Liebert PS036A User Manual

Indoor/Outdoor Process Fluid Chiller
Keeping Business in Business
Designed for Siemens Magnetom Impact
• Dedicated, equipment-matched cooling supplies the proper temperature and water flow year round.
• Factory-tested, piped, wired and charged for hassle-free startup and operation.
• Clean, non-ferrous cooling loop, required for sensitive medical equipment.
• Local service and parts for quick and knowledgeable maintenance and service.
• Optional remote monitoring systems keep you informed of chiller operation.
• ETL/CSA certified.
• ISO 9001 certified company.
Magnetom Impact Specifications
Fluid Specified Water/ Glycol
Max Heat Dissipation—BTUH (kW) 27,325 (8)
Fluid Temperature Range °F (°C) 45-65 (7-18)
Temperature Gradient N/A
Fluid Flow Rate—GPM (l/m) 1.3 (4.9)
Fluid Pressure Drop—PSI (kPa) 7 (48.3)
Process Fluid Chiller Specifications
Model Number PS036A PS036A PS036A
Fluid Circulated Water Ethylene Glycol Propylene Glycol
Net Cooling Capacity—BTUH (kW) 27,800 (8.1) 27,900 (8.2) 27,400 (8.0)
Leaving Fluid Temperature—°F (°C) 47 (8.3) 53 (11.7) 56 (13.3)
Fluid Flow Rate—GPM (l/m) 1.3 (4.9) 1.5 (5.7) 1.6 (6.1)
Magnetom Impact Pressure Drop—PSI (kPa) 7 (48.3) 13.5 (93.1) 16.7 (115.1)
Chiller Pressure Drop—PSI (kPa) 1.5 (10.3) 2.2 (15.2) 2.6 (17.9)
Pump Total Head—PSI (kPa) 41.0 (283) 41.0 (283) 41.0 (283)
Pump—HP (kW) 3/4 (0.6) 3/4 (0.6) 3/4 (0.6)
Indoor/ Outdoor Process Fluid Chiller Designed for Siemens Magnetom Impact 1
OPTIONAL REFRIGERANT PRESSURE GAUGES
SHADED AREAS
INDICATE A
RECOMMENDED CLEARA NCE
FOR COMPONENT REMOVAL,
ACCESS, AND AIR FL OW.
I
H
1" NPT
AIRFLOW
1" MAX.
(25mm)
A
1" MAX.
(25mm)
D
36"
(914mm)
UNIT DIMENSIONAL DATA
IN
C*
2"
18"
(51mm)
(457mm)
I
H
UNIT DIMENSIONAL DATA
3/4" NPT
36"
(914mm)
B
AIRFLOW
OUT
SHADED AREAS
INDICATE A
RECOMMENDED CLEARA NCE
FOR COMPONENT REMOVAL,
ACCESS, AND AIR FL OW.
36"
(914mm)
Model No.
A-Depth in. (mm)
B-Width in. (mm)
C-Height
in. (mm)
Weight
lbs. (kg)
Voltage
(60 Hz)
PS036A 36 (914) 48 (1219) 32.5 (825) 515 (233) 460, 3-phase
208/230, 1- or 3-phase
Standard Features
• Indoor/outdoor cabinet
• Hermetic compressor
• Refrigerant dehydrator
• Expansion valve
• Refrigerant receiver
• Stainless steel expansion tank
• Pressure relief valve
• Hot gas bypass valve capacity control
• Stainless steel pump
Optional Features
Accessories
• Enviro-source emergency bypass
•Fluid pressure gauge
•Check valve
• Dial thermometer
• Relief valve
• Circuit setter
• Ball valve
• High temperature thermostat
• Low flow switch
• Liebert RCM4 remote alarm monitor
• Refrigerant gauges and expansion tank heater
Voltage
(50 Hz)
400, 3-phase
200/230, 1- or 3-phase
1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Phone: 800.877.9222 Fax: 614.841.6022
Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco Italy Phone: 39.049.9719.111 Fax: 39.049.5841257
Liebert Web Site—http:www.liebert.com
SL-16562 (07/00)
23/F Allied Kajima Bldg. 138 Gloucester Road Wanchai Hong Kong Phone: 852.2.572.2201 Fax: 852.2.572.1182
©2000 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice. ®Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or regisered trademarks of their respective owners.
Indoor/ Outdoor Process Fluid Chiller Designed for Siemens Magnetom Impact 2
Loading...