Models
DL-1NM Controller - No Map - 12” x 12” Box
DL-1 Controller with Map - 14” x 24” Box
DL-2 Controller with Map - 24” x 24” Box*
*box has room for second controller
General Description
DISTANCE
LOCATING SYSTEM
DL
SERIES
The AquaALERT Distance locating system
combines linear leak detection cable with microprocessor control and graphic annunciation to
provide the ultimate in water leak detection. A
digital display identifies the alarm and indicates its
location by footage measurement. An integral
Graphic Map correlates to the measurement for
fast, accurate response by facilities personnel.
System Alarm and Trouble contacts are provided
for connection to remote monitoring equipment.
Additionally, the annunciator can display other facility alarms such as Heat or Temperature sensors, as well as
signals from Fire Alarm and Security systems. This provides a convenient location to monitor the status of all
the systems important to your operation.
Model DL-2
Operation
The DL-Series utilizes a special linear sensing cable, featuring two (2) insulated conductors with two supervisory return wires. This 1/4” diameter bundle is both tough and fexible. The special insulation, along with
AquaALERT’s traditional AC supervision, prevents contamination by dirt and virtually eliminates damage from
electrolysis.
When water contacts the cable anywhere along its length, an audible alarm will sound at the AquaALERT
annunciator panel. The display will indicate, in feet, the distance to the location where water has contacted the
cable. The audible alarm will activate and the system Alarm contacts will change state. The audible can be
silenced but the alarm will continue to be displayed until the water is cleaned up and the annunciator is reset.
When the cable or associated wiring is damaged, or disconnected from the controller, the system will indicate
a “Trouble” condition. An audible will sound to alert the operator. The audible can be silenced and the Trouble
indication will remain until the problem is corrected.

DL
LCD-240 LD-2000
1 2 3 4 5
Pwr
Data
+
-
RX +
RX -
Pwr
+
-
W
B
G R
To Water Leak Sensing Cable
Power Supply
Display on Door
Controller in Backbox
A B S
+
-
n/c
n/c
120 vac input
24 vdc output
H
N CAUTION
120 VAC
Rear View
NO C NC
Contacts
SERIES
DISTANCE
LOCATING SYSTEM
1.
Main input power must be from appropriate
disconnect device, as per code requirements.
2.
Wiring must be routed and supported in
manner that prevents strain or damage to
wire and connectors.
3.
Conduit provides grounding.
NOTE: CABLE LENGTH SHOULD BE LIMITED
STRAINRELIEF
WITH RUBBER BUSHING
CONNECTORS
STARTER CABLE
TO 1400 FEET PER ZONE, MAXIMUM.
DLC-100
4“ SQUARE BOX
TO CONTROLLER
CONDUIT
END OF LINE DEVICE
18 Gauge THHN
four-conductor cable
with jacket. Install
per local codes.
NOTE: If the start of the DLC-100 cable is
within 10’ of the controller, the starter
cable can be connected directly to the
controller.
DLC-50