GANG MOUNTED
DIRECTORY
Graphic Annunciators * Water Leak Detection
Fireman’s Smoke Control Panels * ARA Systems
109 Portwatch Way Wilmington, N.C. 28412 Phone: (800) 251-2512 Fax: (800) 251-9878
Internet: www.ledinc.com Email: sales@ledinc.com
Technical Specifications
1. Standby Voltage
12 or 24 vdc
2. Standby Current
0 ma
3. Alarm Current
Increases approximately 20 ma per
activated indicator
4. Indicators
Super Bright LED’s “Non-Polarized”
Red for Alarm • Yellow for Trouble
5. Activating Voltage
-Specify Positive or Negative
12 or 24 vdc
6. Operating Temperature
32°-100°F (0°-38°C)
7. Intended for indoor / dry location
DA-15AS (left)
& DA-5A (right)
DA
SERIES
General Description
The Da-Series annunciators are available in five, ten, fifteen, twenty, twenty-five and thirty zone
models. The annunciators can be configured with a red LED or a red and yellow LED per
window. The windows have pull-out tabs for easy field labeling.
The Da-Series annunciators use high-brightness LEDs and are available with an optional
audible alarm sonalert and silence switch. The audible is activated by an internal diode buss and
can be configured to sound upon alarm, trouble, or alarm and trouble inputs. The silence switch
includes a ring-back feature to insure the switch is not left in the silence position.
The DA-Series Annunicators are designed to be mounted on an ordinary switchbox. There are
five input zones per gang. One extra gang is required to accomodate the optional sonalert and
silence switch. NOTE: The alarm audible is not available on the 30 zone model. The annunciator
has a bright red aluminum faceplate that mounts directly to the switch box. Units can be flush or
surface mounted.
Optional gaskets are available for use in outdoor applications. However, the annunciators should
not be mounted where direct contact with rain is expected. Install under overhang.

DA
SERIES
Specifications
DIRECTORY
ANNUNCIATORS
Number
Model
Number
DA-5A 5 5744S-1 1 DA-RT-1
DA-5AS 5 • • • 5744S-2 2 DA-RT-2
DA-5AT 5 5 5744S-1 1 DA-RT-1
DA-5ATS 5 5 • • • 5744S-2 2 DA-RT-2
DA-10A 10 5744S-2 2 DA-RT-2
DA-10AS 1 0 • • • 5744S-3 3 DA-RT-3
DA-10AT 1 0 1 0 5744S-2 2 DA-RT-2
DA-10ATS 1 0 1 0 • • • 5744S-3 3 DA-RT-3
DA-15A 1 5 5744S-3 3 DA-RT-3
DA-15AS 1 5 • • • N/A 4 DA-RT-4
DA-15AT 1 5 1 5 N/A 3 DA-RT-3
DA-15ATS 1 5 1 5 • • • N/A 4 DA-RT-4
DA-20A 2 0 N/A 4 DA-RT-4
DA-20AS 2 0 • • • N/A 5 DA-RT-5
DA-20AT 2 0 2 0 N/A 4 DA-RT-4
DA-20ATS 2 0 2 0 • • • N/A 5 DA-RT-5
DA-25A 2 5 N/A 5 DA-RT-5
DA-25AS 2 5 • • • N/A 6 DA-RT-6
DA-25AT 2 5 N/A 5 DA-RT-5
DA-25ATS 2 5 2 5 • • • N/A 6 DA-RT-6
DA-30A 3 0 N/A 6 DA-RT-6
DA-30AT 3 0 3 0 N/A 6 DA-RT-6
Alarm
of Zones
Trouble
Common
Trouble
LED
Common
Trouble
Audible
Silence
Switch
Surface Mounting
Wiremold Catalog
Number
Flush Mounting
Standard
Gangable Switch
Electrical Box
Weatherproof
Gasket
Wiring Diagram
M o d e l DA- 5AT S Sho w n
1
TB-1
2
3
4
Son aler t
(-) connection only
needed for models
w/ optional sonalert.
+
CM
+
-
-
T1
A1
T2
A2
T3
A3
T4
A4
(+) connection for
models WITHOUT
sonalert option.
T5
A5
TB-2
NOTES: 1) The annunciator operates at 12 to 24 vdc. One common connection, (specify com+ or com - ), is required per for all
LEDs, plus a switch leg to activate each zone LED.
2) The Alarm inputs are A-1 through A-5 (shown wired) and are red LEDs. The Trouble LEDs are T-1 throughT-5 and
feature yellow LEDs. (unit shown has a common positive and requires a minus to light each LED).
3) The DA-Series sonalert will self activate from an internal diode buss on the circuit board. The sonalert is features a
momentary push button silence switch. When all alarms or troubles are cleared, the sonalert is ready to sound again.
Typical FACP
T1
A1
A2
A3
A4
A5
Trouble Zone Outputs
Alarm Zone Outputs
24 vdc
FAC P A ux P owe r
(-)
(+)