READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE
This fixture is intended for installation in accordance with the National Electrical Code and local regulations.
To assure full compliance with local codes and regulations, check with your local electrical inspector
before installation. To prevent electric shock, turn off electricity at fuse box before proceeding.
Retain these instructions for maintenance reference.
INSTRUCTION FOR INSTALLATION OF PRE-WIRED COMPACT FLUORESCENT
EMERGENCY LIGHTING DECORATIVE SURFACE UTILITY FIXTURES
INSTRUCTION SHEET NO.
IS:EMSU
Page 1 of 3A0200
WARNING: (RISK OF FIRE)
5242PB326UE, 5243SA326UE, 5243SB326UE, 5543PB326UE AND 5543WH326UE. MOST DWELLINGS BUILT BEFORE 1985 HAVE SUPPLY WIRE RATED FOR 60˚.
SUPPLY WIRING MUST BE RATED 90˚C. WHEN INSTALLING THE FOLLOWING MODEL NUMBERS ONLY: 5240WH326UE, 5241WH326UE,
CONSULT A QUALIFIED ELECTRICIAN BEFORE INSTALLATION.
NOTICE: THIS INSTRUCTION SHEET TO BE USED IN CONJUNCTION WITH INSTRUCTIONS
SUPPLIED FOR THE INSTALLATION OF SPECIFIC MODEL BEING INSTALLED.
IMPORTANT SAFEGUARDS
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED INCLUDING:
1. Turn off AC power before proceeding.
2. Be sure all electrical connections are complete and outlet box is closed before battery connectors on emergency pack
are connected.
3. Do not use outdoors.
4. Do not mount near gas or electrical heaters.
5. Do not attemp to service the battery. A sealed, rechargeable, no maintance battery is used. Do not incinerate or mutilate;
may burst or release toxic materials. Do not short circuit; may cause burns. Battery acid can cause burns to skin and
eyes. If acid is spilled on skin or eyes, flush with fresh water and contact a physician immediately.
6. Equipment should be mounted in locations and at a height where it will not be readily subject to tampering by unauthorized
personnel.
7. The use of accessory equipment is not reccommended by the manufacturer and may cause an unsafe condition.
8. Do not use the equipment for other than intended use.
9. This unit has more than one power supply connection piont. To reduce the risk of electrical shock, disconnect both the
normal and the emergency power supplies before servicing.
10. Before servicing to prevent electrical shock, disconnect the battery connectors on the emergency pack (located on the
end of the emergency pack). Make certain that the switch (if the fixture is switched) and the unswitched lines to the
emergency pack are turned off at the fuse box. Servicing should be performed by qualified personnel only.
INSTALLATION
WARNING: TO PREVENT HIGH VOLTAGE ON THE RED & YELLOW OUTPUT LEADS PRIOR TO
INSTALLATION, BATTERY CONNECTOR MUST BE OPEN. DO NOT JOIN BATTERY CONNECTOR UNTIL
INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED TO THE EMERGENCY BALLAST.
A. WIRING -
1. Make sure AC power is off at fuse box.
2. Make sure that the necessary branch circuit wiring is available.
An unswitched source of power is required for the emergency pack.
3. The emergency pack must be fed from the same branch circuit as the AC ballast(s).
4. In switched fixtures, emergency pack must be connected ahead of any local switching.
5. Be sure all electrical connections are made and outlet box is closed before battery
connectors on emergency pack are connected.
6.
Select the appropriate wiring diagram to connect the emergency pack and the AC ballast: (See Pages 2 & 3)
Read and understand all instructions before proceeding.
LIGHTOLIER a GENLYTE THOMAS company.
631 Airport Road, Fall River, MA 02720
INSTRUCTION SHEET NO.
IS:EMSU
Page 2 of 3A0200
INSTRUCTION FOR INSTALLATION OF PRE-WIRED COMPACT FLUORESCENT
READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING FIXTURE
This fixture is intended for installation in accordance with the National Electrical Code and local regulations.
To assure full compliance with local codes and regulations, check with your local electrical inspector
before installation. To prevent electric shock, turn off electricity at fuse box before proceeding.
Retain these instructions for maintenance reference.
EMERGENCY LIGHTING DECORATIVE SURFACE UTILITY FIXTURES
WIRING DIAGRAM A
(2-Lamp 13W OR 26W 4 Pin Quad Tube
Pre-Wired for 120V or 277V)
(TWO EMERGENCY LAMPS ON)
NOTE: FOR UNSWITCHED CIRCUIT, CONNECT
120V OR 277V EMERGENCY PACK HOT
LEAD TO AC BALLAST HOT LEAD.
BATTERY
CONNECTOR
WHITE
INDICATOR
LIGHT
VIOLET +
BROWN -
WIRING DIAGRAM B
(2-Lamp 39W 4 Pin Twin Tube
Pre-Wired for 120V)
(TWO EMERGENCY LAMPS ON)
NOTE: FOR UNSWITCHED CIRCUIT, CONNECT
120V EMERGENCY PACK HOT
LEAD TO AC BALLAST HOT LEAD.
BATTERY
CONNECTOR
WHITE
INDICATOR
LIGHT
VIOLET +
BROWN -
RED
RED
EMERGENCY
BALLAST
EMERGENCY
BALLAST
CAP UNUSED
LEAD
120V (BLK) OR
277V (ORG)
120V (BLK) OR 277V (ORG)
(COM) WHITE
BLUE/WHITE
BLUE
YELLOW
YEL/BLK
RED
277V
(ORG)
120V (BLK)
(COM) WHITE
BLUE/WHITE
BLUE
YELLOW
YEL/BLK
RED
UNUSED
CAPPED
(UNSWITCHED)
TEST
SWITCH
SKT
(UNSWITCHED)
SWITCH
JMPR 2
TEST
JMPR 1
RED
JMPR 1
JMPR 2
RED
BLK
BLK
BLK
BLK
WHITE
WHITEWHITE
SKT
SKTSKT
(SWITCHED OR UNSWITCHED)
HOTCOMHOT
GRD
GREEN
BLACK
WHITE
BLUE
BLUE
YEL A
YEL B
RED
RED
RED
(SWITCHED OR UNSWITCHED)
HOTCOMHOT
GRD
GREEN
BLACK
WHITE
BLUE
BLUE
YEL A
YEL B
RED
RED
RED
AC
BALLAST
AC
BALLAST
WIRING DIAGRAM C
(2-Lamp 39W 4 Pin Twin Tube
Pre-Wired for 277V)
(TWO EMERGENCY LAMPS ON)
NOTE: FOR UNSWITCHED CIRCUIT, CONNECT
277V EMERGENCY PACK HOT
LEAD TO AC BALLAST HOT LEAD.
BATTERY
CONNECTOR
INDICATOR
LIGHT
VIOLET +
BROWN -
RED
WHITE
EMERGENCY
BALLAST
120V
(BLK)
277V (ORG)
(COM) WHITE
BLUE/WHITE
BLUE
YELLOW
YEL/BLK
RED
UNUSED
CAPPED
HOT
(UNSWITCHED)
TEST
SWITCH
BLK
BLK
JMPR 1
(SWITCHED OR UNSWITCHED)
HOTCOM
GRD
GREEN
BLACK
WHITE
BLUE
BLUE
YEL A
YEL B
RED
RED
RED
SKTSKT
JMPR 2
RED
LIGHTOLIER a GENLYTE THOMAS company.
631 Airport Road, Fall River, MA 02720
AC
BALLAST