Lightolier C7E17FL-PL User Manual

Prismatic Lens
Fresnel Lens
Calculite
®
HID Lensed Downlight C7E17FL-PL
Page 1 of 2 7" Aperture, ED17 (Enclosed), Ceramic Metal Halide, Fresnel or Prismatic Lens
Job Information Type:
Lamp(s): Notes:
Lightolier a Genlyte company www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2005 Genlyte LLC • B0809
Features
1. Reflector: Semi-Specular anodized aluminum, 16 ga. Removable from inside
fixture for access to splices and ballast.
2. Lens: Prismatic (C7E17PLWHW) or Fresnel (C7E17FLWHW) lens. Regressed
1 3/4" from ceiling line.
3. Die-Cast Baffle: Painted white, self flange, deep conical step baffle for
low brightness, supports lens. Small Allen-head set screw provides secure attachment for use where vandal resistant luminaires are required.
4. Torsiontite Springs: Permit removal of lens assembly without tools.
5. Socket Cup: Galvanized steel, pre-wired with medium base pulse rated
socket. Snaps onto upper reflector for secure attachment without tools; unitized construction assures proper lamp alignment to optics for consistent performance.
6. Mounting Frame: 0.048"(18-ga.) galvanized steel includes pre-installed
mounting bars.
7. Mounting Ring: 0.048"(18-ga.) galvanized steel. Designed for vertical
adjustment from above or below for ceilings from 0" to 2" thick. Center-line notches allow consistent alignment of multiple fixtures.
8. Retaining Springs: Rust resistant simplify reflector housing removal for
inspection and maintenance.
9. Vertical Adjustment Mechanism: Accommodates mounting to virtually
any ceiling system using mounting bars (provided, or 1/2" EMT tubing (by others). Single locking feature secures all adjustments. Alignment holes and markings allow fixture to be preset prior to installation.
10. Mounting Bars: 0.048" (18-ga.) pre-installed, telescoping bars extend to 30"
long and lock securely into position. Built-in locking tabs provide positive attachment to common T-bar systems. Self-centering feature simplifies instal­lation in 24" O.C. grid systems. Attaches to steel or wood joists without accessories.
11.Ballast: Electronic 120V or 277V or dual voltage (120V/277V) magnetic.
Assembly is accessible from below without tools for inspection and replacement.
12. Junction Box: 0.048" (18-ga.) galvanized steel. UL listed for 8 No. 12 AWG,
90°C through branch circuit conductors; allows inspection from below.
13. Thermal Protector: (not shown) Meets NEC and UL requirements. Do not
install insulation above nor within 3" (76mm) of any part of the luminaire.
Electrical
Electronic Ballast: 120V or 277V, 50/60 Hz., encased, high-power factor, T.H.D.
<15%, thermally and transient protected, RMI / RFI complies with FCC Part 18 non-consumer equipment, shut-down circuit at end of lamp life, sound rating "A", -5° F minimum starting temperature, Type 1 outdoor rating.
Ballast ANSI Code Voltage Max. Amps Input Watts
70W MH M98/M143 120/277 0.67/0.28 78 100W MH M90/M140 120/277 0.90/0.43 110
Magnetic Ballast: 120V/277V dual voltage, 60 Hz., encased and potted, HX-HPF circuit type, high power factor, sound rating “B”, -20° F minimum starting temperature, Type 1 Outdoor rating.
Ballast ANSI Code Voltage Max. Amps Input Watts
70W MH M98/M143 120/277 1.90/0.80 94 100W MH M90/M140 120/277 2.40/1.10 125
Options and Accessories
Auxiliary: Add suffix A to Frame-In Kit and Reflector Trim. See Spec.Sheet “A/E” Emergency Lamp: Add suffix E to FIK and Reflector Trim. See Spec.Sheet “A/E” Slope Ceiling Adapters: See Specification Sheet SCA. Fuse (magnetic ballast): Add suffix F1 or F2 to FIK (F1=120V F2=277V) Chicago Plenum: Consult Factory.
Labels
UL (Suitable for Wet Locations), CSA, I.B.E.W.
