Liebert Hiross Himod 65UC, Himod 27UC, Himod 80UC, Himod 85UC, Himod 90UC Service Manual

...
Page 1
Himod
C Version
Service Manual
English
cod. 272631 − rev. 25.02.2005
Page 2
Page 3
Caution
We recommend that:
turer from any liability.
This manual has been prepared to enable the end−user to carry out only the operations that can be made with the panels closed. Any operations that require the opening of doors or equipment panels must be carried out only by qualified personnel. Each machine is equipped with an Electric Insulating device which allows the operator to work in conditions of safety. Switch off the machine before any maintenance operation to eliminate risks remaining (electric shocks, scalds, automatic restarting, mov­ing parts and remote control).
For "UNDER" units installed on raised floor: switch off the machine before removal of the floor panels within a distance of 850 mm from the machine, to avoid risks of contact with rotating devices.
The panel key supplied with the unit must be kept by the person responsible for maintenance. For identification of the unit (model and serial no.) in case of the necessity for assistance or spare parts, locate the identification
label on the outside of the unit.

Index

1 − Preliminary operations 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 − Inspection 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 − Handling 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 − Operating limits 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4 − Identification 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 − Positioning 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 − Clearance areas and main dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 − Overall dimensions 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 − Installation 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 − Air inlet and outlet 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 − Hole in raised floor 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 − Extension hood 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 − Extension hood with sound reduction cartridges (Over unit) 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 − Horizontal discharge hood (Over unit) 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.6 − Base module 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.7 − Base frame 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.8 − High efficiency filters 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.9 − New Air module 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 − Water connections 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 − General warnings 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 − Auxiliary water connections 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 − Chilled water connections 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4 − Adding ethylene glycol 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 − Electrical connections 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 − Electrical connections 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 − Fan connections 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 − Aeraulic features 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 − Start−up 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1 − First start−up (or after long standstill) 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 − Starting and stopping 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3 − Automatic restart 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 − Operation 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1 − Chilled water valve 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
English
Page 4
8 − Calibrations 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9 − Maintenance / Spare Parts 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1 − Spare parts 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2 − Dismantling the unit 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A − HUMIDAIR humidifier A − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.1 − Preface A − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.2 − Installation A − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.3 − Humidair components A − 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.4 − Start−up and operation A − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.4.1 − Start−up A − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.4.2 − Operation A − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.5 − Maintenance A − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.5.1 − Removing the steam cylinder A − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.5.2 − Replacing the steam cylinder A − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.5.3 − Annual maintenance A − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.6 − Spare part list A − 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The Service Manual HIMOD can also be surfed on the Web at the address: www.HIROSS.IT/pde/TDS/Himod
This document is password−protected. Ask for the password to your Dealer/Area Manager.
English
Page 5
1 − Preliminary operations
Room conditions
Hot water heating coil
Chilled water coil
1.1 − Inspection
On receiving the equipment immediately check its condition; report any damage to the transport compa­ny at once.
1.2 − Handling
S Always keep the unit vertically upright and do not
leave it out in the open.
S If possible transport the unit using a fork lift truck;
otherwise use a crane with belts or cables, avoiding pressing on the top edges of the packing.
1.3 − Operating limits
The units are designed to operate within working ranges (see Tab. 1). These limits are referred to new machines or to those that have been correctly installed and serviced. The warranty clauses are no longer valid for any pos­sible damage or malfunction that may occur during or due to operation outside the application values.
1.4 − Identification
The air conditioner can be identified according to the following nomenclature:
27
UC
Model
Air distribution:
U = Under (downflow)
= Over (upflow)O
Cooling circuit:
A = air−cooled
= water−cooledW
= chilled water
C
F = Freecooler
= Dualfluid (air−cooled)D = Dualfluid (water−cooled)
H
Tab. 1 − Operating limits
Room conditions
Voltage tolerances
UNDER OVER
from: 18°C, 45% R.H.
to: 27°C, 55% R.H
standard 400V 10%/3/50
208B230V ± 10%/3/60
optional
380V ± 10%/3/60 460V ± 10%/3/60
To view the Service Manual HIMOD version A/W/F/D/H, refer to the Manual code 272157
Hot water heating coil
Chilled water coil
Storage conditions
inlet water temperature
water pressure max. 8.5 bar inlet water
temperature
water pressure max. 16 bar
from: − 20°C
to: 50°C
max. 85°C
min. 5°C
English
HIMOD−C
1
Page 6
2 − Positioning
2.1 − Clearance areas and main dimensions
MODEL
27−45 O/UC 55−65−80−85 O/UC 90−10 UC 12−14 UC
A [mm] 1000 1750 2050 2550 B [mm] 1740 1740 1740 1740 C [mm] 800 800 800 800 D [mm] 890 890 890 890 E [mm] 50 50 50 50
F [mm] 1950 1950 1950 1950
MODEL WEIGHT (kg) − standard unit
27 UC 290 45 UC 340 55 UC 495 65 UC 555 80 UC 590 85 UC 610 90 UC 660 10 UC 670 12 UC 830 14 UC 840 27 OC 290 45 OC 340 55 OC 495 65 OC 555 80 OC 590 85 OC 610
2
HIMOD−C
English
Page 7
2.2 − Overall dimensions
27−45 UC 55−65−80−85 UC
Under Version
1000
5 990
90−10 UC 12−14 UC
2050
1750
1950
40
5
5
1740
2550
5
50
885
5
1950
40
5
2040
5
5
2540
50
5
885
5
Over Version
27−45 OC 55−65−80−85 OC
1000
1750
1950
English
5 990
40
5
5
1740
HIMOD−C
5
50
890
3
Page 8
3 − Installation
ATTENTION: The conditioner must never be installed out of doors.
