General Description
The LEDArray Series Indoor displays are LED message centers designed for light industrial, commercial and office use. They quickly display large amounts of information in 8 colors and 3 rainbow effects (red only versions are also available). These message centers are among the brightest and sharpest indoor displays available.
Messages are entered through a wireless, remote control keyboard, as easy to understand and use as an ordinary calculator. Exclusive 3-step message entry with Automode programming eliminates the need to learn complicated programming procedures. Within seconds, the user can create exciting visual messages that cannot be ignored. 10 preset mass notification messages are provided.
In applications requiring multiple units to communicate important informa­tion, Alpha displays can be networked and connected to a PC, to form a powerful integrated visual information system throughout your plant or business facility, or the LED Contact Interface Panel can be used for Fire Alarm or Manual type activation.
1
Rev. 1
Page 2
MNS
SERIES
LEDARRAY
INDOOR DISPLAY
LEDArray Specifications - L.E.D. Mass Notification System
Sizes
Case Dimensions: (With power supply)
Approximate Weight:
Display Dimensions:
Display Array:
Characters Displayed in one-line (minimum):
Display Memory:
Pixel Size (Diameter):
Pixel (LED)Color: Red
Center-to-Center Pixel Spacing (Pitch):
Character Size:
Character Set:
Memory Retention: One month typical
Message Capacity:
Message Operating Modes:
Built-in Animations:
0.2" (.05 cm)
0.3" (0.8 cm)
2.1" (4.3 cm)
Block (sans serif), decorative (serif), upper/lower case,, slim/wide
81 different messages can be stored and displayed
–25 consisting of: Automode, Hold,
Interlock, Roll (6 directions), Rotate, Sparkle-On, Twinkle, Spray-on, Slide-Across, Switch, Wipe (6 directions), Starburst, Flash, Snow, Scroll Condensed Rotate
–Continuous message entry with automatic
centering in any mode –User programmable logos and graphics – Five hold speeds
Cherry Bomb Exploding, Don’t Drink and Drive, Fireworks, Slot Machine, No Smoking, Running Animal, Moving Auto, Welcome and Thank You
LEDArray
28.9"L x 2.1"D x 4.5"H (73.4 cmL x 5.3 cmD x 11.4 cmH)
6.25 lbs (2.13 kg.)
27"L x 2.1"H (68.6 cmL x 5.3 cmH)
90 x 7 pixels
15 characters
7,000 characters
Serial Computer Interface:
Power: Input: 5A, 35W, 7 VAC
Power Cord Length:
Keyboard:
Case Material:
Limited Warranty:
Agency Approvals: – 120 VAC Model: Power supply has UL/CSA listing.
Operating Temperature:
Humidity Range:
Mounting:
RS232 and RS485 (multi-drop networking
for up to 255 displays)
Options:Ethernet LAN adapter
120 VAC OR 230 VAC adapter available
10 Ft. (3m)
Handheld, Eurostyle, IR remote operated
Molded plastic
One-year parts and labor, factory servicing
– 230 VAC Models: Complies with EN 60950:
1992 (Europe).
– FCC Part 15 Class A
– Marked
32°to 120°F, 0°to 49°C
0% to 95% non-condensing
Hardware to accommodate ceiling or wall mounting
Real-Time Clock: Date and time, 12 or 24 hour format,
maintains accurate time without power for up to 30 days typical
POWER REQUIREMENTS
Signs require 115 VAC input power for the plug-in transformer. Use an Exit Sign branch circuit for power. Power consumption @ 115 VAC: Approximately 113 ma in standby mode & Approximately 300 ma typical message.
