WARNING: Do not attempt to service this product yourself except to
replace the battery. Opening or removing the cover may expose you to
dangerous voltages, even when the AC cord is disconnected from the
R
electrical outlet. Refer all servicing to qualified service personnel.
1. SAVE THESE INSTRUCTIONS. THIS MANUAL CONTAINSIMPORTANT SAFETY INSTRUCTIONS. Read all safety and operating
instructions before operating the Uninterruptible Power System (UPS).
Adhere to all warnings on the unit and in this manual. Follow all
operating and user instructions.
2. This product is designed for Commercial/Industrial use only. It is not
intended for use with life support and other designated “critical” devices.
Maximum load must not exceed that shown on the UPS rating label. If
uncertain, consult your dealer. See Limited Warranty.
3. When replacing the batteries, use the appropriate Liebert-Approved
Replacement Battery Kit. Proper disposal of batteries is required. Refer
to your local laws and regulations for disposal requirements.
4. Always turn off the UPS and unplug it before starting the battery
replacement procedure. To replace batteries, refer to the battery
replacement procedure. If you feel unqualified to replace the batteries,
do not open the battery door. Refer all servicing to qualified service
personnel.
5. CAUTION: Do not open or mutilate the batteries. Released electrolyte is
harmful to skin and eyes and may be toxic.
6. The mains supply socket or means of isolation must be within 2 metres
of the equipment and accessible to the operator. The UPS is designed
for data processing equipment.
7. The UPS comes with two output power leads with moulded connectors.
Do not modify the output power leads. Consult dealer if connector does
not match the load socket. UPS must be earthed at all times while in
use. Turn UPS off before unplugging it, or the safety earth will be
removed.
8. The PowerSure Interactive models 700 VA, 1000 VA, and 1400 VA are
not supplied with an input power lead for connection to the mains supply
socket. Use the input mains supply power lead from your data
processing equipment to connect the UPS to the mains supply. For the
2200 VA model, use the supplied 16 ampere rated input mains supply
leads. For UK supply systems, consult a qualified electrician to connect
the lead supplied for the 2200 VA model to the mains supply. Note
caution on following page.
2
CAUTION: The UPS and connected load total earth leakage current
must not exceed 3.5 milliamperes. If the connected load earth leakage
current is likely to exceed 2.5 milliamperes or you are unsure, then
convert the input lead attachment to either a fixed wiring installation or an
industrial plug/socket (e.g. CEE 17 connector). This task should be
carried out by a competent electrical engineer who is conversant with
local electrical codes/regulations.
9. The UPS output supply sockets may be electrically live whenever the
input power lead is plugged into the mains supply socket. Turning the
UPS OFF does not electrically isolate the internal parts. To isolate the
UPS, turn the UPS OFF then isolate it from the mains supply.
10. When installing the UPS or making input and output connections, comply
with relevant safety standards (e.g. IEC950, VDE0805, EN50091-1).
11. This equipment complies with the requirements of the EMC Directive
89/336/EEC and the published technical standards. Continued
compliance requires installation in accordance with these instructions
and the use of manufacturer approved accessories with output cables
not exceeding 10 metres (30 ft.) in length. Use a shielded cable for the
external communications interface.
12. Operate UPS only from a properly earthed, 50 Hz or 60 Hz, 220-240
VAC mains supply. Models are available for 100-127 VAC supply
voltages.
13. Route power supply leads so they are not walked on or pinched.
14. Never block or insert any object into the ventilation holes or other
openings. Maintain a minimum clearance of 100 mm (4 inches) all
around the UPS for proper air flow and cooling.
15. Operate the UPS in an indoor environment only, with an ambient
temperature range of 0° C to +40° C (32° F to +104° F). Install it in a
clean environment, free from moisture, flammable liquids, gasses, or
corrosive substances.
16. Storing magnetic media on top of the UPS may result in data loss or
corruption.
17. Turn the UPS off and unplug the UPS before cleaning. Use only a soft
cloth, never liquid or aerosol cleaners.
18. This equipment can be operated by individuals without previous training.
INTRODUCTION & SYSTEM DESCRIPTION
Congratulations on your choice of the Liebert PowerSure™ Interactive Uninterruptible
Power System (UPS). It provides conditioned power to microcomputers and other
sensitive electronic equipment.
Upon generation, AC power is clean and stable. However, during transmission it may
be subject to voltage sags, spikes, or complete power failure which may interrupt
computer operations, cause data loss, or even damage equipment. The
PowerSure™ Interactive protects equipment from these disturbances.
The PowerSure™ Interactive comes in nominal power ratings of 700, 1000, 1400, or
2200 VA. Complete specifications appear near the end of this section.
The PowerSure™ Interactive is a compact, “line interactive” UPS. A “line interactive”
UPS continuously conditions and regulates its output voltage, whether the mains
power is present or not. It supplies connected equipment with clean sinewave power,
to simulate as much as possible, the power generated by the mains. Sensitive
electronic equipment operates best from sinewave power.
