Features
UL Listed
Enclosure constructed to NEMA 4 standards
Non-glare protective front
Low power consumption
Ultra Bright Light Emitting Diodes - Front-lit
Lamp Test - Standard (located inside panel)
Intended for outdoor location
Technical Specifications
1. Standby Voltage
Nominal 24 Vdc: Min. 18 Vdc to 36 Vdc
2. Standby Current
Typical Range 0 -15 ma
3. Alarm Current
Standby Current is increased Approx. 15
ma for each Activated LED
max input @ 3 Amps
4. Indicators
Super Bright LED’s - Red, Amber and Green
5. Activating Voltage
Positive or Negative as specified
6. Operating Temperature
32-100F (0-38C)
Model WT-2
A
C
L
I
F
F
O
O
R
E
N
T
A
I
A
T
S
S
L
T
A
A
H
T
S
E
R
F
A
I
R
M
E
General Description
The WT Series annunciator is designed for outdoor use and in locations where protection from water and
temperature extremes are needed.
The annunciator is housed in a rugged #16 gauge steel enclosure and door, dip primed and finished in a Taupe
Powder Coat Enamel. The door is attached with a vandal resistant, hidden hinge with a key locked cover to
prevent unauthorized access. The door has a continuous 1/2” close-cell neoprene gasket and the annunciator
window opening uses the Scotch VHB joining System sealing gasket to seal the annunciator window opening.
Terminal strips (behind locked cover) facilitate the wiring of Field Devices. Screw connectors are complete with
captive wire protection and are automatically secured against loosening. Fire Alarm Panel driver modules can
be mounted inside of the annunciator panel.
The electronic components are permanently installed on circuit boards. Electrical connections from the circuit
board(s) to the LED panel are made with Ribbon Connectors.
Normal system operation in indicated by the lighted Green LED indicator. A lamp test switch is also provided.
When activated, ALL system indicators should light as a demonstration that all internal circuits, wiring and
LED’s are functioning properly. The system is modular and can easily be changed or expanded.

WEATHERTIGHT
WT
SERIES
Architect / Engineer Specification
The contractor shall furnish, where indicated on the plans, a Weathertight (Graphic or Directory) Annunciator Panel.
Standard features shall include but not be limited to: Built-In Voltage Regulation, Reverse Polarity Protection, Per Point Diode
Isolation and a Lamp Test Switch. Additionally, the unit shall be capable of lighting all its indicators simultaneously.
The WT series shall be Surface Mounted. Assembly shall be of “Dead-Front” construction, with no exposed screws or hinge.
Artwork and indicators to be protected by a sheet of Non-glare Plexiglass, finished in a taupe, weathertight enclosure.
Annunciator shall be able to operate from a nominal 24 Volts D.C. supplied by the Main Fire Alarm Panel. Unit will utilize the
Fire Alarm Panel’s standby batteries during loss of normal power.
Upon activation of any Alarm initiating device, the annunciator shall display the location of the device in alarm or zone in
alarm.
The Annunciator shall be manufactured by Light Engineered Displays, Inc., or approved equal.
Ordering Information
A drawing is required showing the actual graphic representation needed for your project. The exact location of the indicator
points should be shown and identified by a legend. Mark the Annunciator location on the plans so that the artwork can be
oriented properly (with a “You Are Here” designation). If unit is directory style, provide nomenclature required per zone.
ANNUNCIATORS
Annunciator sizes are shown below, according to model number. The maximum area available for artwork is the outside
dimension, less four inches. We will work from your blueline, copy, fax, sketch, E-mail or CAD file. Please note: your digital
CAD drawing, or a full size, inked mylar generated from the file, will speed production.
Please complete the annunciator Order Form and send with drawing. If Order Form is not available, indicate how annunciator will be activated and list any specifications required.
4" 1 5/8"
Box Door
"W"
"H"
Box Interior
Conduit
MODEL
WT-0
WT-1
WT-2
WT-3
MODEL
WT-05
WT-10
WT-20
WT-30
GRAPHIC STYLE
WIDTH x HEIGHT
21 1/4” x 12 1/4“
27 1/4” x 17“
27” x 27 1/2“
38” x 27”
DIRECTORY STYLE
WIDTH x HEIGHT
21 1/4” x 12 1/4“
27 1/4” x 17“
27” x 27 1/2“
38” x 27”
Installation Notes
1. Do NOT penetrate the top of the enclosure
2. Conduit entry is through sides and bottom only.
3. If mounting holes are drilled through the back of the box, then the rubber washers or grommets must be used to seal out
water.
4. Enclosure is designed for surface or pedestal mount. Under no conditions should the box be recessed more than 3”
deep.
Consult the factory regarding custom sizes, products, options or special requirements.