Sequencing Status Screens.....................................................................................................................................5
Main Menu ............................................................................................................................................................6
Status Sub-menu..........................................................................................................................................6
Set Options Sub-menu.................................................................................................................................8
Set Clock Sub-menu.................................................................................................................................. 14
Main Menu ..........................................................................................................................................................16
Status Screen.............................................................................................................................................17
Alarms Review and Alarms Clear .............................................................................................................21
Set Clock...................................................................................................................................................21
Override A Unit ........................................................................................................................................22
Set Modem Options...................................................................................................................................23
Setup Standby Unit Options...................................................................................................................... 25
Display SS Alarm Block ...........................................................................................................................26
Set New Password.....................................................................................................................................26
Figure i. Typical System Configuration..........................................................................................................iii
Figure 2–1. Local Control Panel ..........................................................................................................................3
Figure 5–4. RAC2-8 Switch and Jumper Settings ..............................................................................................42
ii • User Manual (9/97)
Power Source
120 VAC
Aux Pwr Out
24 VAC, 2A
Terminal
Port
Modem
Port
SiteScan
Liebert
Temp/Humid
Module
(p/n THS28-xx)
Emergency
Power Oper.
Input
Emergency
Power Off
RAC2-8
EIA-232 EIA-232
N.O.
N.C.
N.O.
N.C.
N.O.
N.C.
C
C
C
EIA-422
Twisted Pair
Common Alar m
Output
Humidity Lockout
Relay
Optional Lockout
Relay
Control
Input
UNIT 1
Common
Alarm
Output
Control
Input
Common
Alarm
Output
UNIT 2
Figure i. Typical System Configuration
Control
Common
Input
UNIT 8
Liebert RAC2-8 • iii
Alarm
Output
Section 1: Introduction
See SECTION 5 —
INSTALLATION for special
instructions when using the RAC2-8
with Liebert mini-MATE, miniPlus, and DataMate environmental
control systems.
MATE
The Liebert RAC2-8 remotely controls from two to eight environmental
units. Each unit is assigned to a Zone (room) from 1 to 4. In Zone 1, the
largest room, the temperature and humidity can be monitored. The
common alarm output from each unit is monitored and annunciated by
the RAC2-8. Up to 20 system alarms can be stored with time and date
stamp. All alarms are latching and must be manually cleared.
The most important control functions are Autochangeover,
Autosequencing, and Standby Testing. Each unit can be assigned a
Running or Standby status.
Autochangeover turns on a Standby unit if a Running unit in the same
zone has an alarm. The Running unit (with alarm) will be turned off if
that control option is selected. Each unit will return to its previous
status when the alarm is manually cleared.
Autosequencing balances unit run-times by changing Standby units to
Running (and Running units to Standby) at programmed time intervals.
Standby Testing turns on Standby units at programmed intervals to test
their operation. Note that Autosequencing and Standby Testing cannot
both be selected at the same time.
Other control functions include Manual Override, Emergency Power
Operation, Power Failure Mode, Password, and Programmable Delays.
Refer to SECTION 4 — GLOSSARY OF CONTROL FUNCTIONS
for more details.
System outputs include Humidity Lockout Relay, Optional Control
Lockout Relay, and Common Alarm. Communication ports are
EIA-232 for terminal or printer, a modem port, and a proprietary
EIA-422 port for communication to a Liebert SiteScan monitoring
system.
The RAC2-8 can be operated locally from the built-in control panel or
remotely from an optional terminal (EIA-232 communication). This
manual shows examples of several typical display screens during both
local and remote operation.
Liebert RAC2-8 • 1
Section 2: Start Up
To start up the RAC2-8:
1. Mount unit to wall.
2. Connect cables.
3. Set switches and jumpers on circuit boards as required for your
application. Refer to instructions and illustrations in SECTION 5
— INSTALLATION.
4. Make user programmable selections from the local control panel or
from an optional remote terminal. Refer to SECTION 4 —
GLOSSARY OF CONTROL FUNCTIONS and SECTION 3 —
OPERATION.
5. Apply power to the unit. Note that the ON/OFF switch is inside the
enclosure.
