Liebert PSP User Manual

Page 1
POWER AVAILABILITY
PowerSure™ PSP
USER MANUAL
500-650 VA
230V
Page 2
Page 3
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS. . . . . . . . . . . . . . . . . . . . . 1
Front View of UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Rear View of UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
MAJOR COMPONENTS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Transient Voltage Surge Suppression (TVSS) & EMI / RFI
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Transfer Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
CONTROLS AND INDICATORS. . . . . . . . . . . . . . . . . . . . . . . . . 11
ON/OFF/ Alarm Silence Button . . . . . . . . . . . . . . . . . . . . . . . . 11
Status Indicators: Fault, Utility, Battery. . . . . . . . . . . . . . . . . 12
Utility Indicator (Green) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Battery Indicator (Green/Amber) . . . . . . . . . . . . . . . . . . . . . . . . . 12
Fault Indicator (Red/Green) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Location and Status of Indicators . . . . . . . . . . . . . . . . . . . . . . . . . 12
Transfer Voltage Selectors (DIP Switches). . . . . . . . . . . . . . . . 13
MODES OF OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
DB-9 Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Remote Shutdown Via the DB-9 Connector . . . . . . . . . . . . . . . 17
Shutdown Via Pins 5 & 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Shutdown Via Pins 4 & 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
USB Interface Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Data Line Protection Connectors . . . . . . . . . . . . . . . . . . . . . . . 17
i
Page 4
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Cleaning the UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Maintaining Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Battery Replacement Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . 19
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Guide to Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Troubleshooting Chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Battery Run Times. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
ii
Page 5
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that should be fol­lowed during the installation and maintenance of the Uninterruptible Power System (UPS) and its batteries. Please read this manual thor­oughly before attempting to install or operate this UPS.
Read all safety, installation, and operating instructions before operat­ing the UPS. Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions.
This equipment is designed for Commercial, Industrial or Residential use. Liebert Corporation neither recommends nor knowingly sells this product for use in life support applications or with other designated critical devices.
This equipment can be installed and operated by individuals without previous training.
WARNING
!
SAFETY PRECAUTIONS
• There are no user-serviceable parts inside this UPS except the internal battery pack. Refer all UPS service to quali­fied service personnel. Do not attempt to service this prod­uct yourself.
• Output receptacles on the UPS are electrically live if the UPS is switched on, even if the UPS is not plugged into a Mains supply. The ON/OFF button on the UPS does not electrically isolate the internal parts. Some components are live even when Mains power is disconnected. To isolate the UPS, switch off the UPS first, then unplug it from the Mains.
• Opening or removing the cover may expose you to lethal voltages within this unit even when it is apparently not operating and the input wiring is disconnected from the electrical source.
• Observe all CAUTION and WARNING statements in this manual and on the unit. Failure to do so may result in serious injury or death.
• Never work alone.
1
Page 6
WARNING
!
ELECTRICAL PRECAUTIONS
• This UPS should not be supplied from electrical power sys­tems of the “IT” (Impedance á Terre) type (IEC 364 - Elec­trical Installation of Buildings).
• The UPS must be earthed/grounded at all times during operation. Connect only to a mains supply socket outlet with an earth/ground connection.
CAUTION
!
Although your UPS has been designed and manufactured to assure personal safety, improper use may result in electrical shock or fire. To ensure safety, please observe the following rules:
• Turn off and unplug your UPS before cleaning. Do not use liquid or aerosol cleaners. A dry cloth is recommended to remove dust from the surface of your UPS.
• Do not install or operate your UPS in or near water.
• Do not place your UPS on an unstable cart, stand or table.
• Do not place your UPS in direct sunlight or near heat emitting sources.
• Never block or insert any objects into the ventilation holes or other openings of the UPS. Keep all vents free of dust accumulation that could restrict airflow.
• Do not place the UPS power cord in any area where it may be damaged by heavy objects.
• Placing magnetic storage on the top of the UPS may result in data corruption.
2
Page 7
CAUTION
!
BATTERY HANDLING PRECAUTIONS Servicing of batteries should be performed or supervised by
personnel knowledgeable of batteries and required precautions. Keep unauthorized personnel away from the batteries.
A battery can present a risk of electrical shock and high short-circuit current. The following precautions should be observed when working on batteries:
• Remove watches, rings, and other metal objects.
• Use tools with insulated handles.
