Lifebreath 300DCS, 155MAX, MAXTOP, 195DCS, 200MAX User Manual

...
TI-84R-NE
0207
Residential Heat Recovery (HRV) and Energy Recovery (ERV) Ventilators
MANUFACTURED WITH
CONTROLAIR 15 ELECTRONICS
Models 95MAX, 155MAX, 155ECM, 155MAXRX, 200MAX, 200MAXRX, MAXTOP, 195DCS, 300DCS, 200ERV, 200ERVD
Operation and Installation Manual
New Auto Dehumidistat Function
dehumidistat when outdoor temperatures
exceed 15°C (59°F).
2
Introduction .........................................................................2
Warranty..............................................................................2
ERV Questions & Answers .................................................3
Climate Map ........................................................................4
Technical Data - Model 95MAX ..........................................5
Technical Data - Model 155MAX ........................................6
Technical Data - Model 155ECM ........................................7
Technical Data - Model 155MAX RX ..................................8
Technical Data - Model 200MAX ........................................9
Technical Data - Model 200MAX RX ...............................10
Technical Data - Model MAXTOP .....................................11
Technical Data - Model 195DCS.......................................12
Technical Data - Model 300DCS.......................................13
Technical Data - Model 200ERV.......................................14
Technical Data - Model 200ERVD ....................................15
Function and Control.........................................................16
Glossary of Terms.............................................................16
Selecting Speeds and Modes of Operation.......................17
The Control Pad Mounted in the Control Module..............18
Optional Remote Controls.................................................19
Using the Dehumidistat .....................................................20
Schematic Diagram - Model 95MAX .................................21
Installation .........................................................................22
Installing Air Ducts ...........................................................23
Supply Air Ducting.............................................................24
Stale Air Exhaust System..................................................24
Dampers and Grilles .........................................................24
Installation Diagrams ..................................................25-28
Air Flow Balancing ...........................................................29
Maintenance Routine For HRV .........................................31
Maintenance Routine For ERV .........................................32
Troubleshooting ................................................................33
Interlocking HRV Operation to an Airhandler/
Furnace Blower .................................................................34
Wiring Diagrams ..........................................................35-36
Before installation, careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment, i.e. a forced air furnace or air handler, operating at a higher static. After installation, the compatibility of the two pieces of equipment must be con­firmed by measuring the airflow’s of the Heat Recovery Ventilator (HRV) Energy Recovery Ventilator (ERV) by using the balancing procedure found in this manual.
It is always important to assess how the operation of any HRV/ERV may interact with vented combustion equipment (ie. Gas Furnaces, Oil Furnaces, Wood Stoves, etc.).
NEVER install a ventilator in a situation where its normal operation, lack of operation or partial failure may result in the backdrafting or improper functioning of vented combus­tion equipment!!!
HRV - Aluminum Core
A Heat Recovery Ventilator (HRV) is designed to provide fresh air into a building while exhausting an equal amount of stale air. During the winter months, the incoming cold fresh air is warmed by utilizing the heat recovered from the stale air before it is exhausted to the outdoors. During sum­mer months when the indoor space is air conditioned, the Heat Recovery Ventilator will help in cooling the incoming fresh air with the stale air that is being exhausted.
ERV - Enthalpic Paper Core
An Energy Recovery Ventilator (ERV) is designed to pro­vide fresh air into a building while exhausting an equal amount of stale air. An ERV is designed for use in warm humid areas with heavy air conditioning use. The ERV will transfer both sensible and latent heat from the incoming fresh air to the outgoing stale air thereby reducing the load (due to ventilation) on the air conditioning system.
ERVs are not suitable for climates where the temperature drops below -4°C (25°F).
All Heat Recovery Ventilators carry a Lifetime Warranty on the heat recovery core and a 5 (five) year replacement parts warranty.
All Energy Recovery Ventilators carry a 5 (five) year war­ranty on the energy recovery core and a 5 (five) year replacement parts warranty.
During the warranty period, if any core experiences a failure or perforation caused by normal use while owned by the original purchaser, a replacement core (FOB our plant) will be supplied at no expense.
