Lightolier 4K28 User Manual

Single Swivel Stem Multiple to Short Swivel Stem 3 Cables to Short Swivel Suspension Ext. Kits
Cat. No. Nominal OAL Cat. No. Nominal OAL Cat. No. Nominal OAL Cat. No. Nominal OAL
Specify Finish as Suffix: Specify Finish as Suffix: Specify Finish as Suffix: Specify Finish as Suffix: SB, SN or WH SB, SN or WH SB, SN or WH SB, SN or WH
4SB115 15 3/16” (close-to-ceiling) 4SB224 24 3/16” 4SB328 28” 4SXT48 48” 4SB118 16 5/8” 4SB228 28” See Specification Sheet 4SB324 4SXT96 96” 4SB121 17 15/16” 4SB235 33 5/8” 4SB124 24 3/16” 4SB242 38 15/16” 4SB128 28” See Specification sheet 4SB224 4SB135 33 5/8” 4SB142 38 15/16”
See Specification Sheet(s) 4SB115, 4SB124
Specifications
• Suspension Size: For optimum performance testing recommends OAL (over-
all length) in proportion to the Body diameter or for close-to-ceiling propor­tion length. OAL is defined from bottom of diffuser to ceiling plane.
• Stem Wires: Equipped with 120” of leads with keyed connections for quick
connection to Body wiring.
Options & Accessories
D2 = Dimming Electronic Ballast, 26 Watt, 120V, only
Replace Body Cat No. Suffix “U” with Suffix “D2”.
E3 = 347V (Canada)
Replace Body Suffix “U” with Suffix “E3”.
EM = Emergency Battery Pack
Add Suffix “EM” to Body Cat. No.
Multi-Level Switching: Prewired, consult wiring diagram.
Fusing: Consult Factory
Finishes: SB = Satin Brass, SN = Satin Nickel, WH = White
Complete Luminaire consists of Body and Suspension: Order each separately.
Body Cat. No. Finish Lamps Options
4K28442ASBU Satin Brass 4-26 Triple Tube Compact Fluorescent D2 (26W, 120V only), 4K28442ASNU Satin Nickel or 4-32 Triple Tube Compact Fluorescent E3 (347V), or EM 4K28442AWHU White or 4-42 Triple Tube Compact Fluorescent Add Suffix to Cat. No.
Architectural Decorative 4K28
Page 1 of 2 Pendalux Contemporary 28” Diameter Body 4-26/32/42 Triple Tube
Job Information Type:
Job Name: Cat. No.:
Lamp(s): Notes:
Lightolier a Genlyte company www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2005 Genlyte Group LLC • C0605
7"
1 3/8"
28"
6 5/16"
Nominal OAL
4
3
5
6
2
1
7
45° Max.
Note: Drawing above illustrates only one of the suspen­sion types available for this Luminaire. For other drawings, consult individual Suspension Specification Sheet num­bers as noted in Suspension chart(s) below.
ANGLE MEAN CP LUMENS 0 417 5 420 40 10 415 15 408 115 20 395 25 380 176 30 361 35 337 212 40 312 45 286 221 50 257 55 224 201 60 190 65 157 155 70 123 75 90 97 80 62 85 39 49 90 40
CERTIFIED TEST REPORT NO. 4K28442A
COMPUTED BY LSI PROGRAM **TEST-LITE**
LIGHTOLIER INDIRECT/DIRECT PENDANT FIXTURE
CAT. #4K28442ASBU, 28” DIFFUSER
4-42W PLT TRIPLE TUBE LAMPS, LUMEN RATING = 3200 LMS.
2-ADVANCE BALLAST, #ICF-2S42-M2-LD, 120 VAC
TESTED ACCORDING TO IES PROCEDURES. TEST DISTANCE EXCEEDS FIVE
TIMES THE GREATEST LUMINOUS OPENING OF LUMINAIRE.