• Do not dispose battery or batteries in a fire. The battery may explode.
• Do not open or mutilate the battery or batteries. Released electrolyte is harmful to skin and eyes. It may be toxic.
• When replacing the battery, use same number and type of battery as the suitable recommended type of battery listed in specification table in back of this manual.
• Handle, transport and recycle batteries in accordance with local regulations.
WARNING
!
If your UPS demonstrates any of the following conditions, turn off and unplug your UPS from the outlet and contact your local dealer, Liebert representative, or Liebert Worldwide Support Group.
• The power cord is damaged.
• Liquid has been spilled on the UPS.
• The circuit breaker or fuse opens frequently.
• The UPS does not operate in accordance with the user manual.
Electromagnetic Compatibility—The PowerSure PSP series com­plies with the requirements of the EMC Directive 89/336/EEC and the published technical standards. Continued compliance requires instal­lation in accordance with these instructions and use of Lie­bert-approved accessories only.
Environmental—Operate the UPS in an indoor environment only in an ambient temperature range of 0°C to 40°C (32°F to 104°F). Install in a clean environment, free from conductive contaminants, moisture, flammable liquids, gases or corrosive substances.
Provided are a Liebert MultiLink cable and a USB cable for connec­tion to a computer. Do not use the Liebert MultiLink cable for other applications. Store in a safe place if not required at this time. When using the communication features on this UPS, ensure the cabling connected to the DB-9 or UPS communications ports are kept sepa­rated from the power leads to the UPS input and output.
3
Page 8
INTRODUCTION & SYSTEM DESCRIPTION
Congratulations on your choice of the Liebert PowerSure™ PSP Unin­terruptible Power System (UPS). It provides filtered AC power to sen­sitive electronic equipment and other critical loads.
The PowerSure PSP is an off-line UPS designed for desktop applica­tions. It provides perfect one-to-one power protection for electronic equipment such as PCs, point-of-sale displays, home office equipment and similar electronic gear. The PowerSure PSP is available in 350, 500 and 650VA at 120VAC and 500 and 650VA at 230VAC. The con­figurable input power selector switch offers the user a wide input volt­age window.
In the absence of utility power, the UPS supplies connected equipment with a stepped sinewave.
4
Page 9
Front View of UPS
Power ON/OFF/
Alarm Silence*
Utility Indicator* (Green)
Fault
Indicator*
(Red/Green)
Battery Indicator* (Green/Amber)
* For details, see
Controls and Indicators section
5
Page 10
Rear View of UPS
DB-9 port***
Orange output receptacles (4)*
Battery backup + surge protection
USB port***
DIP switches**
185-270V 185-280V 175-270V
175-280V Refer to user's manual for voltage setting
Data Line Protection Connectors (2)***
Phone/Fax/DSL/ Internet/Modem devices
Battery Back-up + Surge Protection
Black output receptacles (2)*
Surge protection only
AC input
CAUTION: Risk of electric shock.
Refer to bottom of unit for cautionary marking.
Battery cover plate (on bottom of UPS)
For details, see: * Installation section ** Controls and Indicators section *** Communications section
6
Circuit Breaker Push to Reset
Surge Protection Only
Input circuit protector
Page 11
MAJOR COMPONENTS
Input Output
L
N G
TVSS &
EMI / RFI
Filters
Battery
Charger
Battery
Transfer
Switch
Inverter
L
N G
Transient Voltage Surge Suppression (TVSS) & EMI / RFI Filters
These UPS components provide surge protection and filter electro­magnetic interference (EMI) and radio frequency interference (RFI). They minimize surges or interference present in the utility line and keep the sensitive equipment protected.
Transfer Switch
In Normal mode the Transfer Switch passes utility AC power to the connected load. When input utility or frequency is outside acceptable limits, the transfer switch activates and transfers the UPS to battery.
Battery Charger
In Normal mode, the Battery Charger converts utility AC power into regulated DC power to float charge the battery. It is continuously charging the battery whenever the UPS is plugged into a power outlet and utility power is within acceptable limits—even if the UPS is turned OFF.
Battery
The PowerSure PSP utilizes a valve-regulated, nonspillable, lead acid battery. To optimize battery life, operate the UPS in an ambient tem­perature of 20°-25°C (68°-77°F).
Inverter
When utility power fails, the Inverter draws energy from the battery and inverts it into a regulated stepped sinewave supplying power for equipment connected to the orange receptacles.
