Liebert Hiross Himod 65UC, Himod 27UC, Himod 80UC, Himod 85UC, Himod 90UC Service Manual

...
Himod
C Version
Service Manual
English
cod. 272631 − rev. 25.02.2005
Caution
We recommend that:
turer from any liability.
This manual has been prepared to enable the end−user to carry out only the operations that can be made with the panels closed. Any operations that require the opening of doors or equipment panels must be carried out only by qualified personnel. Each machine is equipped with an Electric Insulating device which allows the operator to work in conditions of safety. Switch off the machine before any maintenance operation to eliminate risks remaining (electric shocks, scalds, automatic restarting, mov­ing parts and remote control).
For "UNDER" units installed on raised floor: switch off the machine before removal of the floor panels within a distance of 850 mm from the machine, to avoid risks of contact with rotating devices.
The panel key supplied with the unit must be kept by the person responsible for maintenance. For identification of the unit (model and serial no.) in case of the necessity for assistance or spare parts, locate the identification
label on the outside of the unit.

Index

1 − Preliminary operations 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 − Inspection 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 − Handling 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 − Operating limits 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.4 − Identification 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 − Positioning 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 − Clearance areas and main dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 − Overall dimensions 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 − Installation 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 − Air inlet and outlet 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 − Hole in raised floor 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 − Extension hood 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 − Extension hood with sound reduction cartridges (Over unit) 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 − Horizontal discharge hood (Over unit) 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.6 − Base module 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.7 − Base frame 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.8 − High efficiency filters 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.9 − New Air module 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 − Water connections 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 − General warnings 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 − Auxiliary water connections 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 − Chilled water connections 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4 − Adding ethylene glycol 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 − Electrical connections 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 − Electrical connections 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 − Fan connections 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 − Aeraulic features 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 − Start−up 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1 − First start−up (or after long standstill) 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 − Starting and stopping 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3 − Automatic restart 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 − Operation 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1 − Chilled water valve 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
English
8 − Calibrations 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9 − Maintenance / Spare Parts 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.1 − Spare parts 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2 − Dismantling the unit 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A − HUMIDAIR humidifier A − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.1 − Preface A − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.2 − Installation A − 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.3 − Humidair components A − 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.4 − Start−up and operation A − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.4.1 − Start−up A − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.4.2 − Operation A − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.5 − Maintenance A − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.5.1 − Removing the steam cylinder A − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.5.2 − Replacing the steam cylinder A − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.5.3 − Annual maintenance A − 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