Table of Contents
Introduction
Caution
Warranty
LEAVE FOR HOMEOWNER
NOTE: Due to ongoing research and product development, specifications, ratings and dimensions are subject to change without notice.
TO BE COMPLETED BY CONTRACTOR AFTER INSTALLATION
Installing Contractor _________________________________________Telephone / Contact _____________________
Serial Number______________________________________________Installation Date ________________________
Model _________________________________________________________________________________________
IMPORTANT -
PLEASE READ THIS MANUAL
BEFORE INSTALLING UNIT.
3
What is the difference between an HRV and an ERV?
The core in an HRV (Heat Recovery Ventilator) trans­fers heat from one air stream to the other. This is called sensible heat. The term ERV (Energy Recovery Ventilator) is usually used to describe a unit with an enthalpic core that transfers moisture as well as heat from one air stream to the other. This (moisture transfer) is called latent heat.
Enthalpic - what does it mean?
Enthalpy is the term used to describe the energy content of air. This energy is a combination of the sen­sible and latent heat. Therefore, a core which transfers energy is called an enthalpic core.
Is an ERV better than an HRV?
NOT NECESSARILY! In cold climates such as most of North America, an HRV works better than an ERV. This is because the air inside the home during the win­ter months will be more humid than the outside air. An ERV would transfer the latent heat (humidity) from the exhaust air back into the incoming airstream. This will aggravate moisture problems in the home and encour­age the growth of mold and mildew. If the air in the home is too dry for comfort, an ERV will not help. A humidifier should be used to increase the humidity to a comfortable level.
Where do you use an ERV instead of an HRV?
An ERV is recommended for warm, humid areas with heavy air conditioning use. As there is no defrost in an ERV it is not recommended for areas where the tem­perature drops below -4°C (25°F).
Why transfer moisture in the summer (cooling season)?
The enthalpic core will allow moisture to be transferred from a humid air flow to a dry air flow. This property is useful in the cooling season if an air conditioning sys­tem is used to lower the indoor humidity. You will then have dry, cool air in the exhaust of the ERV, and warm humid air in the supply stream. With these conditions, the ERV will be able to transfer the moisture and heat of the supply air to the exhaust air. In this way, the ERV will supply to the home air which is cooler and drier than outside. Remember that an ERV is not a dehumidifier, and on its own will not take moisture out of the air.
So why use an ERV?
A properly operating air conditioner will not only lower the temperature in your house, but will also lower the humidity level. This prevents an uncomfortable cold
and damp situation. In fact, about 2/3 of the energy used by the air conditioner system is to remove mois­ture. Therefore, when ventilating in the summer, less moisture brought into the home means less work for the air conditioner, and energy savings for you.
During the winter, an ERV recovers some humidity from the exhaust air, reducing the need for humidifica­tion, if the required ventilation rate would make the home too dry.
What's the difference between this type of core and a rotary type?
Here's a list of characteristics of the fixed plate core.
1. No rotating parts, so maintenance is easy and the unit lasts a long time.
2. It is very flexible in terms of installation.
3. The core can easily be changed.
4. Because the supply and exhaust air streams are completely separate, there is very little cross leak­age of any dust or germs.
Can the core become clogged with dust?
Because the surface of the core is a turbulent flow area, dust sticks to it easily; however, because the inside of the element is a laminar flow area, virtually no dust sticks to it.
What is the maintenance?
About once a year you should use a vacuum cleaner to remove the dust from the core's surface. DO NOT WASH WITH WATER!
Is an air filter needed?
To prevent clogging of the core, an air filter should always be installed on the supply and exhaust sides of the core.
How much ventilation do I need?
During seasons when your windows and doors are closed, the ERV should operate continuously when the dwelling is occupied, and either continuously or inter­mittently when not occupied.
For most installations the ERV will normally be set to operate continuously on low speed with the option of going to high speed as the need arises. For example; if you are entertaining and there is a large number of people present (some may be smoking), the unit should be switched to high speed.
