Lightolier 4X4PL User Manual

Calculite® Matrix
9 5/8"
10"
5 7/8"
7 1/8"
5"
5
5 1/2"
4 1/2" 5 3/4"
7
1
2
43
6
1 1/4" Max.
Ceiling Thickness
4 1/2"
5 3/4"
®
Lensed Downlight 4X4PL
Page 1 of 2 4 1/2" X 4 1/2" Square Aperture (1) 26/32W Triple Tube Prismatic Lens
Top View
Ceiling Cutout: 5 1/8" L X 9 5/8" W
Trim Kits Frame-In Kits Reflector
Trims
4X4PLCLW 4X4PLCLP 4X4PLCCLW 4X4PLCCLP 4X4PLCCDW 4X4PLCCDP 4X4PLCCGP 4X4PLWHW
Finish / Flange Frame-In Kits Type Ballast
Specular Clear / White Specular Clear / Polished
Comfort Clear / White
Comfort Clear / Polished
Comfort Clear Diff. / White
Comfort Clear Diff. / Polished
Clear Corrugated / Self Flange
White / White
Features
1. Reflector Trim: Pre-finished aluminum with low iridescence clear finish.
Overlap flange accommodates different ceiling types. Precision mitered flange corners. Prismatic spread lens, 5/32" thick tempered glass.
2. Upper Reflector: High efficiency, 97%, Specular Clear.
3. Housing: 22 Ga. galvanized formed steel. Centerline notches and holes
for consistent alignment of multiple fixtures. Accommodates ceilings up to 1 1/4" thick.
4. Ballast Assembly: Door-mounted for easy service, allows replacement from
inside of fixture.
5. Torsiontite Springs: Precision-tooled steel springs secure reflector trim
to housing for quick tool-less installation. Positive tension holds flange tight
against ceiling.
6. J-Box: 14 Ga. galvanized steel. Accessible from inside and outside of the
fixture. Outside J-box door is hinged for easy access.
7. Mounting Brackets: 16 Ga. steel. Adjustable from inside fixture. Utilize
3/4" or 1 1/2" lathing channel, 1/2" EMT, or optional mounting bars.
Options & Accessories
Chicago Plenum with Fuse (slow blow): add LCF suffix to frame-in kit,
consult factory for specifications.
Lightolier is a Philips group brand
Mounting Bars / T-Bar Anchor Clips: See specification sheet “MBA".
4X4132HU
4X4132HUEM4E
4X4132HCU3
4X4132HJUM7
4X4132HJ1MX
4X4132HJ2MX
Input Voltage
Non-IC Electronic 120 /277 V 26/32W 10" 9 1/2" 5 3/4"
Non-IC Electronic - Emergency 120 /277 V 26/32W 10 " 11" 5 3/4"
Non-IC PowerSpec® HDF Dimming 120 /277 V 26/32W 10 " 9" 5 3/4"
Non-IC Mark 7® Dimming 120 /277 V 26/32W 10 " 9 1/4" 5 3/4"
Non-IC Mark 10® Dimming 120 V 26/32W 10" 9 1/4" 5 3 /4"
Non-IC Mark 10® Dimming 277V 26/32W 10" 9 1/4" 5 3/4"
Triple Tube Wattage
Length Width Height
Electrical
UL Listed for through circuit wiring with max of (8) No. 12 AWG, 90°C supply conductors.
Note: For complete ballast data and lamp / ballast compatibility refer to “Ballast"
specification sheet.
General
UL Listed for wet locations, I.B.E.W. Union Made.
