Light Engineered Displays ARA Panel User Manual

Page 1
AREA OF RESCUE
ASSISTANCE PANEL
Graphic Annunciators * Water Leak Detection Fireman’s Smoke Control Panels * ARA Systems
Internet: www.ledinc.com Email: sales@ledinc.com
Features
Meets ADA requirements Provides audible and visual
communication
Easy push-button operation Secure key-locked enclosure Plenty of room for wiring Dependable solid-state circuits Panel size - 9”w X 18”h X 4”d
ST
SERIES
Model ST-8
System Operation
To place a call, the person needing assistance pushes the button on the call station. The LED on the call station will flash to inform the user that the call has been sent. The control panel will indicate the incoming call with an audible alarm and a flashing LED. The LED will identify the specific area requesting help.
The operator pushes the acknowledge button to silence the audible. The call LED will go from flash­ing to steady to inform the user that the request for help has been received. The LED will remain lit until the control panel is reset. If additional calls are received, the new calls will resound the alarm and the new request will be identified with a flashing LED. Intercom capability is not available on ST systems.
General Description
Area of Rescue Assistance system shall have push-button control circuits and indicator lights for Call and Call Received functions. The Control Panel shall include power supply, status indicators, silence and reset switches, and system test button. The components shall be mounted on a faceplate and clearly marked for their respective uses. The faceplate shall be surrounded by an extruded alumi­num frame with a hinge for attachment to a 4” deep enclosure. The assembly will swing open for easy wiring and is key-locked closed to prevent tampering.
Page 2
AREA OF RESCUE
ST
SERIES
ASSISTANCE PANEL
Typical Wiring Diagram
CALL
STATION
(1)
CALL
STATION
(8)
CALL FOR HELP
1. Push Button
2. LED Flashes
3. LED changes to steady when call is received
43
Sw. (Com.)
21
LED (+) LED (-) 2v Sw. (N.O.)
PUSH
CALL FOR HELP
1. Push Button
2. LED Flashes
3. LED changes to steady when call is received
43
Sw. (Com.)
21
LED (+) LED (-) 2v Sw. (N.O.)
PUSH
R
R
Audible
Parallel with LED
Audible
Parallel with LED
SW.
RESET
(V) ADJ.
(-)V
(+)V
GROUND
LINE
NEUTRAL
TB-1
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
12VDC
01
02030405060708
02
01
+ POWER IN
-
+ INDICATOR COM
SONALERT OUT. LAMP TEST ACK. SWITCH
OPTOCOUPLER COM. 08
07
06
05 04
Sw. (N.O.)
03 02
01
OUTPUTS
TO
Sw. (Com.)
-
01020304050607
+++
+
---
- -
-- -
115VAC
115VAC TO 24VDC
080706
050403
INPUTS
FROM
08
100 Ohms 1Watt
1N4002 Diode
PS-123X S-25-12
TB-3
OUTPUTS
TO
LED (-) 2v
BOARD #___
OUT TO LED (+)
+
TB-2
1
(+)
(Optional)
FACTORY NOTES
INPUTS 1k OUTPUTS 1k 3022 CHIPS FLASHING LEDS 12VDC RELAYS
RIBBON
CONNECTOR
SOCKETS
1
(--)
12vdc Battery
Notes
1. Power Input is to be fused. Fuse at 2 amps.
2. Install Ribbon Connectors with the stripe facing “up”.
3. Alarm Device must switch ______ to activate indicators.
4. Standby current consumption is approximately 35 milliamps. Each indicator, when activated, adds 20 milliamps.
5. The numbered field inputs correlate to the enclosed print.
(-)