3.1 − Air inlet and outlet
27−45 C − under
55−65−80−85 C − under
27−45 C − under
55−65−80−85 C − under
90−10 C − under
12−14 C − under
90−10 C − under
12−14 C − under
A B C D
910 778 40 52
1580 778 80 52
E F G H L
910 804 43 43 45
1660 804 43 43 45
A B C D
1960 297 40 483 2460 297 40 483
E F G H L
1960 799 43 46 45 2460 799 43 46 45
Look−through rear view
ATTENTION: About the upflow (over) units, the extraordinary removal of the fan (560 mm blade diameter) is per­mitted only from the top of the unit. Please keep it on mind during the possible ducting design and manufacturing.
3.2 − Hole in raised floor
27−45 C 55−65−80−85 C
without base frame with base frame without base frame with base frame A [mm] 900 1000 1650 1750 B [mm] 810 885 810 885 C [mm] 93 48 93 48
90−10 UC 12−14 UC
without base frame with base frame without base frame with base frame A [mm] 1970 2050 2470 2550 B [mm] 810 885 810 885 C [mm] 93 48 93 48
CAUTION: For "UNDER" units installed on raised floor, inhibit inappropriate access to the unit from the base to not−authotized staff: i.e. fixing the floor panels up to 850 mm from the unit.
4
HIMOD−C
English
Page 9
3.3 − Extension hood
false ceiling
27−45 C
55−65−80−85 C
90−10 UC
12−14 UC
3.4 − Extension hood with sound reduction car­tridges (Over unit)
A B C D
1000 890 500 / 1200 30 1750 890 500 / 1200 30 2050 890 500 / 1200 30 2550 890 500 / 1200 30
3.5 − Horizontal discharge hood (Over unit)
English
HIMOD−C
front back
A B C
27−45 C
55−65−80−85 C
1000 890 600/900 1750 890 600/900
5
Page 10
3.6 − Base module
If there is no raised floor below the unit it must be placed on a base module to allow access to the external connections. The conditioner is connected to the base module by 4 screws.
3.7 − Base frame
27−45 C
55−65−80−85 C
90−10 UC
12−14 UC
3.8 − High efficiency filters
A B C
990 885 200 1740 885 200 2040 885 200 2540 885 200
6
HIMOD−C
English
Page 11
3.9 − New Air module
UNDER
(C version)
UNDER
(Mod. 90−10 − C version)
OVER
(C version)
UNDER
(Mod. 12−14 − C version)
English
HIMOD−C
7
Page 12
4 − Water connections
4.1 − General warnings
ENSURE THAT THE TUBING DOES NOT OB­STRUCT THE AIR FLOW(Under only).
IF THE TUBING IS TO RUN OUTDOORS, ADD ETHYLENE GLYCOL TO THE CIRCUIT AS DE­SCRIBED IN PARA. 4.4.
4.2 − Auxiliary water connections
− Condensate drain (Fig. 1):
S Use galvanized steel, PVC or flexible polythene
tubing.
S Allow a 2% gradient towards the drain outlet. S There must be a drain trap (1) placed at least 30
mm below the drain tray (2).
S Fill the drain trap with water (3).
Fig. 1 − Condensate drain
2
1
3
min. 30 mm
S Place shut−off ball valves (3) at the conditioner in-
let and outlet to allow easy maintenance.
S It is useful to install a thermometer (4) and a ma-
nometer (5) at the conditioner inlet and outlet.
S Install a water drain tap (6) at the lowest point in
the circuit.
S Place a control valve (7) in the outlet water tubing. S Fill the circuit with water/glycol (see below), up to
a maximum pressure of 7 bar.
Fig. 2 − Chilled water circuit
Air
conditioner
2
1 6
4 5
7 3
BRACKET
to be connected
by user
− Humidifier (optional): See App. A.
− Hot water (optional):
S Use copper or steel (Mannesmann) tubing. S Insulate both tubes using Armaflex insulation.
4.3 − Chilled water connections
S Use copper or steel (Mannesmann) tubing. S Place the tubing on supporting saddles (1). S Insulate both tubes using Armaflex insulation (2).
4.4 − Adding ethylene glycol
Tab. 2 − Ethylene glycol to be added to water
freezing temperature (_C)
ethylene glycol to add to water (% in weight of total mixture)
N.B. Values are for Shell antifreeze 402. For different brands check manufacturer’s data.
0 −5 −11 −18 −27 −39
0 10 20 30 40 50
NOTES:
S To avoid stratification run the circulation pump for
at least 30 min. after adding any glycol.
S After adding water to the water circuit, disconnect
the unit from the sanitary water piping system; in
this way the water mixed with glycol won’t return into the same piping system.
S After any topping−up of water check the glycol
concentration and add any glycol if necessary.
S The hydraulic features of the system vary by adding
glycol. Therefore check the head and the flow rate of the pump to be used.
8
HIMOD−C
English
Page 13
Fig. 3 − Chilled water connections
POS
CONNECTION
Himod C under
27−45
140
125
A
B
Right side view (DX)
120
150
Frontal view
BA
55−65−80−85
140
125
A
B
Right side view (DX)
120
150
BA
Frontal view
DIMENSION
.
27C 45−55C 65−80−85C
A Chilled water inlet 1 " female 1 ¼" female 1 ½" female
B Chilled water outlet 1 " female 1 ¼" female 1 ½" female
English
HIMOD−C
9
Page 14
Fig. 4 − Chilled water connections
POS
CONNECTION
200
Himod C under
90 − 10
95
A
B
Right side view (DX)
100
180
BA
Frontal view
12−14
200
95
A
B
Right side view (DX)
110
185
BA
Frontal view
DIMENSION
.
90−10 C 12−14 C
A Chilled water inlet 2 " male 2 ½" male
B Chilled water outlet 2 " male 2 ½" male
10
HIMOD−C
English
Page 15
Fig. 5 − Chilled water connections
POS
CONNECTION
27−45
160 / 200
Himod C over
220
BA
55−65−80−85
150
Frontal view
300
Left side view (SX)
A
B
90 (80−85 C)
170 (55−65 C)
220
150
BA
Frontal view
300
A
B
Left side view (SX)
DIMENSION
.