7
Page 12
WHATS INCLUDED
The PowerSure PSP is shipped with the following components:
• PowerSure PSP user manual
• Two (2) 10A output power cords, 2.0m (6.6 ft.)
• MultiLink™ software CD
• MultiLink serial cable (M3LS9P9S), 3m (10 ft.)
• RJ-11 cord, 2.1m (7 ft.)
• USB cable, 1.8m (6 ft.)
PowerSure
PSP
RJ-11 cord
2.1m (7 ft.)
MultiLink
software CD
USB cable
1.8 m (6 ft.)
MultiLink
serial cable
(M3LS9P9S)
3m (10 ft.)
Two (2) 10A
output power
cords, 2.0m
(6.6 ft.)
8
Page 13
INSTALLATION
1. Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer, Liebert representative or the Liebert Worldwide Support Group.
2. Decide where to place the PowerSure PSP. Install the UPS indoors in a controlled environment, where it cannot be accidentally turned off. Place it in an area of unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives, and conductive contaminants. Maintain a minimum clearance of 100mm (4 in) on each side of the UPS. Maintain an ambient temperature range of 0°C to 40°C (32°F to 104°F).
NOTE
UPS operation in temperatures above 25°C (77°F) reduces battery life.
Plug computers, monitors & network hubs into orange receptacles
185-270V 185-280V 175-270V
175-280V Refer to user's manual for voltage setting
Battery Back-up + Surge Protection
Plug this type of equipment into black receptacles ONLY
Surge Protection Only
CAUTION: Risk of electric shock.
Refer to bottom of unit for cautionary marking.
Circuit Breaker Push to Reset
Inkjet
printer
Scanner Fax
machine
3. Plug the PowerSure PSP’s attached 1.8m (6-ft.) power cord into an AC outlet.
4. Plug any computers and monitors into the orange battery backed up receptacles.
Other office machines that do not exceed the capacity of the UPS— inkjet printers, scanners and fax machines—may be plugged into either of the two (2) black receptacles, which provide surge protec­tion only.
9
Page 14
5. Connect Phone/Fax/DSL/Internet/Modem devices to data line connec­tors.
Serial port for MultiLink cable connection
185-270V 185-280V
175-270V
175-280V
Refer to user's manual for voltage setting
6. Press and release the ON/OFF/Alarm Silence button to turn on the UPS. The UPS will beep and the Utility Indicator will illuminate (green).
7. Turn on connected equipment.
8. Communication options (see Communications section for details):
Option 1—Serial Communications
Serial communications provides parametric data, for example, input voltage and battery voltage.
a. Connect Multilink serial cable included with the UPS to commu-
nications port.
b. Install the MultiLink software—the software and installation
instructions, as well as the user manual, are on the CD included in the PowerSure PSP package.
Option 2—Contact Closure Communications
Contact Closure communications provides on-battery and low-bat­tery signals for orderly shutdown.
a. Refer to the MultiLink user manual for instructions on making
your own contact closure cable.
b. Install the MultiLink software—the software and installation
instructions, as well as the user manual, are on the CD included in the PowerSure PSP package.
Option 3—USB Communications
Connect USB cable provided with the UPS to the USB ports on the PSP and your computer. The PSP will work automatically with your built-in power management software on Windows XP and 2000 and Mac OS 10.2 or later (see USB Interface Port sec­tion for details).
10
Page 15
CONTROLS AND INDICATORS
ON/OFF/Alarm Silence Button
This button controls output power to the connected load and has three functions:
•ON
•OFF
• Alarm Silence
ON When the UPS is off, pressing and releasing the main ON/
OFF button will start the UPS, and an audible alarm sounds briefly. The UPS is capable of starting on battery (battery start).
OFF When the UPS is on (in either Normal or Battery mode),
pressing the main ON/OFF button for more than two (2) seconds will shut down the UPS. An audible alarm sounds briefly.
Alarm Silence
When a UPS alarm is active, pressing and releasing the main ON/OFF button will silence the active audible alarm, whether utility power is present or not. Once the alarm silence function has been activated, all active audible alarms—except for low battery, overload, or over-tempera­ture conditions—will remain silenced until a new alarm con­dition is detected.
ON/OFF/Alarm Silence
NOTE
Do not hold ON/OFF button down for more than 2 seconds or the UPS will shut down.
