Lightolier Calculite C7CS-P38MH Specification

Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
Lightolier a Genlyte Thomas Company www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2011 Genlyte Thomas Group LLC (Lightolier Division) •B1111
Features
1. Reflector: Low brightness with 45° cut-off to lamp and lamp image.
Specular with minimal flange fits precisely into Cylinder housing.
2. Cylinder Housing: White painted seamless aluminum with groove designed
to minimize visual appearance. Returned edge precisely seats reflector without visible hardware.
3. Socket:Medium base pulse rated socket with nickel plated screw shell.
Special socket design in open rated fixtures accepts only open rated lamps. Snaps onto upper reflector for secure attachment without tools. Unitized con­struction assures proper lamp alignment to optics for consistent performance.
4. Ballast: Electronic or magnetic. Accessible for service and replacement.
5. Back Plate: Cast aluminum, suitable for mounting over 4" octagon outlet box.
Electrical
Electronic Ballast: 120V or 277V. Encased, high power factor, T.H.D.
<15%, thermally and transient protected, RMI/RFI complies with FCC part 18 non-consumer limits, shut-down circuit at end of lamp life, sound rating "A",
-5° F minimum starting temperature, Type 1 outdoor rating.
Ballast ANSI Code Voltage Max. Amps Input Watts
70W MH M98/M143 120/277 0.67/0.28 78 100W MH M90/M140 120/277 0.90/0.43 110
Magnetic Ballast: 120V/277V dual voltage, 60 Hz., core and coil, HX-HPF circuit type, high power factor, -20° F minimum starting temperature, Type 1 Outdoor rating.
Ballast ANSI Code Voltage Max. Amps Input Watts
70W MH M98/M143 120/277 1.90/0.80 94 100W MH M90/M140 120/277 2.40/1.10 125
Options and Accessories
C4CSW: Stem Kit: – White (45° Swivel, 37" long) Provide with 5/8” dia. Stem
and 5 1/2” dia. Canopy. Self-aligning swivel provides max. 45° verti­cal tilting. Installs over 4” octagonal outlet box. Stem can be cut to length on site.
Auxiliary Lighting: Add suffix A to Cylinder Housing and Reflector Trim.
Labels
UL (Suitable For Damp Locations), CSA, I.B.E.W.
9
-1/4"
(235 mm)
1
6-5/8"
(422 mm)
37'
(940 mm)
4
2
1
5
3
1
1 1/8" (283 mm) Dia.
8
" (203 mm) Dia.
7-3/8" (187 mm) Dia.
Wall Mount
Stem Kit
Ceiling Mount
Calculite
®
HID Surface Cylinder C7CS-P38MH
Page 1 of 2 7" Aperture, PAR38 Ceramic Metal Halide Downlight
Reflector Trim Cylinder Housing Lamp
C7P38MH CL Specular Clear, Minimal Flange
CCD Comfort Clear Diffuse, Minimal Flange CCZ Champagne Bronze, Minimal Flange
Ceiling-Mount Wall-Mount C7CS70MHEU C7CW70MHEU Electronic 120V 70W PAR38 Ceramic MH C7CS70MHEU C7CW70MHEU Electronic 277V 70W PAR38 Ceramic MH C7CS10MHEU C7CW10MHEU Electronic 120V 100W PAR38 Ceramic MH C7CS10MHEU C7CW10MHEU Electronic 277V 100W PAR38 Ceramic MH C7CS70MHU C7CW70MEU Magnetic 120V/277V 70W PAR38 Ceramic MH C7CS10MHU C7CW10MEU Magnetic 120V/277V 100W PAR38 Ceramic MH
Calculite
®
HID Surface Cylinder C7CS-P38MH
Page 2 of 2 7" Aperture, PAR38 Ceramic Metal Halide Downlight
Lightolier a Genlyte Thomas Company www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2011 Genlyte Thomas Group LLC (Lightolier Division) •B1111
Job Information Type:
70W PAR38, FLOOD, PHILIPS 3K MH LAMP, LUMEN RATING = 4800 LMS, ELECTRONIC AROMAT BALLAST CL FINISH TRIM
12,500
25,000
30°
6
A
NGLE MEAN CP LUMENS
0
22077
5 19279 1769
1
0 13483 15 7146 2166 20 2784 2
5 721 513 30 205 3
5 85 64 40 29 45 16 50 0 55 00 6
0 0 6
5 00 70 0 75 00 80 0 85 00 90 0
ZONAL LUMENS AND PERCENTAGES
ZONE LUMENS % LAMP %LUMINAIRE
0-30 4446 92.65 98.46 0-40 4510 93.97 99.86 0-60 4516 94.1 100
0-90 4516 94.1 100 40-90 6 0.13 0.14 60-90 00 0
90-180 00 0
0-180 4516 94.1 100
L
UMINANCE SUMMARY - CD. / SQ. M.