Ceiling Cutout: 8" (203mm) dia.
Reflector Trim Frame-In Kit Lamp (Coated, Ceramic MH)
C770MHE1 Electronic, 120V 70W ED17,BD17 (Enclosed) C770MHE2 Electronic, 277V 70W ED17, BD17 (Enclosed) C710MHE1 Electronic, 120V 100W ED17, BD17 (Enclosed) C710MHE2 Electronic, 277V 100W ED17 BD17 (Enclosed) C770MHU Magnetic, 120V/277V 70W ED17, BD1 (Enclosed) C710MHU Magnetic, 120V/277V 100W ED17, BD17 (Enclosed)
18
5/8"
(473
)
C7E17FLWHW Fresnel Lens, White Step Baffle, White Flange C7E17PLWHW Prismatic Lens, White Step Baffle, White Flange
3
20" (508 mm) to 30" (762 mm)
mm
10-1/2"
(267 mm)
-
10-7/8"
(276 mm)
(Electronic Ballast)
8-1/4"
9-3/4"
(210 mm)
(248 mm)
Top View
(Magnetic Ballast)
20" (508 mm) to 30" (762 mm)
9-3/4" (248 mm)
11" (280 mm)
(100W)
Top View
10-7/8"
(276 mm)
8-3/4"
(222 mm)
510127811 1 42
7-5/16" (187 mm) Dia.
8-5/8" (200 mm) Dia.
11
69
Vertical Adjustment: 5/8" (16 mm) to 2 7/8" (73 mm)
2" (50 mm) max. Ceiling Thickness
Calculite
®
HID Lensed Downlight C7E17FL-PL
Page 2 of 2 7" Aperture, ED17 (Enclosed), Ceramic Metal Halide, Fresnel or Prismatic Lens
Lightolier a Genlyte company www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2005 Genlyte LLC • B0809
Job Information Type:
Prismatic Lens
Fresnel Lens
FRESNEL LENS/WHITE BAFFLE - 70W ED17 (ENCLOSED), PHILIPS CERAMIC MH. LUMEN RATING = 6000 LMS., AROMAT ELECTRONIC BALLAST.
500
1000
1500
2000
30°
30°
60°
ANGLE MEAN CP LUMENS
0 2368
5 2318 219 10 2183 15 1988 561 20 1759 25 1497 689 30 1202 35 886 564 40 617 45 421 337 50 283 55 184 173 60 121 65 82 84 70 51 75 24 29 80 11 85 3 5 90 0
ZONAL LUMENS AND PERCENTAGES
ZONE LUMENS % LAMP %LUMINAIRE
0-30 1469 24.49 55.2 0-40 2033 33.89 76.39 0-60 2543 42.4 95.58
0-90 2661 44.36 100 40-90 628 10.47 23.61 60-90 117 1.96 4.42
90-180 0 0 0
0-180 2661 44.36 100
LUMINANCE SUMMARY - CD. / SQ. M.