11
Page 16
Status Indicators: Fault, Utility, Battery
There are three (3) status indicators on the front of the UPS (Utility, Battery and Fault), as shown in the diagram below. Each indicator illuminates to specify the status of the UPS (see Troubleshooting section for details).
Utility Indicator (Green)
The Utility Indicator illuminates green when the UPS is operating and supplying power to connected loads.
Battery Indicator (Green/Amber)
The Battery Indicator illuminates to indicate the UPS is operating on battery (green) or to signify a battery warning (amber).
Fault Indicator (Red/Green)
The Fault Indicator illuminates when the UPS detects a problem: red for an internal UPS fault, green for overload and over-temperature conditions.
Location and Status of Indicators
Utility Indicator
Green: Normal operation
Fault Indicator
Green: Overload/Over tempera ture Red: UPS fault
NOTE
See Troubleshooting section for details.
Battery Indicator
Green: On battery Amber: Battery warning
12
Page 17
Transfer Voltage Selectors (DIP Switches)
The two-position DIP switch control on the rear panel, as shown below, allows the operator to select the utility transfer voltage at which the UPS will switch to battery power.
Rear of UPS
DIP Switches
185-270V 185-280V
175-270V
175-280V
Refer to user's manual for voltage setting
The factory default settings are 185VAC - 270VAC. DIP switch posi­tions for each voltage setting are as follows:
DIP switch settings
Left Right Setting
Up Up 185 - 270VAC (default) Up Down 185 - 280VAC Down Up 175 - 270VAC Down Down 175 - 280VAC
CAUTION
!
Never change the voltage settings while the UPS is ON and powering connected loads. Change DIP switches only when the UPS is OFF.
CAUTION
!
To ensure protection of the connected equipment, the DIP switch settings should match the nominal utility input voltage. DIP switch settings not matching the nominal utility could potentially damage connected equipment.
13
Page 18
MODES OF OPERATION
Normal Mode
During Normal mode operation, the PowerSure PSP supplies condi­tioned, computer-grade power to the connected equipment: utility power passes through the EMI/RFI filters and TVSS circuitry and then through the Transfer Switch to the connected equipment.
When the UPS is in Normal mode, the Utility Indicator illuminates green.
Utility Indicator (Green)
The PowerSure PSP continuously monitors the batteries to maintain them in a fully charged state. The battery charger operates whenever AC power is present, even if the UPS is switched off. By default, the UPS is set to perform an automatic battery test after it has been oper­ating continuously for two (2) weeks. The interval at which the UPS performs a battery test can be configured via MultiLink.
14
Page 19
Battery Mode
The UPS switches to Battery mode in the event of an extreme voltage/ frequency condition or complete utility failure. The battery system supplies power through the Inverter to generate power for the con­nected equipment.
When the UPS is in Battery mode, the Battery Indicator illuminates green and an alarm sounds every 10 seconds.
Battery Indicator (Green)
When a low battery condition occurs, the Battery Indicator changes to flashing amber and the alarm sounds every half-second. Low battery warning is defaulted to two (2) minutes but can be configured via Mul­tiLink. For more information, refer to Troubleshooting section.
Battery Indicator (flashing Amber)
CAUTION
!
Turning off the UPS while in either Normal mode or Battery mode will result in the loss of output power.
NOTE
Once utility power is restored, the UPS resumes normal operation. At this time, the battery charger begins recharging the battery. The UPS is capable of OFF-State charging, i.e., with utility power, the UPS will charge the batteries as long as it is plugged in.
15
Page 20
COMMUNICATIONS
DB-9 Connector
The UPS has a DB-9 (9 pin female) connector on the rear to allow UPS status communications with a computer system running MultiLink™ software. The DB-9 is capable of supplying serial communication, on battery and low battery signals. MultiLink, Liebert’s UPS monitoring and shutdown software, is shipped with the UPS, along with a 3m(10­ft.) DB-9 cable required for running MultiLink.
When MultiLink is installed on the host computer, the UPS can signal “on battery” and “low battery” using opto-couplers. When the UPS is operating in Battery mode, it can receive a signal from the host com­puter system that will shut down the UPS (after gracefully shutting down the operating system on the host computer system) when the remaining battery run time is low. The timing of the signal depends on MultiLink’s configuration settings. This shutdown signal (5-12VDC) must have a duration of at least 2 seconds for the UPS to be shut down. The UPS communicates via serial communications using Liebert ESP II protocol.
