IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that should be followed during the installation and maintenance of the UPS and its batteries. Please read this manual thoroughly before attempting to install or operate this UPS.
This equipment can be installed and operated by indiv idua ls withou t previo us training.
1. PowerSure Personal models are available for 115VAC and 230VAC supply voltages and loads. Please verify that this model matches your AC mains/ load voltage requirements.
2. This equipment is designed for Commercial/Industrial use only. Liebert Corporation neither recommends nor knowingly sells this product for use in critical life support applications.
3. The PowerSure Personal 230VAC models are not supplied with an input power lead for connection to the mains supply. Use the input mains power lead from your data processing equipment to connect the UPS to the mains supply. The UPS is supplied with two output power leads with moulded connectors to connect from the UPS output to your equipment. Additional input/output leads can be obtained from your dealer. Also provided is a Liebert special interconnection cable for connection to DB9 connector on the rear of the UPS for use with Liebert’s SiteNet MultiLink® software (see user manual for details) DO NOT USE FOR OTHER APPLICATIONS. Store in safe place if not required at this time.
4. This UPS must be earthed at all times during operation. Connect only to a mains supply socket outlet with an earth connection. A means of disconnection of the mains supply should be within 2 metres of the UPS.
5. WARNING: Output receptacles on the UPS are electrically live if the UPS is switched ON, even if the UPS is not plugged in to a mains supply. The On/Off button on the UPS does not electrically isolate the internal parts. To isolate the UPS, switch OFF the UPS first, then unplug it from the mains.
To reduce the risk of electric shock, do not remove the cover, as it has no user-
serviceable parts inside. Some components are live, even when AC power is disconnected. For service, contact a qualified technician.
To reduce the risk of fire, use the proper rating when replacing the fuse.
To prevent the risk of fire or electric shock, install the UPS in a temperature and humidity
controlled room, free of conductive contaminants.
6. Your total load earth leakage current must not exceed 2.75 milli-amperes. Most data processing equipment meets this requirement if you use no more than 2 pieces of equipment. For further advice contact your dealer.
7. The UPS relies on your building wiring overcurrent protection, which must be rated between 10-20 amperes.
8. W hen using the communication features on the UPS, ensure the cabling connected to the DB9 communication port or the network connection are kept separated by 25mm from the power leads to the UPS input and output.
2
Electromagnetic Compatibility: This equipment complies with EMC Directive 89/336/EEC and the published technical standards. Continued compliance requires installation in accordance with these instructions and the use of manufacturer approv ed ac ce ssories only.
CAUTION:
Although your UPS has been designed and manufactured to assure personal safety, improper use can result in electrical shock or fire. To insure safety, please observe the following rules:
Turn off and unplug your UPS before cleaning. Do not use liquid or aerosol cleaners. A
dry cloth is recommended to remove dust from the surface of your UPS.
Do not install or operate your UPS in or near water.
Do not place UPS on an unstable cart, stand, or table.
Do not place UPS under direct sunlight or close to heat emitting sources.
Do not place UPS power cord in any area where it may get damaged by heavy objects.
Follow all warnings and instructions marked on the UPS. Do not attempt to service the
UPS, as it has no user-serviceable parts inside. Refer all repairs to qualified service personnel.
ATTENTION:
Turn off and unplug your UPS from the outlet and contact qualified service personnel if:
The power cord or plug is damaged.
Liquid has been spilled on the UPS.
The fuse blows frequently.
The UPS does not operate even when user follows the operating instructions.
CONDITIONS OF USE:
Your UPS provides conditioned power to connected equipment. Maximum load must not exceed that shown on UPS rating label. If uncertain, consult your distributor or Liebert.
Placing magnetic storage media on top of the UPS may result in data corruption.
3
INTRODUCTION & SYSTEM DESCRIPTION
y
Congratulations on your choice of the Liebert PowerSure Personal Uninterruptible Power System (UPS). It provides conditioned power to microcomputers and other sensitive electronic equipment.
MAJOR COMPONENTS
TM
Pow erSure
Per so na l
DB -9 In te rfa c e fo r
Warning LED
Power ON / Standb
Liebert
Main s / B a ttery LED
R
SiteN et MultiL ink C ab le
Output
Receptacles
Input Receptacle
/ Fuse Holder