Your ERV may be equipped with automatic or manual switches, but all ERVs will have a manual speed con­trol override.
ERV Questions and Answers
4
5
Model 95MAX
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed fan operation. 120 VAC, .8 Amps.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of the cabinet designed to accept PVC rein­forced polyester straps that are supplied with the unit.
DEFROST
Recirculating defrost system.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resis­tance. Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, 20 ON/40 Recirculation mode, Recirculation mode (each mode has 5 speeds). Control pad can be removed from HRV and remotely mounted.
WEIGHT 52 lbs. (23.6 kg) Shipping Weight 56 lbs. (25.4 kg)
OPTIONS 99-104 Digital Electronic Timer - 20/40/60 min.
99-109 Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed
to accept remotely mounted Control Pad
99-163 Duct Heater w/ Electronic SCR Thermostat, 1Kw,6”
(150 mm)
99-185 Weatherhoods, Two - 5” (125 mm) c/w 1/4” (6 mm) mesh
screen
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.
TI-113-NE
0107
DIMENSIONS 95MAX inches (mm)
All units conform to CSA and UL standards.
Date: ___________________________________________
Tag: _____________________Qty: ___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency – takes into account all power inputs
Performance (HVI certified)
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 76 (36)
@ 0.2" (50 Pa) 73 (34)
@ 0.3" (75 Pa) 70 (33)
@ 0.4" (100 Pa) 66 (31)
@ 0.5" (125 Pa) 60 (29)
Max. Temperature Recovery 88%
Sensible Effectiveness @ 60 cfm (28 L/s) 32°F (0°C) 88%
*Sensible Efficiency @ 60 cfm (28 L/s) 32°F (0°C) 75%
*Sensible Efficiency @ 61 cfm (29 L/s) -13°F (-25°C) 68%
VAC @ 60HZ 120
WATTS / Low speed. 60
WATTS / High speed 150
Amp rating 0.9
5 - High Speed
18.5"
(470 mm)
24.5" (622 mm)
Removable
Heat Recovery
Core
Drain Pan
Drain spout
FRONT TOP
knockout for
side mounting of
EXHAUST return port
6" round collar
converted to oval
minimum
18 inches (459 mm)
required for
service access
SIDE
Hanging
straps (4)
16"
(406 mm)
Threaded inserts (4) at corners
SUPPLY
Fresh air
from outside
5" round collar
SUPPLY
Fresh air
to building
6" round
(conv. to oval)
collar
18.5"
(470 mm)
EXHAUST
Stale Air
to outside
5" round collar
EXHAUST
Return air
from building
Choice of port location Knockouts on top and side of unit (use 1 only) 6" round (conv. to oval)
collar supplied
80
5
75
70
65
Air Flow (c fm)
60
55
50
0 0.1 0.2 0.3 0.4 0.5 0.6
Static Pressure (in w.g.)
6
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed fan operation. 120 VAC, 1.0 Amps.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
DEHUMIDISTAT
Adjustable Internal Dehumidistat.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resis­tance. Insulated to prevent exterior condensation. Drain connections 2 ­1/2" (12 mm) OD.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, 20 ON/40 Recirculation mode, Recirculation mode (each mode has 5 speeds). Control pad can be removed from HRV and remotely mounted.
Weight 71 lbs. (32.5 kg) Shipping Weight 73 lbs. (33.5 kg)
OPTIONS 99-104 Digital Electronic Timer - 20/40/60 min.
99-109 Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed to
accept remotely mounted Control Pad.
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6”
(150 mm)
99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6”
(150 mm)
99-186 Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh
screen
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.
TI-92-NE
0107
DIMENSIONS 155MAX inches (mm)
Model 155MAX
All units conform to CSA and UL standards.