DB-9 Pin Assignment Description
1 Low Battery (open collector) 2 UPS TxD (typical RS-232 levels) 3 UPS RxD (typical RS-232 levels) 4 Battery Mode Shutdown (5-12VDC, 10-24 mA max) 5 Common 6 Any Mode Shutdown (short to Pin 5) 7 Low Battery (open emitter) 8 Utility Fail (open emitter) 9 Utility Fail (open collector)
DB-9 Pin Assignment Collector to Emitter*
Open
6789
54321
* Maximum voltage and current on Pins 1, 7, 8, and 9 is 55 VDC; 10.0 mA.
16
(+)
Collector
Open
(-)
Emitter
Page 21
Remote Shutdown Via the DB-9 Connector
The PowerSure PSP can be shut down remotely by shorting Pins 5 and 6 or via Pins 4 and 5 of the DB-9 connector.
Shutdown Via Pins 5 & 6
When Pin 6 is shorted to Pin 5, the UPS output is shut off regardless of what mode the UPS is operating in. The UPS cannot be started as long as the pins are shorted. When the short is removed, the UPS out­put can be enabled by pressing the ON/ OFF /Alarm Silence button.
Shutdown Via Pins 4 & 5
While the UPS is operating on battery (with no battery test in progress), a 5-12VDC signal for 2 seconds or longer is required to sig­nal a shutdown. Signals for less than 2 seconds are ignored.
After Pin 4 receives the shutdown signal, a 2-minute shutdown timer inside the UPS begins a countdown. The timer cannot be stopped. If utility power returns during the 2-minute timer countdown, the shut­down timer continues until the end of 2 minutes and then the UPS turns off. The UPS must remain off for at least 10 seconds.
By default, autorestart is enabled so the UPS will restart after 10 seconds. If autorestart is disabled via MultiLink software, the UPS remains off until a manual restart.
USB Interface Port
The PowerSure PSP has a USB interface port for communication that will work with built-in Microsoft Power Manager software on the user’s PC, if so equipped. It will provide UPS status and manages the automatic, orderly shutdown of the computer. The UPS (USB) commu­nications meets HID standard, version 1.11. All USB models are com­patible with Microsoft Windows 2000, Windows XP and Mac OS 10.2 or later. All USB models ship with a 1.8m (6-ft.) USB cable.
Microsoft, Windows, and the Windows logo are trademarks, or registered trademarks of Microsoft Corporation in the United States and/or other countries.
Data Line Protection Connectors
Data line (1 input & 1 output) connectors are located on the rear of the UPS and provide transient voltage surge suppression (TVSS) for Phone/Fax/DSL/Internet/Modem devices.
17
Page 22
MAINTENANCE
The PowerSure PSP UPS requires very little maintenance. Follow these practices to prevent problems.
Cleaning the UPS
The following will help ensure trouble-free operation for years:
• Vacuum dust from the ventilation intake occasionally.
• Wipe the cover periodically with a dry cloth.
Maintaining Batteries
The batteries are valve-regulated, nonspillable, lead acid and must be kept charged to retain their design life. The UPS continuously charges the batteries when connected to the utility supply, even while the UPS is switched off.
When storing the UPS, it is recommended to plug in the UPS for at least 24 hours every four to six months to ensure full recharge of the batteries.
Battery Replacement
CAUTION
!
A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed before replacing the batteries:
• Remove rings, watches, and other metal objects.
• Do not lay tools or other metal objects on top of the batter-
ies.
• If the battery replacement kit is damaged in any way or
shows signs of leakage, contact your local dealer or Liebert representative immediately.
• Do not dispose of batteries in a fire. The batteries may
explode.
• Dispose of old batteries according to local codes.
This UPS is equipped with internal “hot swappable” batteries that the user can replace without shutting down the UPS or connected loads.
NOTE
Caution should be exercised when replacing the batteries because the load is unprotected from disturbances and power outages during this procedure.
18
Page 23
Battery Replacement Procedure
Replacement requires removing the battery cover plate on the bottom of the UPS. No tools are needed.
To replace the batteries:
1. Remove the battery cover plate on the bottom of the UPS.
2. Pull the white tab towards you to remove the battery from the UPS. Pivot battery 90 degrees clockwise as shown below.
Bottom view of UPS
3. Disconnect the insulated connectors from the battery terminals.
Front view of UPS Front view of UPS
NOTE
There may be a small spark at the battery terminals when reconnecting the connectors. This is normal and will not harm you or the UPS.