27C 45−55C 65−80−85C
A Chilled water inlet 1 " female 1 ¼" female 1 ½" female
B Chilled water outlet 1 " female 1 ¼" female 1 ½" female
English
HIMOD−C
11
Page 16
Fig. 6 − Auxiliary water connections
Under single / double
Himod C under/over
Frontal view
155
D
E
27−45−55−65
A
B
C
27−45
Over single / double
27−45 55−65−80−85
Left side view
80
145
E
D
80−85
A
B
C
(SX)
E
D
27−45−55−65 80−85
55−65−80−85
105
215
90
D
E
27−45
55−65−80−85
Frontal view
POS.
105
D A
E
170
B
C
CONNECTION DIMENSION
A HUMIDAIR water supply (optional) ½" G male B HUMIDAIR water drain (optional)
C Condensate drain
D/E (small) Hot water inlet/outlet (optional)
D/E (big) Hot water inlet/outlet (optional)
12
Frontal view
D
E
HIMOD−C
105
170
Left side view (SX)
D A
E
22 mm female
20 mm female
18 x 1 mm
22 x 1 mm
590
B
C
English
Page 17
Fig. 7 − Auxiliary water connections
90−10
135105
Himod C under
Frontal view
12−14
90 490 85
B
A
E
Left side view (SX)
C
D
135105
67
D
E
B
A
C
English
POS.
Frontal view
90 480 85
B
A
E
C
D
CONNECTION DIMENSION
Left side view (SX)
A HUMIDAIR water supply (optional) ½" G male B HUMIDAIR water drain (optional)
C Condensate drain
D/E Hot water inlet/outlet (optional)
22 mm female
20 mm female
22 x 1 mm
HIMOD−C
67
D
E
B
A
C
13
Page 18
Fig. 8 − Water circuit
Himod C 27−55−65
5
3
1
2
4
COOLING WATER INLET
COOLING WATER OUTLET
HOT WATER OUTLET
HOT WATER INLET
POS. DESCRIPTION
1 Chilled water coil
2 Reheating coil (optional)
3 ON−OFF 3−way valve (optional)
4 Chilled water 3−way valve
5 Air purge valve
14
HIMOD−C
English
Page 19
Fig. 9 − Water circuit
Himod C 45−80−85−90−10−12−14
1
5
3
1
2
4
COOLING WATER INLET
COOLING WATER OUTLET
HOT WATER OUTLET
HOT WATER INLET
POS. DESCRIPTION
1 Chilled water coil
2 Reheating coil (optional)
3 ON−OFF 3−way valve (optional)
4 Chilled water 3−way valve
5 Air purge valve
English
HIMOD−C
15
Page 20
5 − Electrical connections
5.1 − Electrical connections
1) Before proceeding with the electrical connections, ensure that:
S all electrical components are undamaged; S all terminal screws are tight; S the supply voltage and frequency are as indicated
on the unit.
2) Power supply cable connections (see Fig. 10): S Connect the cable to the Line inlet terminal
board.
S Use the cable size defined according to the flow
(see Fig. 11), the supply voltage and the installa­tion type.
S Protect the supply using a back−up fuse.
Fig. 10 − Supply cable passage
3) Wiring connections:
4) In case of short circuit, check the sticking of the in-
S Do not fit the supply cable in the raceways inside
the machine electric board.
S Use multipolar cables with sheath (CEI20−22)
only.
S Connections for remote on−off and hot water
consent must be done by the installer.
S The General Alarm terminals allow remote
alarm signalling.
volved remote control switch and possibly replace it.
Under unit (Mod. 90−10 C version)
Under unit Over unit
Under unit (Mod. 12−14 C version)
16
HIMOD−C
English
Page 21
Fig. 11 − Electrical connections
(F): Cooling
()
(F+C): Cooling + Electrical heating
() g
an(s)
heating,
humidification
Fan(s) + heating, + humidification
AUXILIARY TERMINAL BOARD
clogged
filter (CF)
remote on−off
user alarm
(or AAP)
G0
24 24 191111 50 020 3002 24 055G0GGG0 5533 102
smokestat
firestat (AAP)
water
leakage
(LWD)
fans
operating
70
NO*
C*NC*
72 73 400 401 40271
GENERAL ALARM
401 − 402: alarm signal 401 − 400: alarm off
* unit under power
Tab. 3 − Electrical data
CONFIGURATION MODELS
(F): Cooling
Fan(s)
(F+C): Cooling + Electrical heating
F
Fan(s) + heating
(F+C+H): Cooling + Electrical
heating + Humidity
+
+
27 – 45 C
55 – 65 – 80 – 85 C
90 − 10 U C
12 − 14 U C
27 – 45 C
55 – 65 – 80 – 85 C
90 − 10 U C
12 − 14 U C
27 – 45 C
55 – 65 – 80 – 85 C
90 − 10 U C
12 − 14 U C
Supply cable inlet
50 Hz
FLA
(A)
LRA
(A)
3ph / 400V
4,8 16,0 10A
9,7 32,0 16A
17,3 35,6 16A
17,3 53,4 25A
13,3 16,0 16A
26,7 32,0 32A
34,3 35,6 50A
34,3 53,4 50A
22,3 16,0 32A
35,7 32,0 50A
47,3 35,6 63A
47,3 53,4 63A
RESIDUAL−CURRENT CIRCUIT BREAKERS
Inn = 0.3A (400V)
English
HIMOD−C
17
Page 22
60 Hz
(F): Cooling
(F+C): Cooling + Electrical heating
(F): Cooling
(F+C): Cooling + Electrical heating
(F): Cooling
(F+C): Cooling + Electrical heating
CONFIGURATION MODELS
(F): Cooling
Fan(s)
(F+C): Cooling + Electrical heating
Fan(s) + heating
(F+C+H): Cooling + Electrical
heating + Humidity
Fan(s) + heating + humidification
(F): Cooling
Fan(s)
