Light Engineered Displays Fuel Leak Control Panel User Manual

Page 1
A Division of: Light Engineered Displays, Inc. 109 Portwatch Way Wilmington, N.C. 28412 Phone: (800) 251-2512 Fax: (800) 251-9878 Internet: www.ledinc.com Email: sales@ledinc.com
General Description
The AMC-5107 offers all of the features you need for your basic leak and level detection applications. It works with all of the standard 5000 series liquid sen­sors and F4000 vapor sensor.
The AMC-5107 is suitable for large or small scale tank and piping installa­tions, for secondary containment and interstitial monitoring, and for fuel oil storage or bulk water tanks. Wherever the possibility of leaking petroleum liquid, vapor or water can occur, and for level monitoring, trust the AMC-5107 for worry-free performance.
AMC-5107
LEAK /LEVEL / VAPOR
For liquid substance monitoring:
Petroleum, alkalines, acids, water, etc...
MONITOR
AMC
SERIES
Features
Easy to wireCan be powered from 12VDC or
10VAC
Level monitoring, leak detectionMultiple sensor input capabilityProgrammable internal relay6 liquid zones, Intrinsically Safe1 vapor zone, non I-STwo stage self-testRelay (dry contacts) can be set
normally energized. Rated 5A @ 250VAC/30VDC
Specific channels can be tied to relayFront panel label for sensor locationsAlarm acknowledge
(as on AMC-5100) Acknowledged audio alarm will reactivate after a 2 hour delay
Benefits
Affordable, low pricedReduces insurance coverageVery effective for small installationsCapable of a wide variety of
applications No documentation needed to find sensor location
Will reset on power failure conditionsOnly have specific channels trigger
relay for selective alarming ability (i.e. Shut down on petroleum leak, not on water).
Page 2
AMC
SERIES
Specifications
AMC-5107
LEAK /LEVEL / VAPOR
MONITOR
AMC-5107 Monitor Unit
Dimensions: 6.125”W x 4.25“H x 2.d”D (15.5cm W x 13.5cm H x 6.5cm D) Enclosure Material: PVC
Power Requirements
Main Power: 12 VDC or 10 VAC @ 300 mA max for an external Class 2 transformer or adapter.
Liquid Section Features
Monitoring Capability: 6 channels / zones. Protection Circuit: Diode/resistor / fuse IS barrier. Detectable Liquids: Water, petroleum-based products, alkalies, some acids, etc. (consult factory).
Liquid Sensor Types
Normally Open circuit (5000 series, 5008, 5010 series, 5014P, 5015, 5020 and 5025). Normally Closed circuit (5010 reversed, 5016, 5016P and 5025). Dual N/O & N/C circuit (5002B, 5007, 5011, 5017)
Note:
The 5020 probe can be used with a reconfigured 5107 monitor, via the water / petroleum select jumpers.
Warranty
System Components: 1 year, parts and labor (subject to standard LED terms and conditions).
Vapor Section Features
Monitoring Capability: 1 channel / zone. Detectable Vapors: Petroleum based products. Sensor: F4000 with V403 transmitter module.
Indicators and Alarms
Power Indicator: 1 Red LED bar. Liquid Alarm Indicators: 6 Red LED bars. Vapor Alarm Indicators: 1 Red LED bar. Test Indicator: 1 Red LED bar. System Failure Indicator: 1 Red LED bar. Alarm Acknowledge Switch: External (front panel). Audio Alarm Buzzer: Internal
Output
One SPST relay, common to all channels.
Operating Temperature Range
0 to +40 ºC (+32 to +104 ºF)
IMPORTANT: LED products should be used in compliance with applicable federal, provincial, state and local laws and regulations. Product selection should be based on physical specifications and limitations and compatibility with the environment and materials to be handled. LED MAKES NO WARRANTY OF FITNESS FOR A PARTICULAR USE. All information and specifications in the literature are based on the latest product data available at the time of publication. LED reserves the right to make changes at any time in price, materials, specifications and to discontinue models without notice or obligation.