Lightolier C6P30MH User Manual

Calculite
®
HID Downlight C6P30MH
Page 1 of 2 6” Aperture, PAR30 Ceramic MH
Ceiling Cutout: 6 9/16” (167 mm) Dia.
Reflector Trim Frame-In Kit Lamp
C6P3OMH CLW Specular Clear, White Painted Flange.
CLP Specular Clear, Matching Flange. CCDW Comfort Clear Diffuse, White Painted Flange. CCDP Comfort Clear Diffuse, Matching Flange. CCZW Champagne Bronze, White Painted Flange. CCZP Champagne Bronze, Matching Flange.
C639MHE1 Electronic 120V 39W PAR30 Ceramic Metal Halide C639MHE2 Electronic 277V 39W PAR30 Ceramic Metal Halide C670MHE1 Electronic 120V 70W PAR30 Ceramic Metal Halide C670MHE2 Electronic 277V 70W PAR30 Ceramic Metal Halide C639MHU Magnetic 120V/277V 39W PAR30 Ceramic Metal Halide C670MHU Magnetic 120V/277V 70W PAR30 Ceramic Metal Halide
Features
1. Reflector Trim: Clear anodized aluminum, 0.040” (16-ga.). Provides 45° visu-
al cut-off to lamp and lamp image; self-flange painted white or polished flange. Consult factory for other finishes.
2. Socket Cup: Galvanized steel pre-wired with medium base pulse rated sock-
et. Snaps onto upper reflector for secure attachment without tools; assures proper lamp alignment to optics for consistent performance.
3. Mounting Frame: 0.048" (18-ga.) galvanized steel includes pre-installed
mounting bars.
4. Mounting Ring: 0.048" (18-ga.) galvanized steel. Designed for vertical
adjustment from above or below for ceilings from 0" to 2" thick. Center-line notches allow consistent alignment of multiple fixtures.
5. Retention Springs: Rust resistant springs secure reflector in place for quick,
tool-less installation.
6. Frame Vertical Adjustment Mechanism: Vertical adjustment mechanism
accommodates mounting to virtually any ceiling system using pre-installed mounting bars, or 1/2" EMT tubing (by others). Single locking feature secures all adjustments. Alignment holes and markings allow fixture to be pre-set prior to installation.
7. Mounting Bars: 0.048" (18-ga.) Pre-installed, telescoping bars extend to 30"
long and lock securely into position. Built-in locking tabs provide positive attachment to common T-bar systems. Self-centering feature simplifies installation in 24" O.C. grid systems. Attaches to steel or wood joists without accessories.
8. Ballast: Electronic 120V or 277V. Magnetic dual voltage (120V & 277V).
Accessible from below for inspection and/or replacement without tools.
9. Junction Box: 0.048" (18-ga.) galvanized steel. UL listed for 8 No. 12 AWG,
90°C through branch circuit conductors; allows inspection from below.
10. Thermal Protector: (Not Shown) Meets NEC and UL requirements. Do not
install insulation above nor within 3" (76mm) of any part of the luminaire.
Electrical (cont.)
Ballast ANSI Code Voltage Max. Amps Input Watts
39W MH M130 120/277 0.39/0.17 44 70W MH M98/M143 120/277 0.67/0.28 78
Magnetic Ballast: 120/277V dual voltage, 60 Hz., encased and potted, HX-HPF circuit type, high power factor, sound rating “B”, -20°F minimum starting temperature, Type 1 Outdoor rating.
Ballast ANSI Code Voltage Max. Amps Input Watts
39W MH M130 120/277 1.90/0.80 94 70W MH M139 120/277 2.40/1.10 125
Options and Accessories
Slope Ceiling Adapters: See Specification Sheet SCA. Fuse (magnetic ballast) B1 Add suffix F1 or F2 to Frame-In Kit (F1=120V, F2=277V) Chicago Plenum: Consult Factory.
Labels
UL (Suitable for Damp Locations), CSA, I.B.E.W.
Job Information Type:
Job Name: Cat. No.:
Lamp(s): Notes:
Electrical
Electronic Ballast: 120V or 277V, 50/60 Hz., encased, high-power factor, T.H.D.
<15%, thermally and transient protected, RMI / RFI complies with FCC Part 18 non-consumer equipment, shut-down circuit at end of lamp life, sound rating "A", -5°F minimum starting temperature, Type 1 outdoor rating.