Date: ___________________________________________
Tag: _____________________Qty: ___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency – takes into account all power inputs
Performance (HVI certified)
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 150 (71)
@ 0.2" (50 Pa) 146 (69)
@ 0.3" (75 Pa) 134 (63)
@ 0.4" (100 Pa) 121 (57)
@ 0.5" (125 Pa) 106 (50)
@ 0.6" (150 Pa) 92 (43)
Max. Temperature Recovery 78%
Sensible Effectiveness @ 65 cfm (31 L/s) 32°F (0°C) 76%
*Sensible Efficiency @ 65 cfm (31 L/s) 32°F (0°C) 64%
*Sensible Efficiency @ 68 cfm (32 L/s) -13°F (-25°C) 66%
VAC @ 60HZ 120
WATTS / Low speed. 49
WATTS / High speed 120
Amp rating 1.4
FRESH AIR
FROM OUTSIDE
RECIRCULATING
DEFROST
DAMPER
CORE
STALE AIR
TO OUTSIDE
CONDENSATE DRAINS
FILTERS
33 5/8"
(850mm)
*All Duct Connections 6" (150mm)
STALE AIR
FROM INSIDE
BALANCING DAMPER
*NOTE: Front clearance of 25 inches (635 mm) is recommended for servicing unit.
BLOWERS
MOTOR
FRESH AIR
TO INSIDE
19"
(483)
14 3/4"
(375)
160
5
140
120
4
100
3
80
Air Flow (cfm)
2
60
1
40
20
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Static Pres sur e (in w.g. )
5 - High Speed *4 - Medium High Speed *3 - Medium Speed *2 - Medium Low Speed *1 - Low speed * Manufacturers Dat a
Date: ___________________________________________
Tag: _____________________Qty: ___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
7
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
High effficiency electronic comutated ECM motor for maximum energy sav­ings. Each air stream has one centrifugal blower. 5 speed fan operation driven by one double shaft motor. 120 VAC, 1.0 Amps.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
DEHUMIDISTAT
Adjustable Internal Dehumidistat.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resis­tance. Insulated to prevent exterior condensation. Drain connections 2 ­1/2" (12 mm) OD.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, 20 ON/40 Recirculation mode, Recirculation mode (each mode has 5 speeds). Control pad can be removed from HRV and remotely mounted.
Weight 71 lbs. (32.5 kg) Shipping Weight 73 lbs. (33.5 kg)
OPTIONS 99-104 Digital Electronic Timer - 20/40/60 min.
99-109 Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed to
accept remotely mounted Control Pad.
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6”
(150 mm)
99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6”
(150 mm)
99-186 Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh
screen
99-SILENCER6 6” dia. 16” long
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.
DIMENSIONS 155ECM inches (mm)
Model 155ECM
All units conform to CSA and UL standards.
*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency – takes into account all power inputs
Performance (HVI certified)
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 164 (77) @ 0.2" (50 Pa) 157 (74) @ 0.3" (75 Pa) 147 (69) @ 0.4" (100 Pa) 146 (69) @ 0.5" (125 Pa) 140 (66) @ 0.6" (150 Pa) 138 (65) @ 0.7" (175 Pa) 131 (62) @ 0.8" (200 Pa) 121 (57)
Max. Temperature Recovery 79%
Sensible Effectiveness @ 66 cfm (31 L/s) 32°F (0°C) 72%
*Sensible Efficiency @ 66 cfm (31 L/s) 32°F (0°C) 66%
*Sensible Efficiency @ 66 cfm (31 L/s) -13°F (-25°C) 67%
VAC @ 60HZ 120
WATTS / Low speed. 17
WATTS / High speed 95
Amp rating 1.4
5 - High Speed *4 - Medium High Speed *3 - Medium Speed *2 - Medium Low Speed *1 - Low speed * Manufacturers Dat a
FRESH AIR
FROM OUTSIDE
RECIRCULATING
DEFROST
DAMPER
CORE
STALE AIR
TO OUTSIDE
CONDENSATE DRAINS
FILTERS
33 5/8"
(850mm)
*All Duct Connections 6" (150mm)
STALE AIR
FROM INSIDE
BALANCING DAMPER
*NOTE: Front clearance of 25 inches (635 mm) is recommended for ser vicing unit.
