AREA OF RESCUE
ASSISTANCE PANEL
Graphic Annunciators * Water Leak Detection
Fireman’s Smoke Control Panels * ARA Systems
109 Portwatch Way Wilmington, N.C. 28412 Phone: (800) 251-2512 Fax: (800) 251-9878
Internet: www.ledinc.com Email: sales@ledinc.com
Features
Meets ADA requirements
Provides audible and visual
communication
Easy push-button operation
Secure key-locked enclosure
Plenty of room for wiring
Dependable solid-state circuits
Panel size - 9”w X 18”h X 4”d
ST
SERIES
Model ST-8
System Operation
To place a call, the person needing assistance pushes the button on the call station. The LED on the
call station will flash to inform the user that the call has been sent. The control panel will indicate the
incoming call with an audible alarm and a flashing LED. The LED will identify the specific area
requesting help.
The operator pushes the acknowledge button to silence the audible. The call LED will go from flashing to steady to inform the user that the request for help has been received. The LED will remain lit
until the control panel is reset. If additional calls are received, the new calls will resound the alarm
and the new request will be identified with a flashing LED. Intercom capability is not available on ST
systems.
General Description
Area of Rescue Assistance system shall have push-button control circuits and indicator lights for Call
and Call Received functions. The Control Panel shall include power supply, status indicators, silence
and reset switches, and system test button. The components shall be mounted on a faceplate and
clearly marked for their respective uses. The faceplate shall be surrounded by an extruded aluminum frame with a hinge for attachment to a 4” deep enclosure. The assembly will swing open for
easy wiring and is key-locked closed to prevent tampering.

AREA OF RESCUE
ST
SERIES
ASSISTANCE PANEL
Typical Wiring Diagram
CALL
STATION
(1)
CALL
STATION
(8)
CALL FOR HELP
1. Push Button
2. LED Flashes
3. LED changes to steady
when call is received
43
Sw. (Com.)
21
LED (+)
LED (-) 2v
Sw. (N.O.)
PUSH
CALL FOR HELP
1. Push Button
2. LED Flashes
3. LED changes to steady
when call is received
43
Sw. (Com.)
21
LED (+)
LED (-) 2v
Sw. (N.O.)
PUSH
R
R
Audible
Parallel with LED
Audible
Parallel with LED
SW.
RESET
(V) ADJ.
(-)V
(+)V
GROUND
LINE
NEUTRAL
TB-1
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
12VDC
01
02030405060708
02
01
+ POWER IN
-
+ INDICATOR COM
SONALERT OUT.
LAMP TEST
ACK. SWITCH
OPTOCOUPLER COM.
08
07
06
05
04
Sw. (N.O.)
03
02
01
OUTPUTS
TO
Sw. (Com.)
-
01020304050607
+++
+
---
- -
-- -
115VAC
115VAC TO 24VDC
080706
050403
INPUTS
FROM
08
100 Ohms 1Watt
1N4002 Diode
PS-123X
S-25-12
TB-3
OUTPUTS
TO
LED (-) 2v
BOARD #___
OUT TO LED (+)
+
TB-2
1
(+)
(Optional)
FACTORY NOTES
INPUTS 1k
OUTPUTS 1k
3022 CHIPS
FLASHING LEDS
12VDC RELAYS
RIBBON
CONNECTOR
SOCKETS
1
(--)
12vdc Battery
Notes
1. Power Input is to be fused. Fuse at 2 amps.
2. Install Ribbon Connectors with the stripe facing “up”.
3. Alarm Device must switch ______ to activate
indicators.
4. Standby current consumption is approximately 35
milliamps. Each indicator, when activated, adds 20
milliamps.
5. The numbered field inputs correlate to the enclosed
print.
(-)