ZONE LUMENS % LAMP %LUMINAIRE 0-30 358 2.61 3.20 0-40 588 4.29 5.28 0-60 1046 7.80 9.59 0-90 1373 10.73 15.84 40-90 784 6.14 9.06 60-90 327 2.55 3.76 90-180 8040 62.81 92.76 0-180 9412 73.54 100.00
** EFFICIENCY =73.5% **
ANGLE MEAN CP LUMENS 90 40 95 165 227 100 461 105 751 777 110 975 115 1171 1159 120 1351 125 1516 1349 130 1633 135 1706 1317 140 1753 145 1803 1129 150 1826 155 1817 838 160 1779 165 1691 473 170 1506 175 1349 134 180 1428
CANDLEPOWER SUMMARY
ZONAL LUMENS AND PERCENTAGES
DATE: DEC. 20, 2000 PREPARED FOR: LIGHTOLIER, FALL RIVER, MA
ROOM CAVITY RATIO
COEFFICIENTS OF UTILIZATION ZONAL CAVITY METHOD
%EFFECTIVE FLOOR CAVITY REFLECTANCE = .20
80 70 50 30 10
50 30 10 50 30 10 50 30 10 50 30 10 50 30 10 0
1 .58 .56 .53 .51 .49 .46 .38 .36 .35 .25 .25 .24 .14 .14 .13 .08 2 .51 .47 .41 .44 .41 .38 .33 .31 .28 .22 .21 .20 .12 .12 .11 .07 3 .49 .40 .36 .39 .35 .32 .29 .27 .24 .20 .18 .17 .11 .10 .10 .06 4 .39 .34 .31 .35 .30 .27 .26 .23 .21 .16 .16 .14 .10 .09 .08 .05 5 .34 .30 .26 .31 .26 .23 .23 .20 .18 .16 .14 .12 .09 .08 .07 .04 6 .31 .26 .22 .27 .23 .20 .20 .17 .15 .14 .12 .11 .08 .07 .06 .04 7 .28 .23 .19 .24 .20 .17 .18 .15 .13 .13 .11 .09 .07 .06 .05 .03 8 .25 .20 .17 .22 .18 .15 .17 .14 .11 .11 .09 .08 .06 .05 .05 .03 9 .23 .18 .14 .20 .16 .13 .15 .12 .10 .10 .08 .07 .06 .05 .04 .02
10 .20 .16 .13 .18 .14 .11 .14 .11 .09 .09 .08 .06 .05 .04 .04 .02
DETERMINED IN ACCORDANCE WITH CURRENT IES PUBLISHED PROCEDURES
Features
1. Diffusing Reflector: White translucent acrylic, 3/16” thick.
2. Inner Dirt Shield: White translucent acrylic, 1/8” thick.
3. Chassis: Steel 20 gauge, semi-gloss white powder-coat finish.
4. Suspension: Swivel (central) stem, 5/8” steel tube. Canopy, steel, 7” Dia.
fastened internally, no exposed hardware. Permits installation on ceilings with slope of up to 45°. Complies with California Code.
5. Cables: Reflector Bowl is suspended from a central point on three 1/16”
stainless steel cables.
6. Lampholder: Multi-wattage, 4-pin, will accept either GX24q-3 or
GX24q-4 lamp base.
7. Flange Trim: Steel 20 gauge, Plated or Painted Finish.
Lamping (by others)
Compact Fluorescent: Triple Tube, 26, 32, or 42 Watts.
General Electric Osram/Sylvania Philips
26W Triple Tube 4-Pin (Amalgam) Compact Fluorescent Lamp
F26TBX/*/A/4P CF26DT/E/IN/* PL-T26W/*/4P
32W Triple Tube 4-Pin (Amalgam) Compact Fluorescent Lamp
F32TBX/*/A/4P CF32DT/E/IN/* PL-T32W/*/4P
42W Triple Tube 4-Pin (Amalgam) Compact Fluorescent Lamp
F42QBK/*/A/4P CF42DT/E/IN/* PL-T42W/*/4P
*Manufacturers’ color temperature designation.
Electrical
Ballast: Electronic, 2-Lamp HPF, Class P, Programmed Start.
Universal Voltage 120/277V, Multi-Wattage 26/32/42W.
4 Lamps 26 Watt 32Watt 42Watt
Voltage 120V 277V 120V 277V 120V 277V Total Input Watts 110 110 140 140 186 186 Max. Line Current (amps) 1.11 0.48 1.40 0.60 0.60 0.80 Power Factor >0.98 >0.98 >0.98 >0.98 >0.99 >0.99 Ballast Factor 1.02 1.02 0.96 0.96 0.95 0.95 THD<10% Minimum Starting Temperature -5°F /-20°C.
Mounting
Mounts directly to 4” outlet box, using crossbar hanger, supplied.
Labels
cULus listed suitable for damp locations.
Application Data
Reflectancies: 80% Ceiling, 50% Walls, 20% Floor. Light Loss Factor = .75 (.88 BF x .85) FC (footcandles) at 30” work plane.
28 Inch Diameter 30’ x 30’ x 10’ Space Luminaire Spacing: 10’ x 10’
Susp. Dist. 28”
4 Lamps 26W 32W 42W
TTT TTT TTT Illum. (FC) 26 35 45 Maint. Lum. 15/1 15/1 14/1 Ratio Watts/ 1.10 1.36 1.86 Sq. Ft.
Architectural Decorative 4K28
Page 2 of 2 Pendalux Contemporary 28” Diameter Body 4-26/32/42 Triple Tube
Lightolier a Genlyte company www.lightolier.com