Liebert PS036A User Manual

Indoor/Outdoor Process Chiller
Designed for GE Signa or 1.5T Excite
• Dedicated, equipment-matched cooling supplies the proper temperature and water flow year round.
• Factory-tested, piped, wired, and charged for hassle-free start-up and operation.
• Clean, non-ferrous cooling loop, required for sensitive medical equipment.
• Local service and parts for quick and knowledgeable maintenance and service.
• Optional switch-over to alternate water source provides redundant continuous operation.
• Standard product ETL/CSA certified.
• ISO 9000 certified company.
Signa Horizon & CV Specifications
Fluid Specified Water/Glycol
Max Heat Dissipation - BTUH (kW) 28,320 (8.3)
Fluid Temperature Range, °F (°C) 40-82 (4-28)
Temperature Gradient N/A
Fluid Flow Rate - GPM (l/m) 2.1 (8.0)
Fluid Pressure Drop - PSI (kPa) 36.0 (248)
Liebert Process Chiller Specifications
Model Number PS036A PS036A PS036A
Fluid Circulated Water Ethylene Glycol Propylene Glycol
Net Cooling Capacity - BTUH (kW) 29,500 (8.6) 29,600 (8.7) 28,800 (8.4)
Leaving Fluid Temperature ° F (° C) 50 (10) 53 (11.7) 56 (13.3)
Fluid Flow Rate - GPM (l/m) 5.3 (20.1) 5.3 (20.1) 5.3 (20.1)
Signa Horizon & CV Pressure Drop - PSI (kPa) 36.0 (248) 48 (331) 55.1 (380)
Chiller Pressure Drop - PSI (kPa) 5.1 (35.2) 6.8 (46.9) 7.8 (53.8)
Pump Total Head - PSI (kPa) 64.9 (448) 64.9 (448) 64.9 (448)
Pump HP (kW) 3 (2.2) 3 (2.2) 3 (2.2)
Indoor/Outdoor Process Chiller Designed for GE Signa or 1.5T Excite 1
A-Width
Model No.
PS036A 36 (914) 48 (1219) 32.5 (825) 515 (233) 460, 3-phase
Inches (mm)
B-Height
Inches (mm)
C-Depth
Inches (mm)
Weight
Lbs. (kg)
Voltage
(60 Hz)
208/230, 1- or 3-phase
Voltage
(50 Hz)
400, 3-phase
200/230, 1- or 3-phase

Standard Features

• Indoor/outdoor cabinet
• Hermetic compressor
• Refrigerant dehydrator
• Expansion valve
• Refrigerant receiver
• Stainless steel expansion tank
• Pressure relief valve
• Hot gas bypass capacity control valve
• Stainless steel pump

Optional Features

• Refrigerant gauges and expansion tank heater

Required Options

• 3 HP pump, SFA #E6569-06
• Bypass leg from supply to return with circuit setter on supply line and ball valve on bypass line, SFA #E6483-1

Optional Ship-Loose Accessories

• Emergency Water Switchover (EWS) module
• Enviro-source emergency bypass
• Fluid pressure gauge
•Check valve
• Dial thermometer
• Relief valve
• Circuit setter
• Ball valve
• High temperature thermostat
• Low flow switch
• Liebert RCM4 remote alarm monitor
1050 Dearborn Drive P.O. Box 29186 Columbus, OH 43229 Phone: 800.877.9222 Fax: 614.841.6022
Liebert Web Site—http://www.liebert.com
SL-16558 (2/04)
Indoor/Outdoor Process Chiller Designed for GE Signa or 1.5T Excite 2
Via Leonardo Da Vinci 8 Zona Industriale Tognana 35028 Piove Di Sacco (PD) Italy Phone: +39 049 9719 111 Fax: +39 049 5841 257
23F, Allied Kajima Bldg. 138 Gloucester Road Wanchai Hong Kong Phone: +852 2 572 2201 Fax: +852 2 831 0114
©2004 Liebert Corporation. All rights reserved throughout the world. Specifications subject to change without notice. ®Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or regisered trademarks of their respective owners.
Loading...