Figure 2–1. Local Control Panel
Liebert RAC2-8 • 3
4 • User Manual (9/97)
Section 3: Operation
Local
Sequencing Status Screens
This chapter describes how to use the RAC2-8.
The following screens are displayed at the LCD display built into the
RAC2-8 unit control panel. Refer to SECTION 4 — GLOSSARY OF CONTROL FUNCTIONS for more details.
With power ON, the following status screens are displayed in sequence.
LIEBERT RAC2-8
TEMP 71.8°F HUM 47%
MO 07-15-96 13:26:55
NO ALARMS PRESENT
STATUS ZONE 1
01-R 02-S
A=ALM S=STBY R=RUN
STATUS ZONE 2
03-R 04-S
A=ALM S=STBY R=RUN
STATUS ZONE 3
05-R 06-S
A=ALM S=STBY R=RUN
STATUS ZONE 4
07-R 08-S
A=ALM S=STBY R=RUN
Liebert RAC2-8 • 5
Sequencing Status Screens (cont’d.)
xx is the number of alarms recorded
since alarm history was last cleared.
See Alarm submenu.
These functions cannot both be ON
at the same time. Select the function
required for your installation.
Section 3: Operation
AUTO SEQUENCING ON
DAY 06 OF 15 <00:00>
TEMP STAGING OFF
Each screen is automatically displayed for 3 seconds.
To control the display of the status screens, you can press the
Hold/Sequence button to hold a screen and to manually step through the
screens. Press C to resume automatic sequencing. The system returns to
the Sequencing Status Screens if no control keys have been pressed
during a two minute period.
If alarms are present, the last line of the first screen displayed above
reads “ALARMS PRESENT - xx.” Alarm screens are displayed next in
the status sequence. Up to 20 alarms can be displayed, 5 screens of 4
alarms each. Alarms are stored in a First In First Out (FIFO) sequence.
Select either Auto Sequencing or Standby Testing from the Set Options
Sub-menu.
Password Screen
Main Menu
If the Password function is enabled, you must enter the valid password
to access the RAC2-8 Main Menu. At the Enter Password screen, type
the established password:
ENTER PASSWORD
>
Units are shipped from the factory with the Password function disabled.
To enable the Password function, press the MENU button to display the
Main Menu, then press 2 SETUP. Follow the instructions on page 12 to
Set Password.
Press the Menu button to display the Main Menu:
MAIN MENU
1. STATUS 2. SETUP
3. ALARMS 4. SET CLOCK
5. OVERRIDE 6. EXIT
Press 9 to display RAC2-8 revision code and date.
Status Sub-menu
6 • User Manual (9/97)
From the Main Menu, press 1. STATUS to display the Status Submenu:
Section 3: Operation
STATUS MENU
1. UNITS 2. T/H
3. A-DELAY 4. R-DELAY
5. H-DELAY 6. RETURN
1. UNITS
From the Status Sub-menu, press 1. UNITS to display the Unit Status
menu:
UNIT STATUS
01-R 02-S 03-R 04-S
05-R 06-S 07-R 08-S
A=ALM S=STBY R=RUN
2. T/H
From the Status Sub-menu, press 2. T/H to display the
Temperature/Humidity screen:
TEMP 71.8°F HUM 47%
STAGING OFF
PUSH CLEAR TO RETURN
3. A-DELAY
From the Status Sub-menu, press 3. A-DELAY to display the Alarm
Delays screen:
The Alarm Delays screen indicates the time in seconds of an active
delay on each unit. Active alarm delays count up while the condition is
present and count down if the condition is cleared before the Alarm
Delay time elapses.
4. R-DELAY
From the Status Sub-menu, press 4. R-DELAY to display the Restart
Delays screen:
The Restart Delays screen indicates the time in seconds of an active
restart delay on each unit.
5. H-DELAY
From the Status Sub-menu, press 5. H-DELAY to display the Hold
Delay screen:
Set Options Sub-menu
Set Options Sub-menu (cont’d)
HOLD DELAY = 0000
PUSH CLEAR TO RETURN
Hold Delay applies to the system rather than to each unit. Therefore,
only one number is displayed. This display indicates the time in seconds
of an active Hold Delay.