For ease of use, the PowerSure™ Interactive contains a light emitting diode (LED)
bar display to indicate either “load percentage” or “battery capacity” depending upon
the mode of operation. It also provides self diagnostics, a combination alarm
silence/battery test button, and two levels of alarms when the unit is operating on
battery.
The PowerSure™ Interactive has an interface port for communications between the
UPS and a LAN server or other computer system. This port provides detailed
operating information including voltages, currents, and alarm status to the host
system when used in conjunction with Liebert SiteNet® software. SiteNet® software
can also remotely control UPS operation.
GLOSSARY OF SYMBOLS
Indicates AC Input
Indicates AC Output
Indicates Caution: Note the accompanying instruction
Indicates the position of a fuse
Requests the user to consult the manual for additional information
Indicates that the unit contains a valve regulated lead acid battery
4 3
INPUT
OUTPUT
B
CCD
MAJOR COMPONENTS
TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS
These UPS components provide surge protection and filter electromagnetic
interference (EMI) and radio frequency interference (RFI). They minimize any surges
or interference present in the mains line and keep the sensitive equipment protected.
AUTOMATIC VOLTAGE REGULATOR
In normal operation, the automatic voltage regulator (AVR) passes mains AC power
to the connected load. When mains power voltage is outside acceptable limits, the
AVR activates. It raises undervoltage power and lowers overvoltage power. This
keeps the UPS output voltage within the connected equipment’s tolerances and
allows wide mains voltage fluctuations without utilizing battery power.
BI-DIRECTIONAL CONVERTER
In normal operation, the bi-directional converter “converts” mains AC power into
regulated DC power to “float” charge the battery system. Upon a mains power failure,
the bi-directional converter receives its required energy from the battery and “inverts”
it into precise, regulated sinewave AC power. Charging takes place whenever the
UPS is plugged into the wall outlet and mains power is within acceptable limits.
BATTERY
The PowerSure™ Interactive utilizes valve regulated, nonspillable, lead acid
batteries. At typical room temperatures and with the UPS float charging, the battery
system will last many years. For battery run times, refer to the Typical Battery
Discharge Curves.
L
N
TVSS
and
EMI/RFI Filters
Battery
G
Automatic
Voltage
Regulator
Bi-Directional
Converter
L
N
G
MINI-TOWER INSTALLATION
1. Unpack the UPS carefully noting the packing method. Retain the box and
packing material for possible future shipment.
CAUTION: The UPS is heavy (see specifications). Take proper precautions
when lifting or moving it.
2. Visually inspect the UPS for freight damage. Report damage to the carrier and
your dealer.
3. Locate the UPS where it cannot be accidentally disconnected. Locate it in an
area with unrestricted air flow, away from water, flammable liquids, gases, or
corrosives. Maintain a minimum of 100 mm (4 inches) clearance around the
UPS. Maintain an ambient temperature range of 0° to 40° C (32° to 104° F).
NOTE: UPS operation in temperatures above 25° C (77° F) reduces battery life.
4. Shutdown load equipment, turn off mains supply, and unplug load equipment's
power input cable (A) from mains supply socket.
5. 700-1400 VA models: unplug power input cable (A) from load equipment input
socket (D) and plug it into UPS input socket (C). Re-plug the power input cable
(A) into mains supply socket. Proceed with step 9.
2200 VA models: an input cable is not supplied. Proceed with the next step
after obtaining a proper cable with an IEC 320-16 receptacle.
6. Connect the molded connector of the mains AC input supply cable into the UPS.
7. Fit the supplied retainer bracket around the input supply cable and secure the
bracket to the rear of the UPS using the two supplied screws. (See figure on
next page).
8. The free end of the input
supply cable should be
connected to the electrical
supply distribution system in
accordance with local rules
and conditions.
NOTE: The UPS On / Alarm
Silence and Manual Battery
Test buttons do not
electrically isolate the
internal parts. To isolate
the UPS, provide an isolator
that is accessible to the
operator and located within
two meters of the UPS.
B
A
A
DE
E
6 5
The wires in the mains lead are colored with the following code:
Green and Yellow = Earth
Blue = Neutral
Brown = Live
As the color of the wires in the mains lead may not correspond with the colored
marking identifying the terminals in the plug, proceed as follows:
The green and yellow wire must be connected to the terminal in the plug which is
marked with the letter “E” or by the earth symbol, or colored green and yellow.
The blue wire must be connected to the terminal which is marked with the letter
“N” or colored black.
The brown wire must be connected to the terminal which is marked with the letter
“L” or colored red.
9. Connect the supplied IEC320-10 output cable (B) between the load equipment
input socket (D) and one of the UPS AC output sockets (E). Connect all load
equipment to the UPS in this way.
10. Turn on the UPS by pressing the On button for at least one half second; then turn
on the connected load equipment. The UPS is ready for normal operation.
7 8
RACKMOUNT INSTALLATION
1. Unpack the UPS carefully noting the packing method. Retain box and packing
material for possible future shipment.