5. Push the battery pack into the UPS.
Side view of UPS
4. Insert a new battery pack, and push the connectors onto the battery terminals (black to black & red to red).
6. Reattach the battery cover plate.
Front view of UPS Bottom view of UPS
19
Page 24
TROUBLESHOOTING
The information below indicates various symptoms a user may encounter in the event the PowerSure PSP experiences a problem. Use this information to determine whether external factors caused the problem. See Troubleshooting Chart for suggested remedy.
Utility Indicator
Fault Indicator
Battery Indicator
Guide to Status Indicators
Fault
Indicator
1. The Fault indicator illuminates, indicating the UPS detected a problem.
2. An alarm sounds, alerting that the UPS requires attention. The alarm can be silenced except for low battery, overload and over-temperature warning conditions.
3. Utility and/or Battery indicators may be illuminated as a diagnostic aid to the operator, as shown below:
Utility
Indicator
Battery
Indicator
Diagnosis/
Audible Alarm
— —— —— — ——
Green Flashing
Green Flashing
Green ON
Green ON
Green ON
Red Flashing
Red ON
Green ON
Green ON
Green ON
——
Green ON
——
Green ON
——
Normal operation with utility power present; no beep.
GreenONUPS is operating on battery;
GreenONBattery test has been
Amber Flashing
Amber Flashing
Green ON
beep every 10 seconds.
initiated; no beep. Battery needs to be replaced;
long beep every minute. Low battery warning; beep
every half-second. Overload warning, load is
>100%; beep every half­second.
Overload shutdown, load exceeds UPS capacity (110%); continuous beep.
Over temperature (overtemp) warning; beep every 5 seconds (Normal mode).
Over temperature (overtemp) warning; beep every 5 seconds (Battery mode).
Over temperature (overtemp) shutdown; long beep every 5 seconds.
UPS is on, fault warning; continuous beep.
UPS has failed & shut down; continuous beep.
20
Page 25
T roubleshooting Chart
If the UPS fails to operate properly, turn off the unit and repeat the steps in the Installation section of this manual. If the problem per­sists, refer to the chart below:
Problem Cause Solution
Check the circuit protector on the rear of the UPS. If it is tripped, reset it and restart the UPS. For further help, call your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Check for proper connection of battery or batteries.
Reset the circuit protector and restart the UPS.
Have the utility checked by a qualified electrician.
Wait until the voltage rises to an appropriate level or have the utility checked by a qualified electrician.
Wait until voltage lowers to an appropriate level or have the utility checked by a qualified electrician.
Check the circuit protector on the rear of the UPS. If it is tripped, reset it and restart the UPS. If the problem persists, disconnect some of the equipment from your UPS—the total wattage of your equipment must not exceed the capacity of the UPS. For further help, call your local dealer, Liebert representative or the Liebert Worldwide Support Group.
Make sure that the UPS is operating in 0°C to 40°C (32°F to 104°F) and that it has adequate ventilation.
Consult the MultiLink user manual or contact your LAN administrator.
Recharge battery.
Replace battery.
UPS will not start
UPS starts on battery, but will not switch to AC
UPS shuts down, Fault Indicator lit
UPS not providing expected backup time
Overload/Short Circuit
Battery disconnected or is completely discharged
UPS not plugged in Plug in the power cord securely. Circuit protector
tripped Power not available
at utility receptacle Input voltage
below threshold
AC overvoltage
Overload/Short Circuit
Internal UPS fault
High temp shutdown
MultiLink shutdown Overload Reduce load.
Battery not charged due to a recent outage
Battery needs to be replaced
21
Page 26
SPECIFICATIONS
Model Number Power Rating VA/W DIMENSIONS: mm (in.)
