Light Engineered Displays WD-4 User Manual

Page 1
Specifications
Power Input
115 VAC, 60 HZ .5 AMP.
Operating Voltage
12 VDC, Internal 12 VAC
54 HZ Detection Loop
Battery Backup
12 VDC, 1.2 amp/hr battery
with automatic charger
LED Type, for Alarm, Trouble and
Power On status
Outputs
Sonalert and Form-C contacts
A Division of: Light Engineered Displays, Inc. 109 Portwatch Way Wilmington, N.C. 28412 Phone: (800) 251-2512 Fax: (800) 251-9878 Internet: www.ledinc.com Email: sales@ledinc.com
Model WD-1
ZONE LEAK
DETECTION SYSTEM
Model WD-4
WD
SERIES
General Description
The AquaALERT water detection system, featuring models WD-1 and WD-4, is specifically designed for water leak detec­tion in concealed areas or any place water intrusion must be identified immediately so that corrective action can be taken.
Applications would include Electrical or Telephone Equipment rooms, Computer Room subfloors, or any sensitive area that is not normally occupied. Additionally, this system can be used to detect leaks along fluid piping lines. Also, fluid levels can be detected with our optional float switches (see the 6200 Series cutsheet located in the Miscellaneous section of our catalog).
The unit is housed in a metal backbox, with a key-lockable plexiglass door. All indicators and switches are visible from the front of the unit.
The system is designed to work with AquaALERT water detection cable, model WDC-100. Low voltage A.C. is used to supervise the detection loop. This eliminates Electrolysis of the sensing wires woven within the detection cable, a common problem with other systems.
Basic Operation
The WD Series Water Detection System contains one or four fully supervised detection zone(s). The circuit must be termi­nated at the end of the line with a 15K Ohm, 1.2 Watt resistor.
Normal (standby) operation is indicated by a green “Power On” LED.
An Alarm condition occurs when water comes in contact with the Water Detection cable. A Trouble condition occurs when the wiring to the sensor, or the wires within the cable, are broken.
When an Alarm condition occurs, the Red LED will light, the Sonalert will sound, and the Aux. relay contact will close. The Sonalert can be silenced by operating the momentary Acknowledge switch. The Red LED will remain lit until the Alarm condition is corrected. At that time, the LED will reset itself. The sequence is the same for a Trouble condition, except a Yellow LED will be illuminated. Multiple Zone Units have subsequent alarm features.
Page 2
ZONE LEAK
COM COM
-1 2v
+5v
+5v
+12v
Sonalert
Z2
Z3
Z4
Programming Connector
Output to Status Board
Troubl e
Future Serial Port
XPor t
RJ-45 output jack
Form "C" Contacts
System Inputs
connections
NC
NO
NO
COM
COM
NC
Alarm
120 VAC Input
12v Battery
Power Suppl y
+
-
-
+
12 vdc Battery Outp ut
12 vdc Pow er Outpu t
H N
CAUTION
System Enclosure
Z1
WD-4 WD-1
WD
SERIES
DETECTION SYSTEM
Architect/Engineer Specification
The Contractor shall furnish, where indicated on the plans, a Water Leak Detection System. The standard features shall include but not be limited to the following:
1. The system shall utilize linear water leak detection cable.
2. The system shall utilize limited power, low voltage A.C. for the detection circuits to protect the leak detection cable from damage by electrolysis.
3. The system shall supervise the wiring and the water sensing conductors embedded in the leak detection cable. Any break in the wiring shall cause a System Trouble indication at the leak detection control panel.
4. The system shall also include both Alarm and Trouble indications for each input zone as was as a common audible alarm
and auxiliary form-C contacts for connection to external monitoring systems.
5. System inputs shall have adjustable sensitivity to allow for proper operation over a broad range of ambient field conditions.
6. The control panel shall operate from 115 V.A.C. and shall include automatic battery backup using a 12v gel - cell battery.
The panel assembly is housed in a steel enclosure with hinged door and cam lock to prevent unauthorized access.
7. The system shall be Model WD-1 / -4 -8 -16 (specify) as manufactured by AquaALERT, a division of LED Incorporated.
Circuit Board & Enclosure Details
NOTES: Nominal power is 115v AC - 60hz - 500ma. Route power away from all class-2 wiring. Power supply is a universal type with an input voltage range of 85 -264v AC and 47 to 63hz. Output is approximately 13.5v DC, 2 amps max with self-restoring overload protection.
Standby power is provided by a 12v 1.5 amp/hr gelled electrolyte battery. System Alarm and Trouble contacts are rated for 1amp resistive load, max. (class 2) Relays shown de-energized. Each leak detection zone must be terminated with a 15K ohm resistor.
4"
1"
10"
-
+
12v Battery
Backbox
Door
10"
WD-1
WD-1
WD-4
WD-4
Battery Input
Detection Zone
Terminate w/15kohm 1/4watt
System Contacts
Power Supply
120 vac input
12 vdc output
18"
Sensitivity Adj.
N
120 VAC
H
CAUTION
Enclosure
9"
WD-8
Side View
Front View
Front View