Light Engineered Displays AquaAlert Installation Guide

Page 1
A Division of: Light Engineered Displays, Inc. 109 Portwatch Way Wilmington, N.C. 28412 Phone: (800) 251-2512 Fax: (800) 251-9878 Internet: www.ledinc.com Email: sales@ledinc.com
INSTALLATION
MANUAL
DL
SERIES
Getting Started
1. Installation of the system will be easier and more accurate if you utilize a test unit available from AquaALERT at no charge. This will provide for a convenient means to “map” the system as well as allow for any problems to come to the immediate attention of the installer.
2. Mount the back box on the wall.
3. Set a junction box at the starting point for the water detection cable.
4. Pull three wires, (18 ga. stranded THHN or a three conductor cable with jacket), from the J-box to the backbox. NOTE: Local codes must be followed.
5. Install the DL-SC cable to wiring interface in J-Box and connect the three wires as indicated. Run Sensing cable through the J-box and connect to interface. Use a rubber grommet or a non-metalic strain relief to protect the sensing cable.
6. Route the cable as shown on the plans. Secure the cable every five feet with a self-stick cable clamp. MAKE SURE TO MAINTAIN AT
LEAST EIGHT FEET AWAY FROM ANY HVAC UNIT!
7. Continue to add sections to achieve the required length. Place EOL device on the end of the last section.
8. Check your connections and apply power to the system.
Troubleshooting Tips
Test each completed section before adding the next. Energize the test unit. With the EOL device NOT connected, a yellow Trouble indica­tor will light. Install EOL device and reset the test unit. The Trouble indicator should go out. If it does not, inspect your connections. If you still have a problem, please consult the trouble­shooting guide (on reverse side), or consult the factory.
Troubleshooting Tips
1. When all cable is in place and there are NO Trouble conditions, the system can be mapped.
NOTE: Leave the map switch in a normal position. You may operate the sonalert disable switch when mapping the system.
2. Use the as-installed cable plan as your guide. Go to the END of cable and make the first test 10’ from the ends. Make additional tests every 10 feet. Every 20 feet is satisfactory for larger systems.
Best results are obtained by using a shallow dish of water to initiate the alarms. Make sure to start at the end of the line and continue forward until you reach the cable starting point. Dry the cable with a paper towel and reset the panel after each test. Record the footage read­ings on the plan. The results will be used to produce an accurate graphic map for the system.
9. Press the TEST button. The cable length will be displayed and should be within +{ 5% of the total cable length. Please depress the TEST button for 30 seconds for proper alarm and cable length verification.
3. When testing is complete, make sure to return the sonalert disable switch to the Normal position and operate the system reset switch.
4. Return the completed as-built plan (and test unit) to AquaALERT for final processing.
Page 2
INSTALLATION
DL
SERIES
MANUAL
Troubleshooting Guide
TROUBLE
1. Blank Display. No Power On LED.
2. Blank Display. Power LED is ON.
3. No audible Alarm.
4. Cannot silence the Audible Alarm.
5. Cannot reset the DLS controller.
6. System TEST does not function.
7. Incorrect distance displayed.
8. Flashing Display.
9. Cannot turn Trouble LED off.
10. Incorrect display during test.
11. Summary alarm not transferring.
12. Will not detect water.
13. Alarms randomly when reset.
14. Display active after reset no alarm.
PRIMARY ACTION
Verify unit power switch is ON.
This indicates Normal operation.
Verify unit power switch is ON.
Operate RESET switch.
Cable is wet or shorted.
Unit defective - call for service.
Water is in more than one place.
Unit defective - call for service.
Check cable for OPEN connections.
Cable routed too close to HVAC Unit.
Check Summary alarm connections.
Check wiring to water sensing cable.
Check cable with shorting clip.
Check Humidity conditions.
Verify mapping switch is OFF.
SECONDARY ACTION
Verify power connections.
--
Verify Audible Alarm Disable is OFF.
Move audible DISABLE switch to ON
and contact factory for service.
--
--
Cable under HVAC unit is wet from
moisture droplets too small for Alarm.
--
--
Water detected during TEST cycle.
--
Allow 30 sec. for alarm verification.
Move cable from under HVAC unit.
---