Lightolier 440, 340, 240 User Manual

XT, XR XT2/XR2 SERIES 240/340/440
Page 1 of 2 2'x4' LAY-IN RECESSED FLUORESCENT STATIC, FLAT STEEL LENS FRAME (XT)
REGRESSED ALUMINUM LENS FRAME (XR), 2, 3, 4 LAMPS, T8 OR T12
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Volts/Ballast:
Technical Information: (978) 657-7600 • Fax (978) 658-0595 631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2002 Genlyte Thomas Group LLC (Lightolier Division) A0902 SECTION 1A/Folio F50-11 REV. B
Features
• Efficiency 80.9% (3 lamp T8).
• Fixture side rails have rolled-over edges for maximum safety.
• One piece body 3-5/8" deep.
• Ends of housing are formed inward for safer handling while installing troffer.
• Built-in earthquake clips (patent number 5,072,344).
• Flat steel full-size lens frame (XT).
• Regressed extruded aluminum lens frame (XR).
• Lens frame overlaps end of housing for positive mechanical light stop.
• Cam action latches.
• Flat steel lens frame with mitered corner detail is the same size as the ceiling opening for a clean uniform appearance.
• UL-Listed twin knockout access plate for easy closed lens frame wiring.
MOUNTING METHODS
DIMENSIONS
Exposed T-grid ceiling. Exposed T-grid ceiling.
earthquake clip
before
installation
earthquake clip
installed
24" (610mm)
48" (122mm)
3-5/8"
(92mm)
4-1/2"
(114mm)
24"
(610mm)
XT, XR XT2/XR2 SERIES 240/340/440
Page 2 of 2 2'x4' LAY-IN RECESSED FLUORESCENT STATIC, FLAT STEEL LENS FRAME (XT)
REGRESSED ALUMINUM LENS FRAME (XR), 2, 3, 4 LAMPS, T8 OR T12
Technical Information: (978) 657-7600 • Fax (978) 658-0595 631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2002 Genlyte Thomas Group LLC (Lightolier Division) A0902 SECTION 1A/Folio F50-11 REV. B
Job Information Type:
OPTIONS & ACCESSORIES
SPECIAL LENSES: Substitute VB for .125" nominal pattern 12 with 7.8 oz.
average weight per square foot. Substitute VI for .125" nominal pattern 12 with
6.9 oz. average weight per square foot. ACCESS PLATES: Top wiring access plate is shipped with fixture as standard. When access plates are required in advance for wiring convenience, specify separately. Order Catalog Number: ACP CSP.
ELECTRICAL/WIRING OPTIONS: Consult factory. FUSING: Internal fast-blow fusing. SUFFIX: GLR.
Internal slow-blow fusing. SUFFIX: GMF. RADIO INTERFERENCE FILTER 120 or 277 volt, 50 or 60 Hz. One per fixture is standard. SUFFIX: RF.
SPECIFICATIONS
PERFORMANCE: In an installation of 4 lamp 40 W luminaires in a room cavity
ratio of 1, with reflectance of 80% ceiling, 50% walls, 20% floor, the C.U. shall not be less than .78. To reduce glare the VCP shall be not less than 42 either lengthwise or crosswise (at 100 fc level) and the average brightness at 65 shall not exceed 718 footlamberts. To control veiling reflections, luminaire output in the 30°-90° zone shall be not less than 66%.
MATERIALS: Chassis parts are die-formed code gauge cold rolled steel. Housing is embossed for added strength and rigidity with all edges rolled over
for safe handling. Lens frames—(XT) flat full-size steel frame, (XR) regressed full-size aluminum frame. FINISH: Chassis exterior—white baked polyester enamel. Cavity—white baked polyester enamel minimum 86% reflectance. Phosphate undercoating. LENS: Extruded virgin acrylic 3/16" square based female cones, running 45° to the panel edge, .095" nominal thickness (similar to pattern 12). ELECTRICAL: Thermally protected class “P” ballast C.B.M. approved, non PCB. If K.O. is within 3" of ballast, use wire suitable for at least 90°. LABELS: I.B.E.W. Listed by Underwriters Laboratories.
PHOTOMETRY MODEL NO. XT2GVA340120SO
coefficients of utilization — zonal cavity method
RF 20 20 20 RC 80 50 30
RW 70 50 30 50 30 10 50 30 10
1898683 817876 787674 2827672 726865 706764 3766863 656056 635955 4706155 585349 565248 5645548 524742 514642 6594943 474137 464137 7554438 433733 413632 8514033 383328 373228 9473629 342925 342824
10 43 33 26 31 26 22 31 25 22
visual comfort probability
room size ceiling height ceiling height W L 8.5 10.0 13.0 16.0 8.5 10.0 13.0 16.0 20 20 64 68 75 82 61 65 72 79
20 30 57 61 66 73 54 58 63 69 20 40 54 57 62 66 49 53 58 62 20 60 51 54 57 61 46 49 52 57
30 20 65 69 74 80 63 67 72 78 30 30 58 61 65 70 55 59 62 68 30 40 54 57 60 64 50 53 57 60 30 60 50 53 55 59 46 49 51 55 30 80 49 51 52 55 44 46 48 51
40 20 66 70 75 79 65 69 73 78 40 30 59 63 66 70 57 60 64 68 40 40 55 57 60 63 51 54 57 61 40 60 51 53 55 58 47 49 51 54 40 80 49 51 51 54 44 47 48 51 40 100 49 50 50 52 43 45 45 48
60 30 60 63 66 70 58 62 65 69 60 40 55 58 60 63 53 56 58 61 60 60 51 53 55 58 48 50 51 55 60 80 49 51 51 54 45 47 47 50 60 100 49 50 49 51 44 45 45 48
100 40 58 60 62 65 56 59 61 64 100 60 54 55 56 59 51 53 54 57 100 80 51 52 52 55 48 49 49 52 100 100 50 51 50 52 46 47 46 48
room cavity ratio
luminaries lengthwise
luminaries crosswise
ORDERING INFORMATION
Explanation of Catalog Number. Example: XT2GVA340120SOGLR
XT = Recessed
Fluorescent with Flat Steel Lens Frame
XR= Recessed
Fluorescent with Regressed Aluminum Lens Frame
G
CEILING TYPE:
G = Grid (lay-in
T-bar)
LAMP QUANTITY:
2, 3 or 4 Lamps
VOLTAGE:
120 or 277
OPTIONS:
Add appropriate
suffix to catalog no,
ie: (GLR)
2
FIXTURE
WIDTH
VA
LENS/SHIELDING
TYPE:
VA = Virgin Acrylic
(standard) see options and consult factory
40
LAMP/
FIXTURE LENGTH:
(Nominal 48")
BALLAST TYPE:
LE=Magnetic (T12) OC=Magnetic (T8) SS=Electronic (T12) S3=1-3 Lamp Elect. (T12) SO=Electronic Elect. (T8) O3=1-3 Lamp Elect. (T8) O4=1-4 Lamp Elect. (T8) DIM=Dimming (T12) PS=LOL Power Spec T8
Dimming Ballast
Loading...