Job Information Type:
Job Name:
Cat. No.:
Lamp(s): Notes:
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2008 Philips Group • C0808
Calculite® Matrix
®
Lensed Downlight 4X4PL
Page 2 of 2 4 1/2" X 4 1/2" Square Aperture (1) 26/32W Triple Tube Prismatic Lens
26W Triple Tube, Specular Clear Reflector Trim
One Philips lamp, 1800 lumens
Test Report 1764FR Apr. 5, 2002
Angle Along 22.5 45 67.5 Across Lumens
0 646 646 646 646 646 5 644 645 647 648 649 62 10 625 631 642 651 653 15 583 596 628 646 647 175 20 517 543 591 624 628 25 445 470 531 575 583 239 30 368 392 450 492 500 35 287 303 344 375 389 214 40 209 217 232 267 287 45 152 148 145 178 199 129 50 104 94 87 106 125 55 12 26 33 29 16 35 60 1 1 5 1 2 65 1 0 0 1 1 1
70 0 0 0 0 0
75 0 0 0 0 0 0 80 0 0 0 0 0 85 0 0 0 0 0 0 90 0 0 0 0 0
Zone Lumens % Lamp % Luminaire 0-30 475 26.42 55.71 0-40 689 38.32 80.79 0-60 852 47.38 99.90 0-90 853 47.43 100.00
EFFICIENCY = 47.4% Spacing Criterion: Along = 1.0 Across = 1.2
80 70 50 30 10 0
cu
50 30 10 50 30 10 50 30 10 50 30 10 50 30 10 0 1 .53 .52 .51 .52 .51 .50 .50 .49 .48 .48 .47 .47 .46 .46 .45 .45 2 .49 .48 .46 .48 .47 .45 .47 .46 .44 .46 .44 .43 .44 .43 .43 .42 3 .46 .44 .42 .45 .43 .42 .44 .42 .41 .43 .42 .40 .42 .41 .40 .39 4 .43 .41 .39 .43 .40 .38 .41 .39 .38 .41 .39 .37 .40 .38 .37 .36 5 .40 .37 .35 .40 .37 .35 .39 .37 .35 .38 .36 .35 .37 .36 .34 .34 6 .38 .35 .33 .37 .34 .33 .36 .34 .32 .36 .34 .32 .35 .33 .32 .31 7 .35 .32 .30 .35 .32 .30 .34 .31 .30 .33 .31 .29 .33 .31 .29 .29 8 .32 .30 .28 .32 .29 .27 .32 .29 .27 .31 .29 .27 .31 .29 .27 .26
ROOM CAVITY RATIO
9 .30 .27 .25 .30 .27 .25 .29 .27 .25 .29 .27 .25 .29 .26 .25 .24 10 .28 .25 .23 .28 .25 .23 .27 .25 .23 .27 .25 .23 .27 .25 .23 .22
% Effective Ceiling Cavity Reectance
20% Floor Cavity Reectance
CANDLEPOWER SUMMARY
ZONAL LUMENS AND PERCENTAGES
32W Triple Tube, Specular Clear Reflector Trim
One Sylvania lamp, 2400 lumens
Test Report 1711FR Mar. 24, 2002
Angle Along 22.5 45 67.5 Across Lumens
0 781 781 781 781 781 5 777 778 781 784 785 74 10 755 760 776 789 794 15 706 720 757 786 792 212 20 635 657 716 757 760 25 550 575 642 684 688 289 30 459 485 544 578 591 35 363 386 421 460 489 265 40 267 280 291 344 375 45 190 191 185 231 258 165 50 127 119 109 140 163 55 16 28 42 40 19 44
60 2 2 7 2 2
65 0 0 0 0 0 1
70 0 0 0 0 0
75 0 0 0 0 0 0 80 0 0 0 0 0 85 0 0 0 0 0 0 90 0 0 0 0 0
Zone Lumens % Lamp % Luminaire 0-30 575 23.97 54.78 0-40 840 35.02 80.02 0-60 1049 43.73 99.91 0-90 1050 43.77 100.00
EFFICIENCY = 43.8% Spacing Criterion: Along = 1.0 Across = 1.1
80 70 50 30 10 0
cu
50 30 10 50 30 10 50 30 10 50 30 10 50 30 10 0 1 .49 .48 .47 .48 .47 .46 .46 .45 .44 .44 .44 .43 .43 .42 .42 .41 2 .45 .44 .42 .45 .43 .42 .43 .42 .41 .42 .41 .40 .41 .40 .39 .38 3 .42 .40 .39 .42 .40 .38 .41 .39 .38 .40 .38 .37 .39 .37 .36 .36 4 .40 .37 .35 .39 .37 .35 .38 .36 .35 .37 .36 .34 .36 .35 .34 .33 5 .37 .34 .32 .36 .34 .32 .36 .34 .32 .35 .33 .32 .34 .33 .31 .31 6 .34 .32 .30 .34 .32 .30 .33 .31 .30 .33 .31 .29 .32 .31 .29 .29 7 .32 .29 .28 .32 .29 .27 .31 .29 .27 .31 .28 .27 .30 .28 .27 .26 8 .30 .27 .25 .29 .27 .25 .29 .27 .25 .29 .26 .25 .28 .26 .25 .24
ROOM CAVITY RATIO
9 .28 .25 .23 .27 .25 .23 .27 .25 .23 .27 .24 .23 .26 .24 .23 .22 10 .26 .23 .21 .25 .23 .21 .25 .23 .21 .25 .22 .21 .24 .22 .21 .20
% Effective Ceiling Cavity Reectance
20% Floor Cavity Reectance
CANDLEPOWER SUMMARY
ZONAL LUMENS AND PERCENTAGES
Based on specular clear (CL) finish. To estimate other finishes, multiply candelas and CU values by 0.95 for CCL, by 0.90 for CCD.