Lightolier a Genlyte Thomas Company www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2004 Genlyte Thomas Group LLC (Lightolier Division) • A0504
Calculite
®
HID Downlight C6P30MH
Page 2 of 2 6” Aperture, PAR30 Ceramic MH
39W PAR30L PHILIPS FL MH LAMP, LUMEN RATING = 2200 LMS, AROMAT 39W ELECTRONIC BALLAST, CL FINISH REFLECTOR
CANDLEPOWER DISTRIBUTION
ANGLE MEAN CP LUMENS
0 6714
1,125
3,250
4,875
6,500
** EFFICIENCY = 92.9% ** CERTIFIED TEST REPORT NO. 2462FR, DATE: FEB 19, 2004.
SC = .5
5 6480 607 10 5770 15 3724 1045
60°
20 1533 25 496 310 30 156 35 72 62 40 93 45 3 19
`50 0
55 0 0 60 0 65 0 0 70 0 75 0 0
30°
80 0 85 0 0 90 0
COMPUTED BY LSI PROGRAM **TEST-LITE**
70W PAR30L PHILIPS FL MH LAMP, LUMEN RATING = 4850 LMS, AROMAT 70W ELECTRONIC BALLAST, CL FINISH REFLECTOR
CANDLEPOWER DISTRIBUTION
2,500
5,000
7,500
10,000
** EFFICIENCY = 92.9% ** CERTIFIED TEST REPORT NO. 2463FR, DATE: FEB 19, 2004.
SC = .6
ANGLE MEAN CP LUMENS
0 10853
5 10183 962 10 9105 15 7452 2043 20 4818
60°
25 2188 1173 30 943 35 239 260 40 233 45 20 53 50 1 55 0 0 60 0 65 0 0 70 0 75 0 0 80 0 85 0 0 90 0
30°
COMPUTED BY LSI PROGRAM **TEST-LITE**
LUMINANCE SUMMARY CD. / SQ. M.
ANGLE MEAN CD/SQ M
45 195 55 0 65 0 75 0 85 0
ZONAL LUMENS AND PERCENTAGES
ZONE LUMENS % LAMP %LUMINAIRE
0-30 1962 89.22 96.05 0-40 2024 92.03 99.07 0-60 2043 92.89 100
0-90 2043 92.89 100 40-90 18 0.86 0.93 60-90 0 0 0
90-180 0 0 0
0-180 2043 92.89 100
LUMINANCE SUMMARY CD. / SQ. M.
ANGLE MEAN CD/SQ M
45 1583 55 0 65 0 75 0 85 0
ZONAL LUMENS AND PERCENTAGES
ZONE LUMENS % LAMP %LUMINAIRE
0-30 4178 86.15 93.03
0-40 4437 91.5 98.81
0-60 4491 92.6 100
0-90 4491 92.6 100 40-90 53 1.1 1.19 60-90 0 0 0
90-180 0 0 0
0-180 4491 92.6 100
Coefficients of Utilization
CEILING 80% 70% 50% 30%
WALL 70 50 30 10 50 10 50 10 50 10 0
Zonal Cavity Method - Effective Floor Cavity Reflectance = 20%
RCR
0 1.11 1.11 1.11 1.11 1.08 1.08 1.03 1.03 .99 .99 .93 1 1.08 1.06 1.04 1.03 1.04 1.01 1.00 .98 .97 .95 .91 2 1.05 1.02 1.00 .98 1.00 .97 .97 .94 .95 .93 .89 3 1.02 .99 .96 .94 .97 .93 .96 .92 .93 .90 .88 4 1.00 .96 .93 .91 .95 .90 .93 .89 .92 .88 .86 5 .98 .93 .90 .88 .93 .88 .91 .87 .90 .86 .85 6 .96 .91 .88 .86 .91 .86 .90 .85 .88 .85 .83 7 .94 .89 .86 .84 .89 .83 .87 .83 .86 .83 .82 8 .92 .87 .84 .82 .86 .81 .86 .81 .85 .81 .80 9 .90 .85 .82 .80 .85 .80 .84 .80 .83 .79 .78 10 .88 .83 .80 .78 .83 .78 .82 .78 .82 .78 .77
LUMINAIRE INPUT WATTS = 44
Coefficients of Utilization
CEILING 80% 70% 50% 30%
WALL 70 50 30 10 50 10 50 10 50 10 0
Zonal Cavity Method - Effective Floor Cavity Reflectance = 20%
RCR
0 1.10 1.10 1.10 1.10 1.08 1.08 1.03 1.03 .99 .99 .93 1 1.07 1.05 1.03 1.02 1.03 1.00 .99 .97 .96 .94 .90 2 1.04 1.01 .98 .96 .99 .95 .96 .93 .94 .91 .88 3 1.01 .97 .94 .92 .96 .91 .94 .90 .92 .89 .86 4 .98 .94 .91 .89 .93 .88 .91 .87 .90 .86 .84 5 .96 .91 .87 .85 .90 .85 .89 .84 .87 .83 .82 6 .94 .89 .85 .83 .88 .82 .87 .82 .86 .81 .80 7 .91 .86 .82 .80 .85 .79 .84 .79 .83 .79 .78 8 .89 .83 .80 .78 .82 .77 .82 .77 .81 .77 .76 9 .86 .81 .78 .75 .80 .75 .80 .75 .79 .74 .73 10 .84 .79 .75 .73 .78 .73 .78 .73 .77 .73 .72
LUMINAIRE INPUT WATTS = 78
Job Information Type:
Lightolier a Genlyte Thomas Company www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2004 Genlyte Thomas Group LLC (Lightolier Division) • A0504