Process Fluid Chiller
Keeping Business in Business
Designed for Marconi Medical MX8000
• Dedicated, equipment-matched cooling supplies the proper temperature and water flow year round.
• Factory-tested, piped, wired and charged for hassle-free startup and operation.
• Clean, non-ferrous cooling loop, required for sensitive medical equipment.
• Local service and parts for quick and knowledgeable maintenance and service.
• Optional switch-over to alternate water source provides redundant, continuous operation.
• Optional remote monitoring systems keep you informed of chiller operation.
• ETL/CSA certified.
• ISO 9001 certified company.
MX8000 Specifications
Fluid Specified Water or Glycol
Max Heat Dissipation—BTUH (kW) 32,400 (9.5)
Fluid Temperature Range—°F (°C) 36-57 (2-14)
Temperature Gradient 0.5°C/min
Fluid Flow Rate—GPM (l/m) 4.4 (16.7)
Fluid Pressure Drop—PSI (kPa) 2.2 (15)
Process Fluid Chiller Specifications
Model Number PS048A PS048A PS048A
Fluid Circulated Water Ethylene Glycol Propylene Glycol
Net Cooling Capacity—BTUH (kW) 41,200 (12.1) 38,300 (11.2) 36,500 (10.7)
Leaving Fluid Temperature—°F (°C) 48 (8.9) 48 (8.9) 48 (8.9)
Fluid Flow Rate—GPM (l/m) 8 (30.4) 8 (30.4) 8 (30.4)
MX8000 Pressure Drop—PSI (kPa) 2.2 (15.2) 2.2 (15.2) 2.2 (15.2)
Chiller Pressure Drop—PSI (kPa) 8.2 (56.5) 11.1 (76.5) 13.1 (90.3)
Pump Total Head—PSI (kPa) 46.8 (322.7) 46.8 (322.7) 46.8 (322.7)
Head Available for Piping Circuit—PSI (kPa) 36.4 (251) 33.5 (231) 31.5 (217.2)
Pump HP (kW) 1 (0.75) 1 (0.75) 1 (0.75)
Process Fluid Chiller Designed for Marconi Medical MX8000 1
C
B
A
C
C
C
Model No.
A - Width
Inches (mm)
B - Height
Inches (mm)
C - Depth
Inches (mm)
PS048A 53 (4684) 63 (1600)* 36 (918) 532 (241)
* Includes added dimensions for thermal storage tank.
Standard Features
• Indoor/outdoor cabinet
• Scroll compressor
• Refrigerant dehydrator
• Expansion valve
• Refrigerant receiver
• Stainless steel expansion tank
• Pressure relief valve
• Hot gas bypass valve capacity control
• Stainless steel pump
Optional Features
• Refrigerant gauges and expansion tank heater
Optional Ship-Loose Accessories
• Alternate water source (AWS) module
• Enviro-source emergency bypass
•Fluid pressure gauge
•Check valve
• Dial thermometer
• Relief valve
• Circuit setter
• Ball valve
• High temperature thermostat
• Low flow switch
• Liebert RCM4 remote alarm monitor
Required Special Options
• SFA#7055-6, 50 gallon internal storage tank
Weight
Lbs. (kg)
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Phone: 800.877.9222
Fax: 614.841.6022
Liebert Web Site—http:www.liebert.com
SL-16559 (07/00)
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco
Italy
Phone: 39.049.9719.111
Fax: 39.049.5841257
23/F Allied Kajima Bldg.
138 Gloucester Road
Wanchai
Hong Kong
Phone: 852.2.572.2201
Fax: 852.2.572.1182
©2000 Liebert Corporation. All rights
reserved throughout the world.
Specifications subject to change without
notice.
®Liebert and the Liebert logo are
registered trademarks of Liebert
Corporation. All names referred to are
trademarks or regisered trademarks of
their respective owners.