ANGLE MEAN CD/SQ M
45 24091 55 12972 65 7868 75 3806 85 1310
** EFFICIENCY = 44.4% ** CERTIFIED TEST REPORT NO. 2553FR, DATE: MAR 23, 2004
SC = .9 COMPUTED BY LSI PROGRAM **TEST-LITE**
CEILING 80% 70% 50% 30%
WALL 70 50 30 10 50 10 50 10 50 10 0
RCR
0 .53 .53 .53 .53 .52 .52 .49 .49 .47 .47 .44 1 .50 .49 .48 .47 .48 .46 .46 .45 .44 .43 .41 2 .48 .45 .44 .42 .45 .42 .43 .41 .42 .40 .38 3 .45 .42 .40 .38 .41 .38 .40 .37 .39 .37 .35 4 .43 .39 .37 .35 .39 .35 .38 .34 .37 .34 .33 5 .40 .37 .34 .32 .36 .32 .35 .32 .35 .31 .30 6 .38 .34 .31 .30 .34 .29 .33 .29 .33 .29 .28 7 .36 .32 .29 .27 .32 .27 .31 .27 .30 .27 .26 8 .34 .30 .27 .25 .29 .25 .29 .25 .29 .25 .24 9 .32 .28 .25 .23 .28 .23 .27 .23 .27 .23 .22 10 .31 .26 .23 .21 .26 .21 .25 .21 .25 .21 .21
LUMINAIRE INPUT WATTS = 78
Coefficients of Utilization
Zonal Cavity Method - Effective Floor Cavity Reflectance = 20%
FRESNEL LENS/WHITE BAFFLE - 100W ED17 (ENCLOSED) COATED, CERAMIC MH, PHILIPS, LUMEN RATING = 9000 LMS., AROMAT ELECTRONIC BALLAST
1250
2500
30°
1875
625
30°
60°
ANGLE MEAN CP LUMENS
0 2391
5 2355 228 10 2464 15 2630 738 20 2688 25 2629 1173 30 2194 35 1568 999 40 1028 45 658 535 50 420 55 278 261 60 187 65 128 129 70 76 75 32 41 80 14 85 3 6 90 0
ZONAL LUMENS AND PERCENTAGES
ZONE LUMENS % LAMP %LUMINAIRE
0-30 2139 23.77 52.06 0-40 3138 34.87 76.36 0-60 3934 43.71 95.74
0-90 4109 45.66 100 40-90 971 10.79 23.64 60-90 175 1.95 4.26
90-180 0 0 0
0-180 4109 45.66 100
LUMINANCE SUMMARY - CD. / SQ. M.
ANGLE MEAN CD/SQ M
45 37610 55 19605 65 12235 75 4995 85 1598
** EFFICIENCY = 45.7% ** CERTIFIED TEST REPORT NO. 2566FR, DATE: MAR 24, 2004 SC = 1.1 COMPUTED BY LSI PROGRAM **TEST-LITE**
CEILING 80% 70% 50% 30%
WALL 70 50 30 10 50 10 50 10 50 10 0
RCR
0 .54 .54 .54 .54 .53 .53 .51 .51 .49 .49 .46 1 .52 .50 .49 .48 .49 .47 .47 .46 .46 .44 .42 2 .49 .47 .45 .43 .46 .42 .44 .42 .43 .41 .39 3 .46 .43 .41 .39 .42 .38 .41 .38 .40 .37 .36 4 .44 .40 .37 .35 .40 .35 .39 .35 .38 .34 .33 5 .41 .37 .34 .32 .37 .32 .36 .32 .35 .31 .30 6 .39 .35 .32 .30 .34 .29 .33 .29 .33 .29 .28 7 .36 .32 .29 .27 .32 .27 .31 .27 .30 .26 .26 8 .34 .30 .27 .25 .29 .25 .29 .25 .28 .24 .24 9 .32 .28 .25 .23 .27 .23 .27 .22 .26 .22 .22 10 .30 .26 .23 .21 .25 .21 .25 .21 .25 .21 .20
LUMINAIRE INPUT WATTS = 110
Coefficients of Utilization
Zonal Cavity Method - Effective Floor Cavity Reflectance = 20%
PRISMATIC LENS/WHITE BAFFLE - 70W ED17 (ENCLOSED), PHILIPS CERAMIC MH. LUMEN RATING = 6000 LMS., AROMAT ELECTRONIC BALLAST
1250
2500
30°
625
1875
30°
60°
ANGLE MEAN CP LUMENS
0 2368
5 2318 219 10 2183 15 1988 561 20 1759 25 1497 689 30 1202 35 886 564 40 617 45 421 337 50 283 55 184 173 60 121 65 82 84 70 51 75 24 29 80 11 85 3 5 90 0
ZONAL LUMENS AND PERCENTAGES
ZONE LUMENS % LAMP %LUMINAIRE
0-30 1469 24.49 55.2 0-40 2033 33.89 76.39 0-60 2543 42.4 95.58
0-90 2661 44.36 100 40-90 628 10.47 23.61 60-90 117 1.96 4.42
90-180 0 0 0
0-180 2661 44.36 100
LUMINANCE SUMMARY - CD. / SQ. M.