App. A.6 − Spare part list A − 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The Service Manual HIMOD can also be surfed on the Web at the address: www.HIROSS.IT/pde/TDS/Himod
This document is password−protected. Ask for the password to your Dealer/Area Manager.
English
1 − Preliminary operations
Room conditions
Hot water heating coil
Chilled water coil
1.1 − Inspection
On receiving the equipment immediately check its condition; report any damage to the transport compa­ny at once.
1.2 − Handling
S Always keep the unit vertically upright and do not
leave it out in the open.
S If possible transport the unit using a fork lift truck;
otherwise use a crane with belts or cables, avoiding pressing on the top edges of the packing.
1.3 − Operating limits
The units are designed to operate within working ranges (see Tab. 1). These limits are referred to new machines or to those that have been correctly installed and serviced. The warranty clauses are no longer valid for any pos­sible damage or malfunction that may occur during or due to operation outside the application values.
1.4 − Identification
The air conditioner can be identified according to the following nomenclature:
27
UC
Model
Air distribution:
U = Under (downflow)
= Over (upflow)O
Cooling circuit:
A = air−cooled
= water−cooledW
= chilled water
C
F = Freecooler
= Dualfluid (air−cooled)D = Dualfluid (water−cooled)
H
Tab. 1 − Operating limits
Room conditions
Voltage tolerances
UNDER OVER
from: 18°C, 45% R.H.
to: 27°C, 55% R.H
standard 400V 10%/3/50
208B230V ± 10%/3/60
optional
380V ± 10%/3/60 460V ± 10%/3/60
To view the Service Manual HIMOD version A/W/F/D/H, refer to the Manual code 272157
Hot water heating coil
Chilled water coil
Storage conditions
inlet water temperature
water pressure max. 8.5 bar inlet water
temperature
water pressure max. 16 bar
from: − 20°C
to: 50°C
max. 85°C
min. 5°C
English
HIMOD−C
1
2 − Positioning
2.1 − Clearance areas and main dimensions
MODEL
27−45 O/UC 55−65−80−85 O/UC 90−10 UC 12−14 UC
A [mm] 1000 1750 2050 2550 B [mm] 1740 1740 1740 1740 C [mm] 800 800 800 800 D [mm] 890 890 890 890 E [mm] 50 50 50 50
F [mm] 1950 1950 1950 1950
MODEL WEIGHT (kg) − standard unit
27 UC 290 45 UC 340 55 UC 495 65 UC 555 80 UC 590 85 UC 610 90 UC 660 10 UC 670 12 UC 830 14 UC 840 27 OC 290 45 OC 340 55 OC 495 65 OC 555 80 OC 590 85 OC 610
2
HIMOD−C
English
2.2 − Overall dimensions
27−45 UC 55−65−80−85 UC
Under Version
1000
5 990
90−10 UC 12−14 UC
2050
1750
1950
40
5
5
1740
2550
5
50
885
5
1950
40
5
2040
5
5
2540
50
5
885
5
Over Version
27−45 OC 55−65−80−85 OC
1000
1750
1950
English
5 990
40
5
5
1740
HIMOD−C
5
50
890
3
3 − Installation
ATTENTION: The conditioner must never be installed out of doors.
3.1 − Air inlet and outlet
27−45 C − under
55−65−80−85 C − under
27−45 C − under
55−65−80−85 C − under
90−10 C − under
12−14 C − under
90−10 C − under
12−14 C − under
A B C D
910 778 40 52
1580 778 80 52
E F G H L
910 804 43 43 45
1660 804 43 43 45
A B C D
1960 297 40 483 2460 297 40 483
E F G H L
1960 799 43 46 45 2460 799 43 46 45
Look−through rear view
ATTENTION: About the upflow (over) units, the extraordinary removal of the fan (560 mm blade diameter) is per­mitted only from the top of the unit. Please keep it on mind during the possible ducting design and manufacturing.
3.2 − Hole in raised floor
27−45 C 55−65−80−85 C
without base frame with base frame without base frame with base frame A [mm] 900 1000 1650 1750 B [mm] 810 885 810 885 C [mm] 93 48 93 48
90−10 UC 12−14 UC
without base frame with base frame without base frame with base frame A [mm] 1970 2050 2470 2550 B [mm] 810 885 810 885 C [mm] 93 48 93 48
CAUTION: For "UNDER" units installed on raised floor, inhibit inappropriate access to the unit from the base to not−authotized staff: i.e. fixing the floor panels up to 850 mm from the unit.
4
HIMOD−C
English
3.3 − Extension hood
false ceiling
27−45 C
55−65−80−85 C
90−10 UC
12−14 UC
3.4 − Extension hood with sound reduction car­tridges (Over unit)
A B C D
1000 890 500 / 1200 30 1750 890 500 / 1200 30 2050 890 500 / 1200 30 2550 890 500 / 1200 30
3.5 − Horizontal discharge hood (Over unit)
English
HIMOD−C
front back
A B C
27−45 C
55−65−80−85 C
1000 890 600/900 1750 890 600/900
5
3.6 − Base module
If there is no raised floor below the unit it must be placed on a base module to allow access to the external connections. The conditioner is connected to the base module by 4 screws.
3.7 − Base frame
27−45 C
55−65−80−85 C
90−10 UC
12−14 UC
3.8 − High efficiency filters
A B C
990 885 200 1740 885 200 2040 885 200 2540 885 200
6
HIMOD−C
English
3.9 − New Air module
UNDER
(C version)
UNDER
(Mod. 90−10 − C version)
OVER
(C version)
UNDER
(Mod. 12−14 − C version)
English
HIMOD−C
7