) 12' 10" (391.16cm) 6' 5" (184.15cm) 7' 0" (213.36cm) 11' 3" (336.04cm) 5' 7" (154.18cm)
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group •
C0808
Lighting Systems EC1-5
Page 2 of 3 Energos Control System 2-Light T5 per 4' (121.92cm) (Nominal) Louver
Control Ordering Information
Family Series Lamping &
Distribution
EC 1
2 = 2 lamp,
open top
5 = 2 lamp,
slotted top reflector
See Chart on Page 3
Lamp
See Chart on Page 3
ShieldingBallast
P
P = Parabolic
Louver
4 = 4' (121.92cm) 8 = 8' (243.84cm)
VoltageLength
6 = 120 Vac Master 7 = 277 Vac Master 8 = 120 Vac Slave 9 = 277 Vac Slave
Finish
A = Aluminum W= White
Options (Blank)
4 = 4 through wires 5 = 5 through wires 6 = 6 through wires D = Dual Switch T = Tandem Switch E = Emergency
Ordering Instructions
End Cap ECS Systems
1. Order Master 4' (121.92cm) or 8' (243.84cm) ECS Module.
2. Order Power Feed End Set.
ECS Sensor Sample Runs
4' Run: 4' (121.92cm) Master Module with Single Sensor End Set.
8' Run: 8' (243.84cm) Master Module and standard Energos End Set.
8' Run: 8' (243.84cm) Master Module and Dual Sensor End Set.
12' Run: 8' (243.84cm) Master Module, 4' (121.92cm) Slave Module, Dual
Sensor End Set, and Intermediate Cable Assembly.
Continuous Row Mounted ECS Systems:
1. Determine run length
2. Order a minimum of one master per run. Please see Application Guide for master requirements on runs that exceed 16' (487.68cm).
3. Order the required remaining Master and Slave modules to complete the run.
4. Order Power Feed End Set.
5. Order one CABLE ASSEMBLY per MODULE minus one per run.
6. Order additional Single Cable & Cord Sets for every Master Module in run.
ECS End Sets
Single Sensor
End Set EC1SE36W
Single Sensor SRL
End Set EC1SR36W
Dual Sensor End Set EC1DE36W
Dual Sensor SRL End Set EC1DR36W
Single Cable & Power Cord EGCC36
16' Run: 8' (243.84cm) Master Module, 8' (243.84cm) Slave Module, standard Energos End Set, and Intermediate Cable Assembly.
16' Run: 8' (243.84cm) Master Module, 8' (243.84cm) Slave Module, Single Sensor End Set, and Intermediate Cable Assembly.
16' Run: 8' (243.84cm) Master Module, 8' (243.84cm) Slave Module, Single Sensor End Set, and Intermediate Cable Assembly.
Notes:
1. See page 1 of Specification Sheet or consult Application Guide for the definition of Serial Row Linking (SRL).
2. Consult the matching EG specification sheet for Luminaire related specifications (i.e. Housing materials, shielding, mounting dimensions, and photometry).
Standard End Set EG1EC36W
SRL Standard
End Set EC1ER36W
Job Information Type:
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group •
C0808
Lighting Systems EC1-5
Page 3 of 3 Energos Control System 2-Light T5 per 4' (121.92cm) (Nominal) Louver
Ballast Ordering Information
Design Lamp Type Ballast Factor Start Type THD %
F T5 1.00 Program <10
G T5HO 1.00 Program <10
I Dim T5 1.00 / .01 Program <10
J Dim T5HO 1.00 / .03 Program <10
Lamp and Ballast System Data
Design
*25°C Rating All data is per 1 lamp on a two lamp system at 277 VAC.
Lamp Type
(T8 or T5)
FM T5 1 <10 28 2600 3000 2600 31.0 83.87 20000 Program
FN T5 1 <10 28 2600 3500 2600 31.0 83.87 20000 Program FO T5 1 <10 28 2600 4100 2600 31.0 83.87 20000 Program GP HO 1 <10 54 4450 3000 4450 58.5 76.07 20000 Program
GQ HO 1 <10 54 4450 3500 4450 58.5 76.07 20000 Program
GR HO 1 <10 54 4450 4100 4450 58.5 76.07 20000 Program IM T5 DIM 1.0 / .01 <10 28 2600 3000 2600 / 26 33.5 / 8 77.60 NA Program IN T5 DIM 1.0 / .01 <10 28 2600 3500 2600 / 26 33.5 / 8 77.60 NA Program
IO T5 DIM 1.0 / .01 <10 28 2600 4100 2600 / 26 33.5 / 8 77.60 NA Program
JP T5HO DIM 1.0 / .03 <10 54 4450 3000 4450 / 134 63 / 12.5 70.60 NA Program
JQ T5HO DIM 1.0 / .03 <10 54 4450 3500 4450 / 134 63 / 12.5 70.60 NA Program JR T5HO DIM 1.0 / .03 <10 54 4450 4100 4450 / 134 63 / 12.5 70.60 NA Program
Ballast
Factor (BF)
Ballast
THD (%)
Lamp Rated
Wattage
Lamp
Rated
Output
Design Lamp Type Wattage
M T5 28 2600* 3000
N T5 28 2600* 3500 O T5 28 2600* 4100 P T5 54 4450* 3000
Q T5 54 4450* 3500 R T5 54 4450* 4100
*25°C Rating
Lamp Color
(Kelvin)
Data is based on Osram Sylvania specifications. When ordering no lamps provided by Lightolier, use lamp code “Z”.
Do not alter lumen values or ballast factor light losses when completing calculations using Energos IES files. Files have already been adjusted. The lumen value for the lamp (within a Lighting Design program) will be the IES Ouput value shown on this table.
IES Output
(lumens)
Lamp Ordering Information
Rated Output
(Lumens)
System
Input
Watts
System
Efficacy
(lum/watt)
System
Lamp Life
(Hours)
Color (K)
Start Type
Job Information Type:
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group •
C0808
Loading...