Lightolier C6T6A-MHT6RF User Manual

20" to 30"
10-5/8"
15"
19-5/8"
2
2-1/8" (Magnetic)
20-1/4" (Electronic)
19-1/8"
op View
Calculite
®
HID Adjustable Accent C6T6A-MHT6RF
Page 1 of 2 6" Aperture, T6 Ceramic Metal Halide, Flood
Flood Upper Reflector
Ceiling Cutout: 6 9/16" (167mm) Dia.
For Complete Fixture Order: Trim Kit + Upper Reflector (MHT6RF) + Frame-In Kit. Each Sold Separately.
Trim Kit + Flood Upper Reflector Frame-In Kit Lamp
C6T6A + MHT6RF (Flood Upper Reflector)
CLW Specular Clear, White Painted Flange CLP Specular Clear, Matching Flange
CCDW Comfort Clear Diffuse, White Painted Flange CCDP Comfort Clear Diffuse, Matching Flange CCZW Champagne Bronze, White Painted Flange CCZP Champagne Bronze, Matching Flange
C6A39T6E1 Electronic 120V 39W T6 Ceramic MH C6A39T6E2 Electronic 277V 39W T6 Ceramic MH C6A70T6E1 Electronic 120V 70W T6 Ceramic MH C6A70T6E2 Electronic 277V 70W T6 Ceramic MH C6A15T6E1 Electronic 120V 150W T6 Ceramic MH C6A15T6E2 Electronic 277V 150W T6 Ceramic MH
Magnetic 120V/277V 150W T6 Ceramic MH
Features
1. Flood Upper Reflector: Specular textured aluminum; provides 40° beam.
Interchangeable with 12° Spot (MHT6RS) and 25° Narrow Flood (MHT6RNF); see spec sheets C6T6A-MHT6RS and C6T6A-MHT6RNF.
2. Trim Kit:: Low brightness aperture cone; anodized aluminum, self-flanged in
painted white or aperture-matching polished flange. Consult factory for other finishes.
3. Lamp Shield: High-temperature glass as required by code; captive during
re-lamping.
4. Trim Kit Adjustment Mechanism: Provides 40° vertical tilt, 360° horizon-
tal rotation; lockable. Patented EZ-Aim Helical Drive System provides fast and accurate hot aiming with Philips scr
5. Socket Housing: Galvanized steel, pre-wired with G12 pulse rated socket.
Snaps onto yoke for secure attachment without tools; unitized construction
oper alignment of lamp to optics for consistent optical per
es pr
assur mance.
6. Frame Housing: Steel, 0.029" (22-Ga.), matte black finish. Removable cover
7. Frame Vertical Adjustment Mechanism: Accommodates mounting to vir-
8.
9. Retention Springs: Rust resistant springs secure trim for quick, tool-less
10.Ballast / Cover Assembly: Accessible fr
11.Junction Box: 0.059" (16-ga.) galvanized steel. UL listed for 8 No. 12 A
12.Accessory Holder: (Not Shown) Sold separately catalog # CAH6; die-
13.Thermal Protector: (Not Shown) Meets NEC and UL requirements. Do not
e-lamping.
for top r
tually any ceiling system using pre-installed mounting bars, or 1/2" EMT tub­ing (by others). Single locking feature secures all adjustments. Alignment holes and markings allow fixtur adjustment can be made from below from inside fixture.
Mounting Bars:
bars extend to 30" long and lock secur provide positive attachment to common T-bar systems. Self-centering feature simplifies installation in 24" O.C. grid systems. Attaches to steel or wood joists without accessories.
installation.
tools for inspection and ballast replacement .
90°C through branch circuit conductors. Allows inspection from below.
formed steel, matte black finish, slide-in installation. Accepts up to two 4 3/4" dia. media.
install insulation above nor within 3" (76mm) of any part of the luminaire.
Galvanized steel, 0.048" (18-ga.), pr
ewdriver.
e-set prior to installation. Final
e to be pr
ely into position. Built-in locking tabs
om below and r
e-installed telescoping
emovable without
Electrical
Electronic Ballast: 120V or 277V, 50/60 Hz., encased, high power factor, T.H.D
<15%, thermally and transient protected, RMI/RFI complies with FCC Part 18 on­consumer equipment, shut-down circuit at end of lamp life, sound rating “A”,
-5°F (-20°F for 150W) minimum starting temperature, Type 1 outdoor rating. *150W Magnetic Ballast: 120V/277V dual voltage, 60 Hz., encased and potted, HX-HPF circuit type, high power factor, sound rating “B”, -20° F minimum starting temperature, Type 1 Outdoor rating.