Unit W x D x H
Shipping W x D x H
WEIGHT: kg (lbs)
Unit 4.6 (10.2) 4.6 (10.2) Shipping 5.7 (12.6) 5.7 (12.6)
INPUT AC PARAMETERS
Surge Protection 220J Rated Input Voltage 230VAC Voltage Range Without
Battery Operation Frequency Range 46.5 - 63.5 Hz (±0.1 Hz)
OUTPUT AC PARAMETERS
Output Receptacles
Voltage (Battery mode) 230VAC ±8% Waveform (Battery mode) Stepped Sinewave Frequency 50 Hz or 60 Hz; auto sensing Overload Warning
(Normal & Battery modes) Overload Shutdown >110%
BATTERY PARAMETERS
Type Valve-regulated, nonspillable, lead acid QuantityxVoltagexRating 1x12Vx7Ah 1x12Vx9Ah Transfer Time 4 - 6 ms typical Backup Time: At 25°C (77°F), resistive loading, with fully charged batteries
Full Load 4 minutes 5 minutes Half Load 17 minutes 14 minutes
Recharge Time
ENVIRONMENTAL
Operating Temperature Storage Temperature
Relative Humidity 0% to 95%, non-condensing Operating Elevation Up to 3000m (10,000 ft.) at 30°C (86°F) without derating Audible Noise < 40 dBA, at 1 meter
PSP500MT-230 PSP650MT-230
500VA/300W 650VA/390W
95 x 240 x 205
(3.7 x 9.5 x 8)
171 x 332 x 293
(6.7 x 13.1 x 11.5)
175VAC - 280VAC, DIP switch selectable
(see DIP switch settings on page 13)
(4) IEC-320-C13 (orange)
Battery backup + surge protection
(2) IEC-320-C13 (black)
Surge protection
>100%
6 hours to 90% of rated capacity,
after full discharge into resistive load
0°C to +40°C
(+32°F to + 104°F)
-15°C to +40°C
(+5°F to +104°F)
95 x 240 x 205
(3.7 x 9.5 x 8)
171 x 332 x 293
(6.7 x 13.1 x 11.5)
22
Page 27
AGENCY
Safety EN 50091-1; CE low voltage directive; TUV Certificate Surge EN61000-4-5, Level 3, Criteria A ESD EN61000-4-2, Level 3, Criteria A Susceptibility EN61000-4-3, Level 3, Criteria A Electrical Fast
Transient/Burst Emissions EN 50091-2, Class B; CE EMC directive Conducted Immunity EN61000-4-6, Level 3, Criteria A Harmonics EN61000-3-2 Flicker EN61000-3-3 Transportation ISTA Procedure 1A
EN61000-4-4, Level 4, Criteria A
Battery Run Times
Load % 500VA 650VA
5 156 192 10 113 95 20 49 42 30 31 30 40 22 21 50 17 14 60 11 13 70 9 10 80 7 7 90 5 6
100 4 5
NOTE
Approximate discharge times are in minutes and at 25°C (77°F) with a resistive load.
23
Page 28
24
Page 29
1.38" (35 mm)
Rear
of UPS
3.49" (88.6 mm)
Bottom of UPS
5.12" (130 mm)
PowerSure PSP Mounting Template
1. Remove this template from the user manual.
2. Line template up to wall at desired location.
SIDE VIEW OF POWERSURE PSP
(Distance from head of screw to wall should be 0.25" or 6.4mm.)
3. Drill holes where cross hairs are located on template.
4. Remove template and mount screws, using (3) #8 or M4 screws.
5. Mount PowerSure PSP to wall.
Page 30
Page 31
Page 32
POWER AVAILABILITY
PowerSure™ PSP
USER MANUAL
The Company Behind the Pro duct s
With over a million installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics:
Environmental systems—close-control air conditioning from 1 to 60 tons
Power conditioning and UPS with power ranges from 300 VA to more than 1000 kVA
Integrated systems that provide both environmental and power protection in a single, flexible package
Monitoring and control—from systems of any size or location, on-site or remote
Service and support through more than 100 service centers around the world and a 24/7 Customer Response Center
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2003 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SLI-23280 (6/03) Rev. 0
Technical Support/Service
Web Site
www.liebert.com
Monitoring
monitoring@liebert.com
Outside the US: 614-841-6755
Outside the US: 614-841-6755
powertech@liebert.com
Environmental Systems
Outside the United States
800-222-5877
Single-Phase UPS
800-222-5877
upstech@liebert.com
Three-Phase UPS
800-543-2378
800-543-2778
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
+39 049 9719 111
Fax: +39 049 5841 257
23F, Allied Kajima Bldg.
138 Gloucester Road
+852 2 572 2201
Fax: +852 2 831 0114
Italy
Asia
Wanchai
Hong Kong
Loading...