ANGLE MEAN CD/SQ M
4
5 59 55 0 65 0 75 0 8
5 0
*
* EFFICIENCY = 94.1% ** CERTIFIED TEST REPORT NO. 2419FR, DATE: JAN 26, 2004
SC = .4 C
OMPUTED BY LSI PROGRAM **TEST-LITE**
CEILING 80% 70% 50% 30%
WALL 70 50 30 10 50 10 50 10 50 10 0
R
CR
0
1.12 1.12 1.12 1.12 1.09 1.09 1.05 1.05 1.00 1.00 .94 1 1.09 1.07 1.06 1.05 1.06 1.03 1.02 1.00 .98 .97 .93 2 1.06 1.04 1.02 1.00 1.02 .99 .99 .96 .97 .94 .91 3 1.04 1.01 .98 .96 1.00 .96 .98 .94 .96 .93 .90 4 1.02 .98 .96 .94 .98 .93 .96 .92 .94 .91 .89 5
1.00 .96 .93 .91 .95 .91 .94 .90 .92 .89 .88 6
.99 .94 .91 .89 .94 .89 .93 .89 .92 .88 .87 7 .97 .92 .89 .87 .92 .87 .91 .87 .90 .86 .85 8
.95 .91 .88 .86 .90 .85 .89 .85 .89 .85 .84 9 .94 .89 .86 .84 .89 .84 .88 .84 .87 .84 .83 10 .92 .87 .85 .83 .87 .83 .87 .83 .86 .82 .82
LUMINAIRE INPUT WATTS = 78.0
Coefficients of Utilization
Zonal Cavity Method - Effective Floor Cavity Reflectance = 20%
15,000
30,000
30°
60°
A
NGLE MEAN CP LUMENS
0 28361 5
26181 2386 10 19254 15 10393 3130 2
0 4124 25 1090 763 3
0 291 35 120 91 40 47 45 5 11 50 0 55 00 60 0 65 00 7
0 0 75 00 80 0 8
5 00 90 0
Z
ONAL LUMENS AND PERCENTAGES
Z
ONE LUMENS % LAMP %LUMINAIRE 0
-30 6278 92.33 98.41
0
-40 6369 93.67 99.83
0
-60 6380 93.82 100
0
-90 6380 93.82 100
4
0-90 10 0.16 0.17
6
0-90 00 0
9
0-180 00 0 0
-180 6380 93.82 100
LUMINANCE SUMMARY - CD. / SQ. M.
A
NGLE MEAN CD/SQ M
45 231 55 0 65 0 7
5 0
8
5 0
** EFFICIENCY = 93.8% ** CERTIFIED TEST REPORT NO. 2421FR, DATE: JAN 21, 2004
SC = .4 C
OMPUTED BY LSI PROGRAM **TEST-LITE**
C
EILING 80% 70% 50% 30%
WALL 70 50 30 10 50 10 50 10 50 10 0
RCR
0 1.12 1.12 1.12 1.12 1.09 1.09 1.04 1.04 1.00 1.00 .94 1 1.09 1.07 1.06 1.04 1.05 1.03 1.01 1.00 .98 .97 .92 2 1.06 1.03 1.01 .99 1.02 .98 .99 .96 .96 .94 .91 3 1.04 1.00 .98 .96 .99 .95 .97 .94 .95 .92 .90 4 1.02 .98 .95 .93 .97 .92 .95 .91 .94 .91 .89 5
1.00 .96 .92 .90 .95 .90 .93 .89 .92 .89 .87
6
.98 .94 .91 .89 .93 .89 .92 .88 .91 .87 .86
7
.96 .92 .89 .87 .91 .86 .90 .86 .89 .86 .85 8 .95 .90 .87 .85 .89 .85 .89 .85 .88 .84 .83 9 .93 .88 .86 .84 .88 .84 .87 .83 .87 .83 .82 10 .92 .87 .84 .82 .87 .82 .86 .82 .86 .82 .81
LUMINAIRE INPUT WATTS = 110.0
Coefficients of Utilization
Zonal Cavity Method - Effective Floor Cavity Reflectance = 20%
100W PAR38, FLOOD, PHILIPS 3K MH LAMP, LUMEN RATING = 6800 LMS, ELECTRONIC AROMAT BALLAST, CL FINISH TRIM
1,250
2,500
3,750
5,000
30°
60°
ANGLE MEAN CP LUMS.