BLOWERS
MOTOR
FRESH AIR
TO INSIDE
19"
(483)
14 3/4"
(375)
190
170
150
130
110
90
Air Flow (cfm)
70
50
30
10
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
1
2
Static Pressure (in w.g.)
4
3
5
ATTENTION
The ECM motor produces a tone that some may find objectionable. We recommend the installation of the optional 99-SILENCER6 on the ‘Stale Air from Inside’ and ‘Fresh Air to Inside’ ducts.
8
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed fan operation. 120 VAC, 1.0 Amps.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
DEHUMIDISTAT
Adjustable Internal Dehumidistat.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resis­tance. Insulated to prevent exterior condensation. Drain connections 2 ­1/2" (12 mm) OD.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, 20 ON/40 Recirculation mode, Recirculation mode (each mode has 5 speeds). Control pad can be removed from HRV and remotely mounted.
Weight 71 lbs. (32.5 kg) Shipping Weight 73 lbs. (33.5 kg)
OPTIONS 99-104 Digital Electronic Timer - 20/40/60 min.
99-109 Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed to
accept remotely mounted Control Pad.
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6”
(150 mm)
99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6”
(150 mm)
99-186 Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh
screen
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.
1105
DIMENSIONS 155MAX RX inches (mm)
Model 155MAX RX
All units conform to CSA and UL standards.
Date: ___________________________________________
Tag: _____________________Qty: ___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency – takes into account all power inputs
Performance
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 150 (71)
@ 0.2" (50 Pa) 146 (69)
@ 0.3" (75 Pa) 134 (63)
@ 0.4" (100 Pa) 121 (57)
@ 0.5" (125 Pa) 106 (50)
@ 0.6" (150 Pa) 92 (43)
Max. Temperature Recovery 78%
Sensible Effectiveness @ 65 cfm (31 L/s) 32°F (0°C) 76%
*Sensible Efficiency @ 65 cfm (31 L/s) 32°F (0°C) 64%
*Sensible Efficiency @ 68 cfm (32 L/s) -13°F (-25°C) 66%
VAC @ 60HZ 120
WATTS / Low speed. 49
WATTS / High speed 120
Amp rating 1.4
STALE AIR
FROM INSIDE
BLOWERS
MOTOR
FRESH AIR
TO INSIDE
BALANCING DAMPER
FILTERS
33 5/8"
(850mm)
*All Duct Connections 6" (150mm)
FRESH AIR
FROM OUTSIDE
RECIRCULATING
DEFROST
DAMPER
CORE
STALE AIR
TO OUTSIDE
CONDENSATE DRAINS
19"
(483)
*NOTE: Front clearance of 25 inches (635 mm) is recommended for servicing unit.
14 3/4"
(375)
160
5
140
120
4
100
3
80
Air Flow (cfm)
2
60
1
40
20
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Static Press ure (in w.g.)
5 - High Speed 4 - Medium High Speed 3 - Medium Speed 2 - Medium Low Speed 1 - Low speed
9
OPTIONS 99-104 Digital Electronic Timer - 20/40/60 min.
99-109 Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed to
accept remotely mounted Control Pad.
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6”
(150mm)
99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6”
(150mm)
99-186 Weatherhoods, Two - 6” (150mm) c/w 1/4” (6mm) mesh
screen
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.
TI-99-NE
0107
Model 200MAX
DIMENSIONS 200MAX inches (mm)
All units conform to CSA and UL standards.
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed fan operation. 120 VAC, 1.4 Amps.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
DEHUMIDISTAT
Adjustable Internal Dehumidistat.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 2
- 1/2" (12 mm) OD.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, 20 ON/40 Recirculation mode, Recirculation mode (each mode has 5 speeds). Control pad can be removed from HRV and remotely mounted.
