Introduction
The AquaALERT spot type Water Detector, series
WD-SD, is specifically designed for water leak
detection and water level monitoring. A special
low voltage circuit uses very little current to detect
the presence of conductive fluids. Typical installations include computer room subfloor areas,
telephone equipment rooms, basements, bathroom units, and areas adjacent to water tanks or
piping.
WD-SD
SPOT DETECTION
WD-SD
SERIES
Operation
A WD Series detector is available for use with
either 12 vdc or 24 vdc circuits. The detector has
a Form C contact and is intended to be monitored
by a remote alarm panel, or a graphic annunciator
panel. The sensing probe consists of two conductors woven within a polyester cable. Several
drops of water, soaking into the cable, is all that is
needed to operate the detector. Once operated,
the Form C contact will change state to activate
the remote alarm panel. After the probe has
dried-out, the contact will return to normal. Contact is rated for one amp, at 120 vac.
Installation and Testing
Place the detector in the area where water leak is
anticipated. Remove the top for access to the
terminal strip located inside unit. Connect to
alarm panel or annunciator as per the diagram
shown on the reverse side. When connections
have been made, test the unit by using a jumper
to simulate water reaching the probe. After proper
operation is verified, replace top and secure with
screws provided. If placement is to be permanent, secure the detector to the floor with silicon
adhesive. Fasten the probe to the floor using the
self-stick cable clamps provided. Unit is designed
for cable entry. When conduit is required, set a
J-box adjacent to the detector and connect with a
short length of cable. Wiring must conform to
local codes.
Specifications
WD-SD/12
Voltage: 12 VDC
Probe current (Max): .8 ma
Total Current Draw (Max): 40 ma
Relay Rating: 1 amp
WD-SD/24
Voltage: 24 VDC
Probe Current (Max): 2 ma
Total current Draw (Max): 28 ma
Relay Rating: 1 amp
*NOTE: No current draw until water is detected.
12/24 VAC and audible models are available.

WD-SD
SERIES
Wiring Diagram
WD-SD
SPOT DETECTION
To next detector From power supply
+
–
3 4 51 2 6 7 8
Probe
–
24 vdc
Power
+
Contact
Probe
Probe
Probe
Probe
TYPICAL HOOK-UP
3 4 51 2 7
3 4 51 2 7
3 4 51 2 76 8
6 8
+
6 8
+
+
+
To Annunciator
Power
Alarm initiating
Alarm Zone
Power
Trouble initiating
Alarm Zone
Alarm Zone
ALTERNATE HOOK-UP FOR FIRE & SECURITY PANELS
NOTE: 1. Unit is powered directly from Alarm Zone
2. Relay requires 20 ma. to activate.
Warranty
We will repair or replace any defective unit within one year of purchase except in cases of abuse,
misuse or incorrect wiring.
There are no warranties which extend beyond the use of this product. There is no warranty of fitness
for a particular purpose. In no event shall AquaALERT of Light Engineered Displays, Inc. be liable to
the purchaser or any other party for consequential or incidential damages.
AquaALERT Water Sensing Products, Division of Light Engineered Displays, Inc.