8.2.1 Checking the inverter and the frequency signal 20
8.2.2 Checking the compressor 21
Page 2/21
Service Information No. 01/2008 IGN 2556/2566
1.0 Operating and control elements
1 Up Setting button temperature higher
2 Down Setting button temperature lower
3 Temperature/function display
4 ON/OFF ON/OFF button
5 SuperFrost SuperFrost function
6 Alarm Alarm OFF button for audible alarm
1
2
3
Freezer compartment
4
5
6
2.0 Functions at a glance
Control:
Temperature display:
Temperature range:
Temperature alarm:
Door alarm:
Fan:
Defrosting:
Interior light:
Service menu:
Compressor:
Solenoid valve
refrigeration circuit:
Electronic
Actual value
-14°C to -28°C
Visual, audible
Audible
Present
Automatic
Present
Present
VCC
Not present
Page 3/21
Service Information No. 01/2008 IGN 2556/2566
r
3.0 Description of appliance
The IGN 2556/2566 is a NoFrost freezer using a series 6 control system with actual value display.
The appliance has a lamellar evaporator with fan and integrated defrost heater. Two sensors, an air sensor and
an evaporator sensor, see to the control and automatic defrosting. A safety temperature limiter protects the
appliance against excessively high temperatures during the defrosting phase.
The IGN 2566 is equipped with an IceMaker.
3.1 Sensor positions, schematic diagrams
Foamed-in rear wall
Fan
evaporato
Evaporator sensor
Air sensor
IGN 2566 only:
IceMaker
Fig. 3.1 / 2Fig. 3.1 / 1
Page 4/21
Service Information No. 01/2008 IGN 2556/2566
4.0 Main components and their functions
4.1 Electrical components and functions
4.1.1 General
Electronic control system
Type:
Components:
Series 6 electronic control system
Electronic single-board solution
4.1.2 Freezer compartment
Electronic control system
Setting range:
Display range:
Functions
Temperature alarm:
-14°C to -28°C
0°C to -49°C
Values outside the range are indicated by a cross bar
Alarm value: 4K warmer than set value.
Warmest alarm value: -10 °C
Coldest alarm value: -20 °C
Delay: 20 minutes
Visual: Flashing alarm LED
Audible: 4 beeps (suppressed during start-up)
Defrosting:
During start-up: The temperature display flashes until the switch-off
value is reached, the audible alarm is switched OFF.
(e.g. given a set value of -18°C, a temperature of –14°C must be present for at
least 20 minutes, then a temperature alarm is raised.)
When the defrosting phase begins, the temperature alarm is suppressed for
1.5hrs.
ON: - During start-up after 6 hours cumulative compressor
running time.
- After a cumulative compressor running time of 10 to 30 hours
maximum, depending on the number/duration of the door
openings.
When the defrosting phase begins, the compressor and the fan are
switched OFF and the defrost heater is switched ON.
Duration: The defrost heater remains switched ON until
- the freezer compartment evaporator sensor has reached +32°C
or
- a max. defrosting time of 50 minutes has been reached.
Info: After the end of the heating phase the compressor is switched ON
with a 15-minute delay. Fan ON, from -25°C.
If the SuperFrost function is activated during the defrosting phase,
this will not interrupt defrosting.
Door alarm:
When: If door is open, after 60 seconds.
Audible: 3 beeps.
Page 5/21
Service Information No. 01/2008 IGN 2556/2566
SuperFrost:
Sensor
Air sensor:
Evaporator sensor:
Switch
Door switch:
ON: Freezer compartment sets itself to -32°C (quantity-controlled, min.
30 hrs., max. 65 hrs.)
The appliance sets itself to -32°C for at least 30 hours. In the
following 35 hours cooling by 11K to the set value must have been
reached or a total time of 65 hours must have elapsed in order that
SuperFrost is automatically ended.
OFF: The freezer compartment sets itself to the set value.
Note: If SuperFrost is actuated during a defrosting phase, the SuperFrost
function is not performed before the defrosting phase has run.
Position: Behind the front panel of the evaporator module.
Function: - Switches the compressor ON/OFF.
- Generates the display value.
Position: Slipped into the lamellar evaporator.
Function: - Switches the defrost heater OFF (ends the defrosting phase).
- Switches the fan ON/OFF.
Position: In front panel
Loads
Fan:
Type: Reed contact
Contact type: Make contact
Function: Activation via:
magnet on the door, magnet is replaceable.
Switching signal when: door open: fan OFF
door alarm ON after 60 seconds
Position: In the evaporator module, at the back centre.
Function:
Evaporator
sensor
Switch-on
value
Switch-on
value
Switch-on
value
Switch-off
value
e.g. If the evaporator sensor has reached the switch-on value for the fan and the
compressor is ON and the door is CLOSED, then the fan is ON.
Compressor Door Fan
OFF CLOSED
ON CLOSED
OFF/ON OPEN
OFF/ON
CLOSED/
OPEN
OFF
ON
OFF
OFF
Switch-on value evaporator sensor:
a) During start-up/after defrosting: -25°C
b) In the normal mode 2K colder than air sensor
Page 6/21
Service Information No. 01/2008 IGN 2556/2566
Defrost heater:
Compressor:
Position: Clipped into lamellar evaporator
Function: Keeps the evaporator free from ice. Activation via electronic control
system.
Defrost heater ON:
- Depending on the number and duration of door openings, the
electronic system calculates the defrost cycles between 10-30
hours cumulative compressor running time.
- Upon start-up after 6 hours cumulative
compressor running time.
Function: ON:Air sensor switch-on value
Note: On-delay time (8 minutes) must have elapsed.
OFF: Air sensor switch-off value.
VCC compressor, frequency-controlled.
• Compressor with 4 different speeds (1600 / 1900 / 3000 / 3600 rpm).
• The inverter electronic control is fitted directly on the compressor. The inverter
electronic control controls the compressor with a pulse-width modulated
square-wave voltage.
•For speed value input, the inverter electronic module receives a square wave
frequency signal from the power PCB.
This frequency signal is output with 56, 71, 87,100 or 117 Hz, depending on
the speed at which the compressor is to run.
Frequency in Hz Speed in rpm Operation
56 Compressor OFF Compressor OFF
71 1600 Ideal case
87 1900 Control mode
100,
0 (signal interruption),
other values than the
defined frequencies
117 3600 SuperFrost
•Runtime longer than 70 minutes:
Speed increase by one step during compressor operation.
•Runtime shorter than 40 minutes:
Speed reduction on next start-up.
3000
Start-up, signal
interruption, signal fault
For troubleshooting, see section 8.2 Troubleshooting VCC compressor / inverter
Page 7/21
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.