In an installation of 2 lamp 32W luminaires in a room cavity ratio of 1 reflectance 80% ceiling, 50% post-wall, 20% floor the CU. shall no be less than
0.69. To prevent glare the VCP shall not be less than 88 either lengthwise or crosswise (at 100 fc level) and that the average luminance will conform with the IES RP-24 preferred standard, and have a fixture efficiency of not less than 60%.
MATERIALS
Chassis parts are die-formed 20 gauge cold rolled steel.
LOUVER
Post-anodized aluminum.
FINISH
Louver - Low iridescense specular post-wall, anodized vertical grain sheet or Low iridescence reflector matte post-anodized vertical grain sheet. Chassis exte­rior white baked polyester powder coat.
ELECTRICAL
Rapid start HPF thermally protected class “P” ballast CBM certified by ETL if K.O. is within 3 of ballast use wire suitable for at least 90”.
LABELS
Listed by CSA/UL.
Meets IES RP-24 Preferred Practice.
Ideal for intensive VDT use areas.
Only 5.5” deep.
Utilizes CFI Advance Technology Reflector Louver.
Precise fitting reflector louver.
Louver securely held with CFI concealed torsionite spring clips
Fixture Efficiency 62.4%
Lightolier a Genlyte Thomas Company www.lightolier.com
Technical Information: (978) 657-7600 Fax (978) 658-0595 631 Airport Road, Fall River, MA 02720 (508) 679-8131 Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2002 Genlyte Thomas Group LLC (Lightolier Division) A0902 Section 2/Folio G09-10
VP PARABOLIC ADS8G16MS140
Page 2 of 2 8x48 RECESSED FLUORESCENT16 CELL PARABOLIC LOUVER
STATIC IES RP24 PREFERRED
40116G8S AD
Advance Technology Full Width
Refector Louver
48 in length
Fixture Width
8 = 8
Ceiling Type
G = Grid
(Lay in T-Bar)
Number of
Cells
Louver finish
MS-Low
Iridescence
Reflector Matte
PS-Low Iridescence
CFI Anodized
Specular
Lamp Quantity
Lamp
Length
40 = 48
Voltage
120 277 347
Ballast Type
OC = T8
SO = Electric
T8
DI = dimming
Options Add appropriate suffix to calalog
no., ie HRD)
Body Style
S=Static
Consult factory for availability of louver finishes.
SPECIFICATIONS PERFORMANCE: In an installation of 2 lamp 32W luminaires in a room cavity
ratio of 1 reflectance 80% ceiling, 50% post-wall, 20% floor the CU. shall no be less than 0.69. To prevent glare the VCP shall not be less than 88 either length­wise or crosswise (at 100 fc level) and that the average luminance will conform with the IES RP-24 preferred standard, and have a fixture efficiency of not less than 60%.
MATERIALS: Chassis parts are die-formed 20 gauge cold rolled steel. LOUVER:Post-anodized aluminum.
FINISH: Louver - Low iridescense specular post-wall, anodized vertical grain
sheet or Low iridescence reflector matte post-anodized vertical grain sheet. Chassis exterior white baked polyester powder coat. ELECTRICAL: Rapid start HPF thermally protected class “P ballast CBM certi­fied by ETL if K.O. is within 3 of ballast use wire suitable for at least 90”.
LABELS:Listed by CSA/UL.