CAUTION: The UPS is heavy (see specifications). Take the proper precautions
when lifting or moving the UPS.
2. Visually inspect the UPS for freight damage. Report any damage to the carrier
and your dealer.
3. Locate the UPS indoors where it cannot be accidentally disconnected. Locate it
in an area with unrestricted air flow, away from water, flammable liquids, gases,
or corrosives. Maintain a minimum of 100 mm (4 inches) clearance around the
UPS. Maintain an ambient temperature range of 0° to 40° C (32° to 104° F).NOTE: UPS operation in temperatures above 77° F (25° C) reduces battery life.
4. Gently lay UPS on its bottom side so that the front bezel is facing you.
5. The Rackmount UPS must be supported by a shelf or rails. The front bezel will
not support the weight of the UPS.
CAUTION: To Increase the stability of the rack enclosure, place the UPS in the
lowest possible rack position).
6. Refer to the Installation instructions supplied with the Rack Slide or Shelf Kits to
complete the installation procedures.
7. 700-1400 VA models: unplug power input cable (A) from load equipment input
socket (D) and plug it into UPS input socket (C). Re-plug the power input cable
(A) into mains supply socket. Proceed with step 13.
2200 VA models: an input cable is not supplied. Proceed with the next step
after obtaining a proper cable with an IEC 320-16 receptacle.
8. Connect the molded connector of the mains AC input supply cable into the UPS.
9. Fit the supplied retainer bracket around the input supply cable and secure the
bracket to the rear of the UPS using the two supplied screws (see figure on next
page).
10. Ensuring load equipment is turned off, plug all loads into the UPS output
receptacles.
11. The free end of the input supply cable should be connected to the electrical
supply distribution system in accordance with local rules and conditions.
NOTE: The UPS On/Alarm Silence and Manual Battery Test buttons do not
electrically isolate the internal parts. To isolate the UPS, provide an isolator that
is accessible to the operator and located within two meters of the UPS.
12. The wires in the mains lead are colored with the following code:
Green and Yellow = Earth
Blue = Neutral
Brown = Live
As the color of the wires in the mains lead may not correspond with the colored
marking identifying the terminals in the plug, proceed as follows:
The green and yellow wire must be connected to the terminal in the plug which is
marked with the letter “E” or by the earth symbol, or colored green and yellow.
The blue wire must be connected to the terminal which is marked with the letter
“N” or colored black.
The brown wire must be connected to the terminal which is marked with the letter
“L” or colored red.
13. Connect the supplied IEC 320-10 output cable (B) between the load equipment
input socket (D) and one of the UPS AC output sockets (E). Connect all load
equipment to the UPS in this way.
14. Turn on the UPS, by pressing the On/Off button, then turn on the connected load
equipment. The UPS is ready for normal operation.
CONTROLS AND INDICATORS
On/Off Button
The On/Off button controls output power to connected load(s).
CAUTION: Pressing the On/Off button when AC mains is not present will cause the
UPS to begin operating from battery. This should not be performed unless the UPS
input is connected to a properly earthed socket.
Load/Battery Level Indicators (ALL GREEN)
The Load/Battery Level Indicators have dual functions. During normal mode
operation, LED indicators display electrical load placed upon the UPS; and during
battery mode operation, LED indicators display battery capacity remaining. Each
LED designates a 25% load or battery capacity increment. All four LED indicators
illuminate at full load/battery capacity. If the UPS becomes loaded beyond full rating,
the top LED indicator will flash continuously while an alarm sounds.
Mains/Battery Status Indicator (GREEN)
An illuminated LED indicates the power button is on and mains power is available. A
flashing LED along with an alarm signifies mains voltage is out of specification and
UPS is operating in battery mode.
Mains High/Low Indicator (AMBER)
An illuminated LED indicates the UPS is correcting mains power, due to a mains
overvoltage or undervoltage condition.
Fault Indicator (GREEN)
The Fault indicator is the second uppermost LED (contained in load/battery level
indicators). A flashing LED indicates the UPS has detected a problem. An alarm
sounds to alert that the UPS requires attention. Refer to Troubleshooting Guide.
Alarm Silence/Battery Test Button
The Alarm Silence/Battery Test button serves a dual purpose. During normal mode
operation, press button for at least one half second to test capacity of the battery
system. The UPS will operate in battery mode for approximately 15 seconds. The
illuminated LED indicators in Load/Battery Level determine battery mode capacity in
25% increments.
During battery mode operation or active alarm condition, this button functions as the
alarm silence feature. Pressing this button for at least one half second will silence the
alarm. After the alarm is silenced, the PowerSure™ Interactive will reactivate the
alarm system to alert of additional problems. The low battery alarm is the single
alarm that cannot be silenced.
During a Battery Test, if the top two LEDs do not illuminate allow the UPS to
recharge the batteries for 24 hours. After 24 hours, retest the batteries. If the
batteries have been retested and the top two LEDs still do not illuminate, contact your
dealer or Liebert Technical Support (LTS) for a battery replacement kit.
9 10
Loading...
+ 9 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.