2
Rev. 1
Page 3
LEDARRAY
INDOOR DISPLAY
MNS
SERIES
LEDArray Mounting Instructions
Model
(weight)
PPD
(1 lb 5 oz, 595.35 g)
LEDArray
(6.25 lb, 2.83 kg)
MegaDot
(12.25 lbs, 5.6 kg)
Mounting Instructions
Wall
Ceiling mounts
9 3/8" (23.8 cm) apart
Wall mounting holes 4" (10.2 cm) apart
Flip-up ceiling mounts 24" (61 cm) apart
1
Wall mounting holes 24" (61 cm) or 16" (40.6 cm) apart
or A mounting kit can be used to mount the sign on a wall, ceiling, or counter. (The kit contains brackets that attach to the end of the sign and can swivel.)
1. Attach two wall brackets in the mounting kit to a wall 46 3/4” (118.7 cm) apart. (measured from the center of each bracket).
2. Attach the mounting brackets to the sign as shown.
Wall mounting distance
Lock washers
The mounting bracket and screws are included.
The flip-up ceiling mounts will come out if the sign is turned over.
Using the mounting kit and a chain (not supplied in the kit), mount the sign from the ceiling as shown:
CounterCeiling
The mounting bracket and screws are included.
The sign will stand up if placed on a counter. However, for greater stability, use a mounting kit.
The sign will stand up if placed on a counter. However, for greater stability, use the mounting kit:
FIG.
A
B
C
*D
See Pg. 4
*See Pg. 6
P/N
---
MNS-Cable
MNS-Adpt
MNS-Cntr
Figure 1
Enclosures
NOTE: LEDArray signs are for indoor use only and should not be continuously exposed to direct sunlight.
NOTE: Mounting hardware that is used to hang or suspend a sign must be able of supporting at least 4 times the
DESCRIPTION
Ferrite: Insert the end of the 4-conductor data cable (B) with the ferrite core into the RJ11 port on the electronic display - the ferrite core must be closer to the electronic display than it is to the modular network adapter.
RS485 1ft cable RS485 8ft cable Modular Network Adapter
Contact Monitor & Sign Controller
BEFORE MOUNTING A SIGN, REMOVE POWER FROM THE SIGN!
WARNING
Hazardous voltage. Contact with high voltage may cause death or serious injury. Always disconnect power to sign prior to servicing.
weight of the sign.
3
Rev. 2
Page 4
MNS
SERIES
LEDARRAY
INDOOR DISPLAY
DRY CONTACTS TO RS-485 DATA INTERFACE
Model: MNS-ctrl - for LEDArray and MegaDot signs
The ALPHA Discrete Input Interface allows messages to be displayed on standard LEDArray electronic signs by using simple on/off contacts to trigger messages that have been stored in a sign. The ALPHA Discrete Input Interface is designed for low-voltage applications.
Messages to be displayed are stored in a sign using either:
• Infrared handheld remote control
• Adaptive software such as ALPHA Messaging software
CPU / Input Module — serves as an interface between the Input Modules and LEDArray signs. Up to four Input modules can be used, depending on the Operating Mode used. The eight, dry contact inputs of each Input Module can be configured to one of five possible Operating Modes:
— Mode Ø: Discrete Fixed — Mode 1: Momentary Triggered — Mode 2: Binary Coded Decimal (BCD) — Mode 3: Binary — Mode 4: Counter
Power Module*not shown* — supplies power to the CPU Module / Input Modules
Figure 1
(see component descriptions on other side)
GN
YL
A
B
C
CONNECTIONS TO NETWORK ADAPTER
Red (-) Differential: Connect to YL (Yellow Terminal)
Black (+) Differential: Connect to BK (Black Terminal)
Drain Wire (Shield): Must be continuous throughout network.
NOTE: Only connect to RD (Red Terminal) if the sign is a 4000, 7000 or 9000 series.
These modules are installed in a 12”x12”x4” deep box with a hinged door and cam lock to prevent unauth­orized access. The inputs to the modules are pre-wired to terminal blocks for easy installation. A pair of wires from your dry contact(s) is all that is needed to activate the associated messages(s). The messages are pre-programed but can easily be changed with a hand-held remote or laptop computer.