(F+C): Cooling + Electrical heating
Fan(s) + heating
(F+C+H): Cooling + Electrical
heating + Humidity
Fan(s) + heating + humidification
(F): Cooling
Fan(s)
(F+C): Cooling + Electrical heating
Fan(s) + heating
(F+C+H): Cooling + Electrical
heating +Humidity
Fan(s) + heating + humidification
3ph / 208−230V
27 – 45 C
55 – 65 – 80 – 85 C
27 – 45 C
55 – 65 – 80 – 85 C
27 – 45 C
55 – 65 – 80 – 85 C
27 – 45 C
55 – 65 – 80 – 85 C
27 – 45 C
55 – 65 – 80 – 85 C
27 – 45 C
55 – 65 – 80 – 85 C
27 – 45 C
55 – 65 – 80 – 85 C
27 – 45 C
55 – 65 – 80 – 85 C
27 – 45 C
55 – 65 – 80 – 85 C
FLA
(A)
8,9 35,4 16A
17,8 70,8 25A
24,3 35,4 32A
48,6 70,8 50A
33,3 33,3 63A
57,6 57,6 80A
LRA
RESIDUAL−CURRENT CIRCUIT BREAKERS
(A)
3ph / 380V
4,9 20,4 10A
9,7 40,8 16A
13,8 20,4 16A
27,5 40,8 32A
22,8 22,8 40A
36,5 36,5 50A
3ph / 460V
4,0 16,0 10A
8,0 32,0 10A
11,4 16,0 16A
22,7 32,0 25A
20,4 20,4 32A
31,7 31,7 40A
Inn = 0.3A (400V)
NOTES:
S The cables have to be sized in compliance with local standards and according to the type and characteristics (e.g. Amperes) of installation. S The specific power the user−installed switch allows must be lower than 300,000 A2 x s. S Prescriptions on the differential relay required to the user:
S for special places (healthcare facilities, etc...) comply with the local regulations; S For ordinary places, a low sensitivity is suggested (300 mA) coordinated with the value of the ground heater (IEC 364): Ra v 50/Ia (Art.
413.1.4.1, CEI 64−8);
S In case of frequent over−voltages with mains impulse, it is advisable to install a selective differential and to evaluate the need for adopting
other devices.
S (Models 90−10−12−14 U C only) The value of current (Full Load Ampere) is calculated considering electric heaters running at a capacity
of 17,55 kW, configuration F+C and F+C+H.
18
HIMOD−C
English
Page 23
5.2 − Fan connections
The fan is electrically feeded by an autotransformer that is connected by the constructor in order to obtain the nominal air flow and the Available External Static Pressure (AESP). To change the factory connection proceed as follow:
− identify the unit’s graph;
− check the factory fan blocks connection ( or ) and correct if necessary (see Fig. 12);
− find the output connectors and the bridges corre­sponding to the graph values (see para. 5.3;
− connect the bridges and the output connectors;
− connect the 400V supply cables to the C" termi­nals.
− choose the curve’s point where both the air flow and the static pressure are the most suitable for the installation;
After a wiring modification, execute a loadless test on the autotransformer. Check the voltage of each wire, in order not to damage the transformer (always
refer to the output voltage column va-
lues).
N.B. A FAN SPEED VARIATION CHANGES THE WOR-
KING CONDITION OF THE UNIT.
Fig. 12 − Example of electrical connection to the autotransformer
AUTOTRANSFORMER
In the example picture, the power supply voltage required is 260 V, at 50 Hz.. The fan blocks are connected.
FAN MOTOR
Reference colors:
u1 : brown v1 : light blue w1 : black u2 : red v2 : grey w2 : orange klixon: white PE : yellow/green
E
E
E
260V
autotransformer
output
English
HIMOD−C
19
Page 24
Tab. 4 − Autotransformer output connections
50 Hz
autotrasformer outlet voltage
(1)
185 E A H 185
200 E A G 200
215 E A F 215
230 A 230
245 F A E 245
260 G A E 260
275 H A E 275 160 (156)
280 E B G 280 160 (162)
295 E B F 295 170 (167)
310 B 310 180 (179)
325 F B E 325 180 (185)
340 G B E 340 200 (196)
355 H B E 355 200 (202)
370 E C G 370 210 (214)
385 E C F 385 220 (219)
400 C 400 230 (231)
output
connectors
output STD graph value
bridge  fan connection fan connection
60 Hz
autotrasformer outlet voltage
(1) connection: fan inlet voltage = autotrasformer outlet voltage
(1)
190 E B G 190
208 A 208
210 E B F 210
230 B 230
250 F B E 250
270 G B E 270 160 (156)
290 H B E 290 170 (167)
320 E C H 320 180 (179)
340 E C G 340 200 (196)
360 E C F 360 210 (214)
380 C 380 220 (219)
400 F C E 400 230 (231)
420 G C E 420
440 H C E 440
460 D 460
connection: fan inlet voltage = autotrasformer outlet voltage multiplied by 0.577
output
connectors
output STD graph value
bridge fan connection fan connection
20
HIMOD−C
English
Page 25
Tab. 5 − Standard fan connections for HIMOD with autotransformer
50 Hz
Standard
Model
25/27U C 215
35/45U C 215
50/55U C 230
60/65U C 230
70/80U C 230
75/85U C 230
90U C 260
10U C 280
12U C 260