ANGLE MEAN CD/SQ M
45 24091 55 12972 65 7868 75 3806 85 1310
** EFFICIENCY = 44.4% ** CERTIFIED TEST REPORT NO. 2553FR, DATE: MAR 23, 2004 SC = .9 COMPUTED BY LSI PROGRAM **TEST-LITE**
CEILING 80% 70% 50% 30%
WALL 70 50 30 10 50 10 50 10 50 10 0
RCR
0 .53 .53 .53 .53 .52 .52 .49 .49 .47 .47 .44 1 .50 .49 .48 .47 .48 .46 .46 .45 .44 .43 .41 2 .48 .45 .44 .42 .45 .42 .43 .41 .42 .40 .38 3 .45 .42 .40 .38 .41 .38 .40 .37 .39 .37 .35 4 .43 .39 .37 .35 .39 .35 .38 .34 .37 .34 .33 5 .40 .37 .34 .32 .36 .32 .35 .32 .35 .31 .30 6 .38 .34 .31 .30 .34 .29 .33 .29 .33 .29 .28 7 .36 .32 .29 .27 .32 .27 .31 .27 .30 .27 .26 8 .34 .30 .27 .25 .29 .25 .29 .25 .29 .25 .24 9 .32 .28 .25 .23 .28 .23 .27 .23 .27 .23 .22 10 .31 .26 .23 .21 .26 .21 .25 .21 .25 .21 .21
LUMINAIRE INPUT WATTS = 78
Coefficients of Utilization
Zonal Cavity Method - Effective Floor Cavity Reflectance = 20%
PRISMATIC LENS/WHITE BAFFLE - 100W ED17 (ENCLOSED) COATED, CERAMIC MH, PHILIPS, LUMEN RATING = 9000 LMS., AROMAT ELECTRONIC BALLAST
1750
3500
30°
2625
875
30°
60°
ANGLE MEAN CP LUMENS
0 3550
5 3476 329 10 3272 15 2980 841 20 2636 25 2243 1033 30 1801 35 1327 845 40 924 45 630 505 50 423 55 274 258 60 180 65 121 123 70 75 75 35 42 80 15 85 2 5 90 0
ZONAL LUMENS AND PERCENTAGES
ZONE LUMENS % LAMP %LUMINAIRE
0-30 2202 24.47 55.32 0-40 3046 33.86 76.54 0-60 3809 42.33 95.71
0-90 3980 44.23 100 40-90 933 10.38 23.46 60-90 170 1.9 4.29
90-180 0 0 0
0-180 3980 44.23 100
LUMINANCE SUMMARY - CD. / SQ. M.
ANGLE MEAN CD/SQ M
45 36025 55 19321 65 11616 75 5405 85 1117
** EFFICIENCY = 44.2% ** CERTIFIED TEST REPORT NO. 2567FR, DATE: MAR 24, 2004
SC = .9 COMPUTED BY LSI PROGRAM **TEST-LITE**
CEILING 80% 70% 50% 30%
WALL 70 50 30 10 50 10 50 10 50 10 0
RCR
0 .53 .53 .53 .53 .51 .51 .49 .49 .47 .47 .44 1 .50 .49 .48 .47 .48 .46 .46 .44 .44 .43 .41 2 .47 .45 .43 .42 .44 .41 .43 .40 .42 .40 .38 3 .45 .42 .40 .38 .41 .38 .40 .37 .39 .36 .35 4 .43 .39 .37 .35 .39 .35 .38 .34 .37 .34 .33 5 .40 .37 .34 .32 .36 .32 .35 .31 .35 .31 .30 6 .38 .34 .31 .29 .34 .29 .33 .29 .32 .29 .28 7 .36 .32 .29 .27 .31 .27 .31 .27 .30 .27 .26 8 .34 .30 .27 .25 .29 .25 .29 .25 .28 .25 .24 9 .32 .28 .25 .23 .27 .23 .27 .23 .27 .23 .22 10 .30 .26 .23 .21 .26 .21 .25 .21 .25 .21 .21
LUMINAIRE INPUT WATTS = 110
Coefficients of Utilization
Zonal Cavity Method - Effective Floor Cavity Reflectance = 20%
Loading...