Weight 71 lbs. (32.5 kg) Shipping Weight 73 lbs. (33.5 kg)
Date: ___________________________________________
Tag: _____________________Qty: ___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency – takes into account all power inputs
Performance (HVI certified)
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 207 (97) @ 0.2" (50 Pa) 200 (94) @ 0.3" (75 Pa) 184 (87) @ 0.4" (100 Pa) 171 (80) @ 0.5" (125 Pa) 152 (71) @ 0.6" (150 Pa) 130 (61) @ 0.7" (175 Pa) 116 (55) @ 0.8" (200 Pa) 86 (40)
Max. Temperature Recovery 74%
Sensible Effectiveness @ 66 cfm (31 L/s) 32°F (0°C) 74%
*Sensible Efficiency @ 66 cfm (31 L/s) 32°F (0°C) 64%
*Sensible Efficiency @ 109 cfm (51 L/s) -13°F (-25°C) 62%
VAC @ 60HZ 120
WATTS / Low speed. 87
WATTS / High speed 164
Amp rating 1.4
5 - High Speed *4 - Medium High Speed *3 - Medium Speed *2 - Medium Low Speed *1 - Low speed * Manufacturers Dat a
FRESH AIR
FROM OUTSIDE
RECIRCULATING
DEFROST
DAMPER
CORE
STALE AIR
TO OUTSIDE
CONDENSATE DRAINS
FILTERS
33 5/8"
(850 mm)
*All Duct Connections 6" (150 mm)
STALE AIR
FROM INSIDE
BLOWERS
MOTOR
FRESH AIR
TO INSIDE
BALANCING DAMPER
19"
(483 mm)
14 3/4"
(375 mm)
*NOTE: Front clearance of 25 inches (635 mm) is recommended for servicing unit.
220
5
200
180
4
160
3
140
120
2
Air Flow (cfm)
100
1
80
60
40
0 0. 1 0.2 0.3 0.4 0. 5 0.6 0.7 0.8 0. 9
Static Pressure (in w.g.)
10
OPTIONS 99-104 Digital Electronic Timer - 20/40/60 min.
99-109 Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed to
accept remotely mounted Control Pad.
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6”
(150mm)
99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6”
(150mm)
99-186 Weatherhoods, Two - 6” (150mm) c/w 1/4” (6mm) mesh
screen
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.
All units conform to CSA and UL standards.
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed fan operation. 120 VAC, 1.4 Amps.
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
DEHUMIDISTAT
Adjustable Internal Dehumidistat.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 2 - 1/2" (12 mm) OD.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, 20 ON/40 Recirculation mode, Recirculation mode (each mode has 5 speeds). Control pad can be removed from HRV and remotely mounted.
Weight 71 lbs. (32.5 kg) Shipping Weight 73 lbs. (33.5 kg)
1105
Model 200MAX RX
DIMENSIONS 200MAX RX inches (mm)
Date: ___________________________________________
Tag: _____________________Qty: ___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency – takes into account all power inputs
Performance
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 207 (97) @ 0.2" (50 Pa) 200 (94) @ 0.3" (75 Pa) 184 (87) @ 0.4" (100 Pa) 171 (80) @ 0.5" (125 Pa) 152 (71) @ 0.6" (150 Pa) 130 (61) @ 0.7" (175 Pa) 116 (55) @ 0.8" (200 Pa) 86 (40)
Max. Temperature Recovery 74%
Sensible Effectiveness @ 66 cfm (31 L/s) 32°F (0°C) 74%
*Sensible Efficiency @ 66 cfm (31 L/s) 32°F (0°C) 64%
*Sensible Efficiency @ 109 cfm (51 L/s) -13°F (-25°C) 62%
VAC @ 60HZ 120
WATTS / Low speed. 87
WATTS / High speed 164
Amp rating 1.4
5 - High Speed 4 - Medium High Speed 3 - Medium Speed 2 - Medium Low Speed 1 - Low speed
STALE AIR
FROM INSIDE
BLOWERS
MOTOR
FRESH AIR
TO INSIDE
BALANCING DAMPER
FILTERS
33 5/8"
(850mm)
*All Duct Connections 6" (150mm)
FRESH AIR
FROM OUTSIDE
RECIRCULATING
DEFROST
DAMPER
CORE
STALE AIR
TO OUTSIDE
CONDENSATE DRAINS
19"
(483)
14 3/4"
(375)
*NOTE: Front clearance of 25 inches (635 mm) is recommended for servicing unit.