14U C 325
autotrasformer outlet voltage
(1)
connections output connectors bridge
E A F
E A F
A
A
A
A
G A E
E B G
G A E
F B E
25/27O C 230
35/45O C 230
50/55O C 230
60/65O C 230
70/80O C 230
75/85O C 230
Model
27U C 250
45U C 250
55U C 260
65U C 260
80U C 280
85U C 280
27O C 270
45O C 270
55O C 260
65O C 260
80O C 280
85O C 280
autotrasformer outlet voltage
(1)
A
A
A
A
A
A
60 Hz
Standard
connections output connectors bridge
F B E
F B E
G A E
G A E
E B G
E B G
G B E
G B E
G A E
G A E
E B G
E B G
(1) connection: fan inlet voltage = autotrasformer outlet voltage
connection: fan inlet voltage = autotrasformer outlet voltage multiplied by 0.577
English
HIMOD−C
21
Page 26
Tab. 6 − Electrical data
component
Model
27U C 4.3 4.4 16 1.4
45U C 4.3 4.4 16 1.4
55U C 2 x 4.3 2 x 4.4 2 x 16 2 x 1.5
65U C 2 x 4.3 2 x 4.4 2 x 16 2 x 1.5
80U C 2 x 4.3 2 x 4.4 2 x 16 2 x 1.5
85U C 2 x 4.3 2 x 4.4 2 x 16 2 x 1.5
90U C 2 x 5.8 2 x 6.0 2 x 17.8 2 x 2.4
10U C 2 x 5.9 2 x 6.0 2 x 17.8 2 x 2.6
12U C 3 x 5.9 3 x 6.0 3 x 17.8 3 x 2.5
14U C 3 x 5.9 3 x 6.0 3 x 17.8 3 x 3.1
27O C 4.3 4.4 16 1.5
45O C 4.3 4.4 16 1.5
55O C 2 x 4.3 2 x 4.4 2 x 16 2 x 1.5
65O C 2 x 4.3 2 x 4.4 2 x 16 2 x 1.5
80O C 2 x 4.4 2 x 4.4 2 x 16 2 x 1.6
85O C 2 x 4.4 2 x 4.4 2 x 16 2 x 1.6
OA (A)
50 Hz
(3ph − 160  400V)
FLA
(A)
FAN
LRA
(A)
absorbed power
(kW)
60 Hz
component
Model
OA (A)
FLA
(A)
27U C 3.4 3.5 16 1.1
45U C 3.4 3.5 16 1.2
55U C 2 x 3.3 2 x 3.5 2 x 16 2 x 1.2
65U C 2 x 3.4 2 x 3.5 2 x 16 2 x 1.2
80U C 2 x 3.2 2 x 3.5 2 x 16 2 x 1.2
85U C 2 x 3.3 2 x 3.5 2 x 16 2 x 1.2
27O C 3.3 3.5 16 1.2
45O C 3.3 3.5 16 1.2
55O C 2 x 3.3 2 x 3.5 2 x 16 2 x 1.2
65O C 2 x 3.3 2 x 3.5 2 x 16 2 x 1.2
80O C 2 x 3.3 2 x 3.5 2 x 16 2 x 1.3
85O C 2 x 3.3 2 x 3.5 2 x 16 2 x 1.3
1. The fan OA" value and the absorbed power are refered to standard air flow; Under unit with underflow air discharge and 20 Pa available exter­nal static pressure; Over unit with ducted air discharge and 50 Pa available external static pressure.
NOTE: the indicated fan currents are measured on their terminal boards; to calculate the current absorption of the fans to the machine supply
terminals multiply the indicated values by the selected transforming ratio (see Tab. 4).
FAN
(3ph − 160  460V)
LRA
(A)
absorbed power
(kW)
22
HIMOD−C
English
Page 27
Tab. 7 − Optional electrical data
9.0
5.8
C
13.0
9.0
15.0
5.8
9.0
5.8
8.0
5.8
Component ELECTRICAL HEATING HUMIDIFIER
Model FLA (A) rated power [kW] FLA (A) rated power [kW]
(400V / 3Ph / 50Hz)
27−45 U/O C 8.5 5.85
55−65−80−85 U/O C 17.0 11.70
90−10−12−14 U
Component ELECTRICAL HEATING HUMIDIFIER
Model FLA (A) rated power [kW] FLA (A) rated power [kW]
17.0 11.70
25.4 17.55
(208−230V / 3Ph / 60Hz)
27−45 U/O C 15.4 5.85
55−65−80−85 U/O C 30.8 11.70
50 Hz
60 Hz
(380V / 3Ph / 60Hz)
27−45 U/O C 8.9 5.85
55−65−80−85 U/O C 17.8 11.70
(460V / 3Ph / 60Hz)
27−45 U/O C 7.4 5.85
55−65−80−85 U/O C 14.7 11.70
5.3 − Aeraulic features
The aeraulic features, namely the values of the useful static pressure while the voltage changes (graphs), can be surfed on the Web at the following address:
www.HIROSS.IT/pde/TDS/Aeraulic_features
This document is password−protected. Ask for the password to your Dealer/Area Manager.
English
HIMOD−C
23
Page 28
6 − Start−up
6.1 − First start−up (or after long stand-
still)
Start the air conditioner as follows:
1) Open all valves in the water circuit according to the instruction label attached to the valve.
2) Check that there are no water leakages.
3) Bleed all air out of the chilled water circuit using the bleed valve on the chilled water coil.
4) Close all MCBs on the electrical panel.
5) Check the supply voltage on all phases.
6) Start the unit by pressing ON OFF (see Fig. 13).
7) Check the electrical absorption of all components (see Chap. 5).
8) Ensure that the fans rotate in the correct direction (see arrow on fan). CAUTION: risk of contact with rotating devices.
9) Ensure that all control system settings are correct and that there are no alarms (see Control manual).
10)Verify the water flow.
11)Verify the Fresh Air Intake operation (if fitted).
12)Once the system is operating under load, check the various components, as follows:
S Verify that the fans are operating properly. S Ensure that the temperature and relative hu-
midity are being controlled, and that the humid­ifier (optional) and heating steps (optional) op­erate when required.