0 4860
5 4540 437 10 4365 15 4197 1180 20 3890 25 3162 1498 30 2735 35 1466 929 40 250 45 42 65 50 0 55 00 60 0 65 00 70 0 75 00 80 0 85 00 90 0
ZONAL LUMENS AND PERCENTAGES
ZONE LUMENS % LAMP %LUMINAIRE
0-30 3115 64.9 75.81 0-40 4044 84.26 98.42 0-60 4109 85.61 100
0-90 4109 85.61 100 40-90 64 1.35 1.58 60-90 00 0
90-180 00 0
0-180 4109 85.61 100
LUMINANCE SUMMARY - CD. / SQ. M.
ANGLE MEAN CD/SQ M
45 2104 55 0 65 0 75 0 85 0
** EFFICIENCY = 85.6% ** CERTIFIED TEST REPORT NO. 2420FR, DATE: JAN 26, 2004
SC = .9 COMPUTED BY LSI PROGRAM **TEST-LITE**
CEILING 80% 70% 50% 30%
WALL 70 50 30 10 50 10 50 10 50 10 0
RCR
0 1.02 1.02 1.02 1.02 1.00 1.00 .95 .95 .91 .91 .86 1 .98 .96 .94 .93 .95 .91 .91 .89 .88 .86 .82 2 .94 .91 .89 .86 .90 .85 .87 .83 .85 .82 .79 3 .91 .87 .83 .81 .85 .80 .84 .79 .82 .78 .75 4 .88 .83 .79 .76 .82 .76 .80 .75 .78 .74 .72 5 .84 .79 .74 .72 .78 .71 .76 .71 .75 .70 .68 6 .81 .75 .71 .68 .74 .68 .73 .67 .72 .67 .66 7 .78 .71 .67 .64 .71 .64 .70 .64 .69 .63 .62 8 .75 .68 .64 .61 .67 .61 .67 .61 .66 .60 .59 9 .71 .65 .60 .58 .64 .58 .63 .57 .63 .57 .56 10 .69 .62 .57 .54 .61 .54 .61 .54 .60 .54 .53
LUMINAIRE INPUT WATTS = 78.0
Coefficients of Utilization
Zonal Cavity Method - Effective Floor Cavity Reflectance = 20%
70W PAR38, WIDE FLOOD, PHILIPS 3K MH LAMP, LUMEN RATING = 4800 LMS, ELECTRONIC AROMAT BALLAST, CL FINISH TRIM
2,000
4,000
6,000
8,000
30°
60°
ANGLE MEAN CP LUMS.
0 7868
5 7495 709 10 6849 15 6228 1761 20 5546 25 4296 2032 30 3425 35 1738 1130 40 296 45 69 84 50 2 55 00 60 0 65 00 70 0 75 00 80 0 85 00 90 0
ZONAL LUMENS AND PERCENTAGES
ZONE LUMENS % LAMP %LUMINAIRE
0-30 4502 66.21 78.74 0-40 5632 82.83 98.51 0-60 5717 84.08 100
0-90 5717 84.08 100 40-90 84 1.25 1.49 60-90 00 0
90-180 00 0
0-180 5717 84.08 100
LUMINANCE SUMMARY - CD. / SQ. M.
ANGLE MEAN CD/SQ M
45 3439 55 0 65 0 75 0 85 0
*** EFFICIENCY = 84.1% ** CERTIFIED TEST REPORT NO. 2422FR,
SC = .8 DATE: JAN 21, 2004
COMPUTED BY LSI PROGRAM **TEST-LITE**
CEILING 80% 70% 50% 30%
WALL 70 50 30 10 50 10 50 10 50 10 0
RCR
0 1.00 1.00 1.00 1.00 .98 .98 .93 .93 .89 .89 .84 1 .97 .95 .93 .91 .93 .90 .89 .87 .86 .85 .81 2 .93 .90 .87 .85 .88 .84 .86 .82 .83 .81 .78 3 .90 .86 .82 .80 .84 .79 .83 .78 .81 .77 .75 4 .87 .82 .78 .76 .81 .75 .79 .74 .78 .74 .72 5 .83 .78 .74 .71 .77 .71 .76 .71 .75 .70 .68 6 .81 .75 .71 .68 .74 .68 .73 .68 .72 .67 .66 7 .77 .71 .68 .65 .71 .64 .70 .64 .69 .64 .63 8 .75 .68 .64 .62 .68 .61 .67 .61 .66 .61 .60 9 .71 .65 .61 .58 .65 .58 .64 .58 .63 .58 .57 10 .69 .62 .58 .56 .62 .56 .61 .55 .61 .55 .54
LUMINAIRE INPUT WATTS = 110.0
Coefficients of Utilization
Zonal Cavity Method - Effective Floor Cavity Reflectance = 20%
100W PAR38, WIDE FLOOD, PHILIPS 3K MH LAMP, LUMEN RATING = 6800 LMS, ELECTRONIC AROMAT BALLAST, CL FINISH TRIM
Loading...