BR
WH
BL
OR
BK
RD
SHLD
– RS485 (Red)
+ RS485 (Black)
CPU/Input Module
SH. POS. NEG.
1 2
Side View
4
Rev. 2
Page 5
LEDARRAY
INDOOR DISPLAY
Operating Modes
NOTE: Only one Operating Mode can be used at a time. For example, if three Input Modules were
connected together, all three modules would have to use the same Operating Mode.
NOTE: The MNS-Cntrl has been pre-set at the factory.
MNS
SERIES
Description:
Module configuration:
Maximum no. of messages:
Maximum no. of inputs:
When an input (IØ - I7) is high, the associated sign message is displayed. It is possible to have several messages running simultaneously on a sign.
Minimum configuration
Power
Module
internal jumper settings:
32
32 (8 inputs per module x 4 Input Modules connected)
CPU
Module
Input Module
Input
Module
AØ = Ø A1 = Ø A2 = Ø
Input
Module
AØ = 1 A1 = Ø A2 = 1
Input
+++
Module
AØ = Ø
A1 = 1 A2 = 1
+
Input
Module
AØ = 1 A1 = 1 A2 = 1
NOTE: The MNS-Cntrl has been pre-wired at the factory.
Power Module
-
+
CPU Module
+
-
Input 24 VDC Nominal
+18-36 VDC
+
Power Module
-
+
CPU Module
5 VDC Out
+
-
+18-36 VDC
Factory Cable
+
Power Supply
Module 2
Sinking (NPN) circuit:
Input Module
Sinking (NPN)
24 VDC
COM(ØV)
I7
I6
I5
I4
I3
I2
I1
COM(ØV)
NON-ISOLATED
NOTES: Standby current is 83ma plus 20ma for each activated message.
All Input Modules are internally fused. Wire the modules according to local electrical code.
+18-36 VDC
COM(Ø
V) is internally connected.
24 VDC is internally connected.
+
Input Module Sinking (NPN)
24 VDC
COM(ØV)
I7
I6
I5
I4
I3
I2
I1
COM(ØV)
ISOLATED
CPU / Input
Module 1
5
Rev. 1
Page 6
MNS
SERIES
LEDARRAY
INDOOR DISPLAY
Connecting Using RS-485 Network
Networking one or more signs (shielded)
NOTE: When signs are networked to the CPU Module, all the signs must be the same model when ALPHA Messaging software is used.
YL
GN
BR
WH
BL
OR
BK
RD
SHLD
– RS485 (Red)
+ RS485 (Black)
Connect RED wire from RS485 cable to YL screw.
Connect BLACK wire from RS485 cable to BK screw.
ONLY connect SHIELD wire from RS485 cable to RD screw if the sign is a
Series 4ØØØ or Series 7ØØØ. For LEDarray, connect the two SHIELD wires to each other, but not to the RD screw.
RS485 cable
Mass Notification Signs
Connecting using RS-485 Network.
1-foot RS485 cable or
8-foot RS485 cable
Enclosures
4"
Modular Network
Adapter
To next
sign
Install EOL Device on last sign in network (supplied with controller).
1 7/8"
Door
12"
MASS NOTIFICATION SYSTEM
SYSTEM CONTACT / SIGN NETWORK INTERFACE
See Figure 1
Page 4
PWRL2
L1
(RS232/485)
DISPLAY
SERIALCOM
(RS232)
Use a twisted pair, 22awg with common shield.
Use modular adapter for network wiring. Connect to sign with RJ-11 cable.
Maximum = 4ØØØ feet (@ 96ØØ baud)
28.9"
Backbox
12"
MODEL G1212
POWER
FRONT VIEWSIDE VIEW
4.5"
LEDARRAY DISPLAY
SIGN IS 2.1” DEEP
DISPLAY AREA IS 27”L x 2.1”H
MNS-CONTROLLER
6
Rev. 1