S Ensure that chilled water valve operates when
required.
6.2 − Starting and stopping
Turn on the unit operating on the ON/OFF switch pla­ced on the left case of the unit (Fig. 13). If the ON/OFF remote device is not installed, the green LED on the Microface case will light up together with the LED pla­ced below the ON/OFF switch. The fan starts imme­diately (the fan always works when the unit is ON); af­ter 2 minutes the regulation is activated, so the cooling (compressor), heating (electric heaters), humidifying and dehumidifying devices can start.
Adjust the set−point as indicated in Control ma-
nual.
Stop the unit putting the ON/OFF switch in OFF.
S The main switch QS should only be switched off if
the unit is stopped for a long period of time.
6.3 − Automatic restart
If desired, the unit will automatically restart on the re­turn of power after a supply interruption (see Control manual).
Fig. 13 − On−Off switch
7 − Operation
Unit operation is completely automatic. The below se­quence explains how the unit operates :
S The air, sucked in by the fan(s), enters the unit. S The air is immediately filtered. S The TEMPERATURE sensor or HUMITEMP (tem-
perature + rel. humidity) sensor (check type installed), verifies the state of the inlet air, and relays this information to the control system.
S The control system compares the relayed informa-
tion to the set point and proportional band values programmed into its memory: it then commands the air conditioner to treat the air as follows (see also Control manual):
S COOLING
Chilled water flows through the chilled water coil, thus cooling the air passing over it. The chilled water flow is controlled by a timed mod­ulating (3−way) valve, which regulates the flow rate in order to obtain the exact amount of cool­ing required.
S HEATING
This can take one of two forms:
− electrical heating (optional): the heating ele­ments heat the air passing over them. There are 3 heating steps.
− hot water heating (optional): if hot water is available, this flows through the hot water coil, thus heating the air passing over it. The hot wa­ter flow is controlled by an on−off (3−way) valve.
S DEHUMIDIFICATION − optional
Maximum chilled water flow is requested through the coil, whose temperature drops be­low the dew point of the air, thus dehumidifying it. If necessary, heating is used to reheat the air.
N.B.: If, during dehumidification, the ambient temperature drops below a specified level, de­humidification will be stopped if necessary (see LOW LIMIT intervention in Control manual).
S HUMIDIFICATION − optional
The humidifier creates steam, which is distrib­uted into the air stream via the steam distribu­tion pipe (see also App. A).
24
HIMOD−C
English
Page 29
S Filtered new air is injected into the air stream via
the Fresh Air Intake.
S The treated air passes through the fans, which op-
erate continuously, and is then dispersed out of the unit.
S Under unit only: the air passes from the underfloor
void into the room via air distribution outlets.
For "UNDER" units installed on raised floor: switch off the machine before removal of the floor panels within a distance of 850 mm from the ma­chine, to avoid risks of contact with rotating devices (see Fig. 15).
N.B.: Manual control can be performed using the control
system (see Control manual).
Fig. 14 − Position of the chilled water valve actuator
3 mm
Manual adjust-
A B
ment with 3 mm al­len key
7.1 − Chilled water valve
The 3−way valve controls the chilled water flow. It op­erates as follows (Fig. 14):
S When the valve is fully open (i.e. max. chilled water
flow) the actuator slot is set to ’1’.
S When the valve is closed (i.e. no chilled water flow)
the actuator slot is set to ’0’.
The valve running time is set to the value specified in the Control Manual.
Note 1: In the unlikely event of control system failure, the valve can be manually controlled by means of a 3 mm allen key placed into the actuator slot. NEVER PERFORM THIS OPERATION USING A SCREWDRIVER.
Note 2: For models 90−10−12−14 UC the chilled wa­ter valve is not foreseen for the manual operation. When actuator stem is completely down the valve is closed (by−pass 100%), when actuator stem is com­pletely up the valve is open (by−pass 0%) and all water flows into the coil.
B
3 m m
3 mm
A
Position indicator in
Position 0 = CLOSED
Valve Closed
(by−pass open)
Position indicator in
Position 1 = OPEN
Valve fully Open
(by−pass closed)
Fig. 15 − Floor panels removal on a safety way
850 mm
English
HIMOD−C
25
Page 30
8 − Calibrations
S The air conditioner has already been factory−te-
sted and calibrated as shown below.
COMPONENT SETTING NOTES
Fan differential pressure switch
Clogged filter
differential pressure switch
(CF)
0.8 mbar
Filters G4 = 2 mbar
9 − Maintenance / Spare Parts
AS THE HIROMATIC/MICROFACE FEATURES AUTOMATIC RESTART (AFTER A SUPPLY IN­TERRUPTION) IT IS ADVISED TO EITHER DI­SABILITATE AUTORESTART OR TO OPEN SWITCH QS WHEN PERFORMING ANY MAIN­TENANCE.
Maintenance schedule − Monthly check
Check that the fan motor rotates freely without any abnormal noise, and en-
FANS
AIR FILTERS
NEW AIR FILTER
(if fitted)
CONTROL SYSTEM Verify the operation of LEDs, display and alarms.
HUMIDIFIER
(if fitted)
ELECTRICAL
CIRCUIT
CHILLED WATER
CIRCUIT
sure that the bearings are not running hot. Also check the current absorption.
Verify the state of the filters; if necessary clean or replace them. In very dusty ambients perform this check more frequently.
Verify the state of the filter; if necessary clean or replace it.
See App. A.
S Check the electrical supply on all phases. S Ensure that all electrical connections are tight. S Ensure that there are no water leaks. S Bleed any air out of the chilled water circuit using the bleed valve situa-
ted on the top right of the chilled water coil.
S Verify the correct chilled water flow. S Check the inlet − outlet fluid temperature and pressure using the ther-
mometers and manometers, if fitted.
S On a daily basis check the HIROMATIC/MICRO-
FACE readings for temperature and, if shown, rel. humidity.
