LCD-240 with
GRAPHIC MAP
Graphic Annunciators * Water Leak Detection
Fireman’s Smoke Control Panels * ARA Systems
109 Portwatch Way Wilmington, N.C. 28412 Phone: (800) 251-2512 Fax: (800) 251-9878
Internet: www.ledinc.com Email: sales@ledinc.com
Technical Specifications
Standby Voltage = 12 to 24VDC
A wall-mount transformer is
provided. Loss of power or data
will result in a Trouble Condition
at the FACP
Baud Rate = 9600
LCD
SERIES
Bits = 8
Stop = 1
Parity = 0
Selectable for RS-232 or RS-485
data
Temperature: 32° to 100°F
Humidity: Non-condensing
Current: 125 ma.
Model LCD-240/1G
General Description
The LCD-240 was designed for use on a fire alarm system printer port. The
unit displays the same information the would be printed on a printer. When embedded in a Graphic Map, the LCD-240/G provides complete annunciation
without using LEDs or lamps.
Each alarm initiating device will be shown on the graphic map, along with its
corresponding address. When an alarm occurs, the unit will display the alarm
addresses, and a descriptive message. The address shown on the LCD display is then correlated to the device location on the map.

LCD
SERIES
1. For RS-232 operation, Jumper pins 1 & 2 on J1, J2 and J3 (shown for RS-232).
2. For RS-485 operation, Jumper pins 2 & 3 on J1, J2 and J3.
* RS-485 Input: Connect TXA to TB-1, Terminal 4.
Connect TXB to TB-1, Terminal 3.
3. For RS-485 operation, the CCM must be connected to a data converter. The converter OUTPUT is connected
to the individual LCD-240 unit(s). Consult LED for assistance.
LCD-240 with
GRAPHIC MAP
TB-1 TB-8
12/24 VDC Input
TX 1.
-
SG 2.
RTS 3.
+
CTS 4.
NC 5.
RX 6.
1 2 3 4 5 6 7 8
+
-
R X S C D U
J-1
J-2 J-3
1 2 3 1 2 3 1 2 3
LCD-240 REAR VIEW
Inter-Connections LCD-240CCM
8 to 12 volts
TXB
TXA
Connect Momentary Switches
for Scroll UP/DOWN Function
Power Input
R (3)
S (5)
X (4)
+
-
2
12 vdc
1
Ordering Information
A drawing is required showing the actual graphic representation needed for your project. The exact location of the indicator
points should be shown and identified by a legend. Mark the Annunciator location on the plans so that the artwork can be
oriented properly with a “You Are Here” designation.
Graphic sizes are shown below, according to model number. The maximum area available for artwork is the outside dimension, less two inches. We will work from your blueline, copy, fax, sketch, email or CAD file. Please note: a full size, inked
mylar, from your CAD drawing, will speed production.
Please complete the annunciator Order Form and send with drawing. If Order Form is not available, indicate how annunciator will be activated and list any specifications required.
4" 7/8"
"W"
WIDTH x HEIGHT
23 7/8” x 14”
23 7/8” x 24 1/2”
Vertical or Horizontal
"H"
MODEL
LCD-240/1G
LCD-240/2G
NOTE: Units May Be Mounted
For Semi-flush mounting, add 3” to
overall “W” and “H” dimensions.
Backbox
Graphic Door
Consult the factory regarding custom sizes, products, options or special requirements.