Ballast ANSI Code Voltage Max. Amps Input Watts
39W MH M130 120/277 0.39/0.17 44 70W MH 150W MH M142 120/277 1.40/0.60 167
* 150W MH M142 120/277 3.70/1.60 180
-
for
Options and Accessories
Chicago Plenum: Consult Factor Fuse (magnetic ballast): Add suf
M139 120/277 0.67/0.28 78
y
fix
F1 or F2 to Frame-In Kit (F1=120V
, F2=277V)
Labels
UL (Suitable for Damp Locations), CSA, I.B.E.W. For 150W, install fixtures with minimum spacing between:
1. Center-to-center of adjacent luminaries: 2 feet.
2. Top of luminaire to overhead building member: 1/2 inch.
3. Luminaire center to side building member: 1 foot.
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
WG,
Notes:
Lightolier a Genlyte company www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2006 Genlyte Gr
oup LLC • B0406
Calculite
®
HID Adjustable Accent C6T6A-MHT6RF
Page 2 of 2 6" Aperture, T6 Ceramic Metal Halide, Flood
(FC) is initial footcandles at center of beam. Beam length (L) and beam width
W) are to where the candlepower is
( reduced to 50% of the center beam candlepower. (C) is the distance to the center of the beam.
CANDLEPOWER DISTRIBUTION
1,125
2,250
3,375
4,500
2,000
4,000
6,000
8,000
60°
30°
60°
°
30
ANGLE WALL 0 828
1125
5
1484
10
2129
15
3032
20
3951
25
4448
30
4042
35
3092
40
2004
45
1365
50 55 804 60 357 65 109 70 12
0
75 80 0 85 0 90 0
ANGLE WALL 0 2129 5 2598 10 3416 15 4621 20 5826 25 7165 30 7886 35 7331 40 5692 45 4040 50 2544
1262
55 60 460 65 113 70 12 75 2 80 0 85 0
0
90
39W T6 - FLOOD UPPER REFLECTOR
AIMED 30 deg. TOWARD WALL
LAMP: 39W T6 MH, PHILIPS LUMEN RATING: 3400 LMS. CBCP: 4448 Beam Angle: 28 AROMAT 39W ELECTRONIC BALLAST
DATE: MAR 9, 2004 CERTIFIED TEST REPORT NO. 2528FR
COMPUTED BY LSI PROGRAM **TEST-LITE**
DC FCL W
3.5' 80 4.1' 3.5'
6'
4.6' 45 5.4' 4.6'
8' 10' 5.8' 29 6.8' 5.8' 12' 6.9' 20 8.1' 6.9' 15' 8.7' 13 10.2' 8.6'
70W T6 - FLOOD UPPER REFLECTOR
AIMED 30 deg. TOWARD WALL
LAMP: 70W T6 MH, PHILIPS LUMEN RATING: 6600 LMS. CBCP: 7886 Beam Angle: 33 AROMAT 70W ELECTRONIC BALLAST
DATE: MAR 13, 2004 CERTIFIED TEST REPORT NO. 2527FR
COMPUTED BY LSI PROGRAM
**TEST-LITE**
DC FCL W
8' 4.6' 80 6.5' 5.5' 10' 5.8' 51 8.1' 6.8' 12' 6.9' 36 9.8' 8.2' 15' 8.7' 23 12.2' 10.3' 20' 11.5' 13 16.3' 13.7'
° Aiming Angle
30
Horizontal Surface
30° Aiming Angle
Horizontal Surface
° Aiming Angle
30
ertical Surface
V
CFCLW
D
2' 3.5' 139 4.9' 2.0' 3' 5.2' 62 7.4' 3.0'
6.9' 35 9.8' 4.0'
4'
10.4' 15 14.7' 6.0'
6' 8' 13.9' 9 19.6' 8.0'
30° Aiming Angle
Vertical Surface
DC FCL W
3' 5.2' 110 9.6' 3.6' 4' 6.9' 62 12.9' 4.7' 6' 10.4' 27 19.3' 7.1' 8' 13.9' 15 25.7' 9.5' 12' 20.8' 7 38.6' 14.2'
3,750
7,500
11,250
15,000
ANGLE WALL 150W T6 - FLOOD UPPER REFLECTOR 0 3264
4588
5
60°
30°
10 6230 15 20 11273 25 13598 30 14410 35 12748 40 45 6584 50 4740 55 3021 60 1451 65 70 71 75 15 80 85 15 90
LAMP: 150W T6 MH, PHILIPS
8522
LUMEN RATING: 14000 LMS.
CBCP: 14410 Beam Angle: 32 AROMA
9706
DATE: MAR 11, 2004
TIFIED TEST REPOR
CER
COMPUTED BY LSI PROGRAM
443
**TEST
15
15
T 150W ELECTRONIC BALLAST
T NO. 2533FR
-LITE**
J
Lightolier a Genlyte company www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2006 Genlyte Group LLC • B0406
Aiming Angle
°
30
Horizontal Surface
W
L
FC
C
D
8' 4.6' 146 6.3' 5.3' 10' 5.8' 94 7.9' 6.6' 12' 6.9' 65 9.4' 7.9' 15' 8.7' 42 11.8' 9.9' 20' 11.5' 23 15.7' 13.2'
CFCLW
D
3' 5.2' 200 9.1' 3.4' 4' 6.9' 113 12.2' 4.6' 6' 10.4' 50 18.3' 6.9' 8' 13.9' 28 24.4' 9.2' 12' 20.8' 13 36.5' 13.8'