S The Maintenance Programme below should be car-
ried out by a qualified technician, preferably wor­king under a maintenance contract.
calibrate
9.1 − Spare parts
It is recommended the use of original spare parts. When placing an order refer to Component List" en­closed with the machine and quote the unit model no. and serial no.
9.2 − Dismantling the unit
The machine has been designed and built to ensure continuous operation.
26
The working life of some of the main components, such as the fan and the compressor, depends on the maintenance that they receive. If the unit has to be dismantled, this operation must be done by skilled refrigeration technicians.
HIMOD−C
English
Page 31
App. A − HUMIDAIR humidifier
App. A.1 − Preface
The HUMIDAIR represents the best humidifier technology available, guaranteeing the steam as clean as possible together with simple maintenance.
Tab. 8 − Humidair specifications
steam
HUMIDAIR KIT
model code kg/h (*) V/ph/Hz (l) (l/min.) (l/min.)
HAK 93H
HAK 93L
For humidifier current (FLA) and rated power refer to electrical features in air conditioner manual.
(*) Unit is factory−set to produce 70% of the maximum value (see Microface manual).
141103 2.7 − 9.0
141104 2.7 − 9.0
production
(variable)
humidifier
power supply
voltage
380 460 V
trifase
50−60 Hz
208 230 V
trifase
50−60 Hz
App. A.2 − Installation
The humidifier is supplied already mounted within the air conditioner. The only necessary operations are the connections for the supply water (Fig. 1) and drain wa-
In order to obtain optimum performance from the HUMIDAIR it is advisable to read this manual care­fully.
max. cylinder water volume
5.34 0.6 2.5
5.34 0.6 2.5
max. supply
water quantity
ter (Fig. 2); for the positions of the supply/drain con­nections within the unit see Fig. 6 and Fig.7.
max. drain
water quantity
Fig. 1 − Supply water connection
SUPPLY WATER FEATURES
S The supply water temperature must never exceed 40_C.
S The supply water pressure must be between 0.3 and 6 bar.
If greater, use a pressure reducing valve set to 3−4 bar.
S Sanitary water should be used. Do not use demineralized
water or water containing impurities.
S Conductivity range : 1251250 mS/cm.
water
supply
CUT−OFF TAP
Must be included in the supply water tubing.
supplying limit
SUPPLY WATER TUBING
S It is supplied a 1−m−long plastic
tube, diameter 6 x 1mm with ½" G m connections.
B
A
ALTERNATIVE SUPPLY WATER TUBING
Unscrew the ring nut A and connect a tube straight to the 3/4"G Male connection B on the humidifier.
English
A − 1
Page 32
Fig. 2 − Drain water connection
DRAIN WATER DEVICE
Dispose the drain water into an ordinary drainage network, using a funnel (the drainage network must be able to with­stand water temperatures up to 100 _C).
NOTES:
1) Allow a 2% gradient towards the drain outlet.
2) Avoid back pressures in the drain piping.
WATER DRAIN TUBING
It is supplied a hose with an integral
drain trap.
K
L
DO NOT DISMANTLE THE
DRAIN TRAP.
S DO NOT DISMANTLE THE
DRAIN TRAP.
S The hose is already fitted onto
the humidifier drain outlet (K).
S Fill the drain trap with water
(L).
S The drain pipe is made of plastic
material which does not con­duct electricity.
App. A.3 − Humidair components
The components of the HUMIDAIR humidifiers are shown below.
Fig. 3 − The humidifier and its connections
DRAIN VALVE ASSEMBLY (D)
A
filling cup
H
SUPPLY VALVE (F)
F
O
overflow tube
from humidifier power electrodes
steam outlet
Y
Z
U
P
to electrical supply
from level sensor to interface
L
S
level electrode
R
S
S
power electrodes
C
S
steam cylinder
A − 2
water
supply
supply valve
drain valve
G
F
V V
S
S
N
drain tank
D
S
T
E
water drain outlet
from supply valve to interface
from supply valve to interface
English
Page 33
App. A.4 − Start−up and operation
App. A.4.1 − Start−up
Before using the humidifier, check the following:
S Supply and drain connections. S That the cut−off tap is open. S All wiring. S Earthing. S Steam hose connection between steam cylinder
and distributor.
To start the humidifier simply switch on the air condi­tioner, which will in turn automatically start and stop the humidifier as required. The (adjustable) parame­ters which determine humidifier operation have al­ready been factory−preset (see HIROMATIC manu­al).
App. A.4.2 − Operation
Water, provided it contains even a small quantity of salts in solution, is a conductor of electricity. There­fore, if the steam cylinder is filled with water and a po­tential difference is applied between the production electrodes, the water behaves like an ordinary electri­cal resistance and becomes hot, thus creating steam. The steam production rate can be controlled by vary­ing the water level in the cylinder; the higher the water level, the deeper the electrodes are immersed into it and the greater the steam production.
Note 1
In case of low water conductivity the cylinder 93H (9.0 kg/h) or 53H (4.5kg/h) can be substituted with the cy­linder 93L or 53L without changing the power supply. Please remember to set the right cylinder type into the Control system. The steam production will remain unchanged.
Note 2
When starting with an empty cylinder, the water con­ductivity is normally insufficient for the HUMIDI­FIER STEAM OUTPUT to be reached immediately. Therefore the humidifier produces as much steam as possible to fill the cylinder completely. Any evapora­tion water is immediately refilled. The drain valve is kept shut and therefore, as the steam does not contain any salts, the conductivity of the wa­ter within the cylinder slowly increases until the HU­MIDIFIER STEAM OUTPUT is obtained. The length of the start−up period depends upon the water conductivity. For very conductive water it may occur that the HUMIDIFIER STEAM OUTPUT is obtained immediately.
App. A.5 − Maintenance
App. A.5.1 − Removing the steam cylinder
To remove the steam cylinder, proceed as follows (see Fig. 3):
1) Open the General Switch relative to the humidifi­er.