From the Main Menu, press 2. SETUP to display the Set Options
Menu:
SET OPTIONS MENU
1. UNITS 2. DELAYS
3. TEMP/HUM 4. STANDBY
5. PASSWORD 6. RETURN
1. UNITS
From the Set Options Sub-menu, press 1. UNITS to display the Set
Units menu:
8 • User Manual (9/97)
SET UNITS MENU
1. ZONES/UNITS
2. EMER.OP 3. LABELS
4. SHUTDOWN 5. RETURN
Section 3: Operation
Note that the Clear button will not
allow you to exit these screens until
all selections have been made.
From the Set Units menu, select 1. ZONES/UNITS to select the number
of zones, number of units in each zone, and operating status of each
unit. Complete all of these selections before exiting this setup
function.
When you press 1. ZONES/UNITS, the RAC2-8 sequences through the
screens you must complete.
SET NUMBER OF ZONES
RANGE 1-4 <4> >_
PUSH ENTER FOR NEXT
SET NUMBER OF UNITS
ZONE 1 <2> >_
PUSH ENTER FOR NEXT
Set Number of Units screen will be iterated for each zone selected (up
to 4).
The RAC2-8 then displays the Set Status screen for Zone 1:
SET STATUS ZONE 1
01-R 02-S
1=RUN O=STBY E=NEXT
Set Status screen is iterated for each zone selected. Press 1, or 0 to set
the status. After you have selected the operating status of units in your
last zone, Press E to return to the Set Units Menu.
Set Options Sub-menu (cont’d)
From the Set Units menu, press 2. EMER OP. to display the Set
Emergency Operating Units ON screen:
SET EMRG.OP UNITS ON
01-R 02-0 03-0 04-R
05-0 06-R 07-0 08-0
1=RUN O=OFF E=NEXT
Beginning with unit 01, set each unit's emergency operating status.
Press E to continue to the next unit. When you have configured the last
unit, the RAC2-8 returns to the Set Units menu.
From the Set Units menu, press 3. LABELS to display the Assign
Labels to Unit screen:
ASSIGN LABEL TO UNIT
1-01 2-02 3-03 4-04
5-05 6-06 7-07 8-08
PUSH ENTER FOR NEXT
Beginning with unit 01, assign a label to each unit. You can use two
numbers, two letters, or a two-character number/letter label. Press E to
continue to the next unit. When you have configured the last unit, the
RAC2-8 returns to the Set Units menu.
Liebert RAC2-8 • 9
Section 3: Operation
From the Set Units menu, press 4. SHUTDOWN to display the
Shutdown on Alarm screen:
Beginning with unit 01, indicate 1 (Yes) or 0 (No) if the unit should
shut down on alarm. When you have selected the shutdown status for
the last unit, the RAC2-8 displays the Set Units menu.
When you have configured the delays, from the Set Units menu, press 5
to return to the Set Options Menu.
2. DELAYS
SECTION 4 — GLOSSARY OF
CONTROL FUNCTIONS
includes a functional description
of each delay.
Set Options Sub-menu (cont’d)
From the Set Options Sub-menu, press 2. DELAYS to display the Set
Delays menu:
SET DELAYS MENU
1. ALARM 2.HOLD
3. UNIT RESTART
5. RETURN
From the Set Delays menu, press 1. ALARM to configure the Alarm
Delay:
ENTER ALARM DELAY
<10.0> XX.X MINUTES
THEN PUSH ENTER
PUSH CLEAR TO RETURN
Enter the desired time for the alarm delay. The default is 10 minutes.
Press E to accept the new delay, then press C to return to the Set Delays
menu.
From the Set Delays menu, press 2. HOLD to configure the Hold
Delay:
10 • User Manual (9/97)
ENTER HOLD DELAY
<10.0> XX.X MINUTES
THEN PUSH ENTER
PUSH CLEAR TO RETURN
Enter the desired time for the hold delay. The default is 10 minutes.
Press E to accept the new delay, then press C to return to the Set Delays
menu.