220
5
200
180
4
160
3
140
120
2
Air Flow (cfm)
100
1
80
60
40
0 0. 1 0.2 0.3 0.4 0. 5 0.6 0.7 0.8 0. 9
Static Pressure (in w.g.)
11
ENGINEERING DATA
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily removed for cleaning or service.
MOTORS AND BLOWERS
Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed fan operation. 120 VAC, 1.4 Amps.
FILTERS - Washable air filters in exhaust and supply air streams. MOUNTING THE HRV - Four threaded inserts at corners of case designed
to accept four reinforced polyester straps that are supplied with the unit.
DEFROST
Recirculating damper defrost system.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation. Drain connections 2
- 1/2" (12 mm) OD.
CONTROLS
ControlAir 15 - Standby/ON mode, 20 ON/ 40 OFF mode, 20 ON/40 Recirculation mode, Recirculation mode (each mode has 5 speeds). Control pad can be removed from HRV and remotely mounted.
Weight 87 lbs. (39.5 kg) Shipping Weight 89 lbs. (40.5 kg)
(
OPTIONS 99-104 Digital Electronic Timer - 20/40/60 min.
99-109 Air Sentry™ Air Quality Monitor designed to accept
remotely mounted Control Pad
99-250 Ventilation Dehumidistat - Dehumidistat designed to
accept remotely mounted Control Pad
99-163 Duct Heater w/ Electronic SCR Thermostat, 1 Kw, 6”
(150mm)
99-164 Duct Heater w/ Electronic SCR Thermostat, 2 Kw, 6”
(150mm)
99-186 Weatherhoods, Two - 6” (150mm) c/w 1/4” (6mm) mesh
screen
WARRANTY
Units carry a LIFETIME warranty on the heat recovery core and a 5 year replacement parts warranty.
TI-100-NE
0107
Model MAXTOP
All units conform to CSA and UL standards.
DIMENSIONS MAXTOP
inches (mm
)
Date: ___________________________________________
Tag: _____________________Qty: ___________________
Project: _________________________________________
Engineer: _______________________________________
Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________
*Sensible Efficiency – thermal **Latent Efficiency – moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams Efficiency – takes into account all power inputs
Performance (HVI certified)
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 196 (93) @ 0.2" (50 Pa) 188 (89) @ 0.3" (75 Pa) 178 (84) @ 0.4" (100 Pa) 165 (78) @ 0.5" (125 Pa) 149 (70) @ 0.6" (150 Pa) 131 (62) @ 0.7" (175 Pa) 109 (51) @ 0.8" (200 Pa) 79 (37) @ 0.9" (225 Pa) 48 (23)
Max. Temperature Recovery 83%
Sensible Effectiveness @ 65 cfm (31 L/s) 32°F (0°C) 80%
*Sensible Efficiency @ 65 cfm (31 L/s) 32°F (0°C) 69%
*Sensible Efficiency @ 67 cfm (31 L/s) -13°F (-25°C) 70%
VAC @ 60HZ 120
WATTS / Low speed. 74
WATTS / High speed 164
Amp rating 1.4
5 - High Speed *4 - Medium High Speed *3 - Medium Speed *2 - Medium Low Speed *1 - Low speed * Manufacturers Dat a
CONTROLS
25 1/2 "
648 mm)
22 1/2"
(572 mm)
FRONT VIEW
7 1/2"
(191 mm)
18"
(457 mm)
DRAIN CONNECTION
26 1/2"
(673 mm)
SIDE VIEW
ALL DUCT CONNECTIONS ARE 6" (150 mm)
STALE AIR EXHAUST
SUPPLY OF FRESH AIR
TOP VIEW
FRESH AIR SUPPLY TO BUILDING
STALE AIR RETURN FROM BUILDING
*Service Clearance 25" (635 mm)
220
200
5
180
4
160
3
140
2
120
100
Air Flow (c fm)
1
80
60
40
20
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Static Press ure (in w.g.)
Loading...