2) Drain all the water from the cylinder by activating "HUM. DRAIN" in the HIROMATIC Service menu several times (see Microface manual).
3) Disconnect the steam hose (S) (made of non−con­ductive rubber).
4) Disconnect the power electrode wires (P) and level sensor wire (L).
5) Undo the clip (R).
6) Pull the cylinder (C) out of its gland at the bottom (G).
App. A.5.2 − Replacing the steam cylinder
When the steam cylinder is approaching the stage where it needs to be replaced, warning A25 is gener­ated (see HIROMATIC manual) to advise the user that the cylinder must be replaced. To replace the cyl­inder, proceed as follows (see Fig. 3):
1) Carry out the instructions in para. Removing the steam cylinder.
2) Using the new cylinder, carry out 4)−6) of para. 5.1 in reverse order.
3) Connect the steam hose (S); the clip on the hose needs to be tightened only slightly.
4) Manually switch the humidifier on for 2−3 minutes (in the HIROMATIC Service menu). Then switch it off.
5) Drain the water as for 2) in para. Removing the steam cylinder.
6) If the air conditioner features a HIROMATIC with Graphic display, reset the humidifier working hours (window no. 1 of PARAMETE R ME NU) to zero.
7) Close the General Switch relative to the humidifier.
App. A.5.3 − Annual maintenance
Annually (e.g. before any close−down period) carry out the following service on the humidifier (see Fig. 3):
1) Carry out the instructions in para. Removing the steam cylinder.
2) Disconnect the supply (F) and drain (D) valve wires.
3) Unscrew and remove the drain tank (T).
4) Unscrew the drain valve assembly screws (V).
5) Remove the drain valve assembly.
6) Unscrew and remove the drain valve solenoid (O).
7) Unscrew and remove the drain valve armature (A).
8) Clean all parts of the drain valve using a commer­cially available descaling agent (to remove any in­crustations).
9) Detach the hose from the supply valve.
10)Remove the supply valve connection (N).
11)Unscrew the supply valve (F) and remove it.
12)Clean the supply valve using a jet of water.
13)Replace any hose which has become hard and brittle.
14)Thoroughly flush the drain line (E).
15)Reassemble the humidifier by carrying out the above instructions in reverse order.
ATTENTION
Always empty the cylinder completely before any clo­se−down period.
English
A − 3
Page 34
App. A.6 − Spare part list
POSITION
CO
NJ
C
NJ
NJ
NJ
It is recommended the use of original spare parts. When placing an order quote the part code, as well as the air conditioner model no. and serial no.
POSITION
(see Fig. 3)
C
T 141200 Drain tank 1 1 1 1 1
U 141201 Filling cup 1 1 1 1 1
N 141300 Supply valve connection 1 1 1 1 1
K 2400006 Rubber gasket for drain tank 1 1 1 1 1
B 240007 Rubber gasket for supply valve connection 1 1 1 1 1
F
A 183205 Drain valve armature 1 1 1 1 1
H 183206 Drain valve housing 1 1 1 1 1
O 254001 Drain valve solenoid 1 1 1 1 1 (+)
X 254393 Connector for level electrode 1 1 1 1 1
Y 254394 Connector for production electrode 2 3 3 3 3
Z 271099 Base 1 1 1 1 1
(+) = Spare part recommended (*) = Consumable material
DE DESCRIPTION
141070 Steam cylinder 140
141071 Steam cylinder 263
141072 Steam cylinder 243
141073 Steam cylinder 363
141074 Steam cylinder 343
183209 Complete supply valve
183204 Complete supply valve
275905 Isolator for level sensor 1 1 1 1 1
21L 53H 53L 93H 93L
1
1
INSTALLED QUANTITY
1
1
1
1 1 1 1
Notes
(*)
(*)
(*)
(*)
1
(*)
A − 4
English
Page 35
Il Fabbricante dichiara che questo prodotto è conforme alle direttive Europee: The Manufacturer hereby declares that this product conforms to the European Union directives: Der Hersteller erklärt hiermit, dass dieses Produkt den Anforderungen der Europäischen Richtlinien gerecht wird: Le Fabricant déclare que ce produit est conforme aux directives Européennes: El Fabricante declara que este producto es conforme a las directivas Europeas: O Fabricante declara que este produto está em conformidade com as directivas Europeias: Tillverkare försäkrar härmed att denna produkt överensstämmer med Europeiska Uniones direktiv: De Fabrikant verklaart dat dit produkt conform de Europese richtlijnen is: Vaimistaja vakuuttaa täten, että tämä tuote täyättää seuraavien EU-direktiivien vaatimukset: Produsent erklærer herved at dette produktet er i samsvar med EU-direktiver: Fabrikant erklærer herved, at dette produkt opfylder kravene i EU direktiverne:
Since the Liebert HIROSS Company has a policy of continuous
Ο ΚατασÀευαστÞj δηλþνει üτι το παÃüνπÃοΪüνεßναι ÀατασÀευασmÝνο αýmφωνα mετιj οδηγßεj τηj Ε.Ε.:
product improvement, it reserves the right to change design and specifications without previous notice.
98/37/CE; 89/336/CEE; 73/23/CEE; 97/23/CE
Printed in Italy by Liebert HIROSS S.p A.
Issued by T.D.Service
Page 36
Zona Industriale Tognana
Via Leonardo da Vinci, 16/18
35028 Piove di Sacco (PD)
ITALY
Tel. +39 049 9719111
Telefax +39 049 5841257
Internet :
www.liebert-hiross.com
Since the Liebert HIROSS Company has a policy of continuous product improvement, it reserves the right to change design and specifications without previous notice.
Liebert HIROSS
is a division of
EMERSON
Printed in Italy by Liebert HIROSS S.p A.
Issued by T.D.Service
Loading...