Liebert® propeller fan condensing units are available in a range of sizes and configurations to offer
flexibility in designing a precision environmental control system. The appropriate propeller fan
condensing unit paired with a corresponding Liebert fan coil evaporator model such as Liebert
DataMate
environmental control application requirements.
Split system condensing units are connected to the evaporator unit by two refrigerant lines (four in
8-ton systems) and a low-voltage control cable. The condensing unit requires a separate power source
and power disconnect switch.
1.1.1Base System 95°F (35°C) Ambient Models
The heart of the refrigeration system is a quiet, high efficiency scroll compressor with internal
vibration isolation mountings, pressure safety controls and built-in overload protection. Standard
features include crankcase heater, high-pressure switch, condenser coil, sight glass, filter drier, hot
gas bypass system with liquid quenching valve, direct drive propeller fan and motor, and Liebert
Lee-Temp
the appropriate evaporator section up to 95°F (35°C) outside ambient temperature.
1.1.2105°F (41°C) Ambient Models
These models contain similar components to the base models except the coils and fans are sized to
provide catalog capacity of the appropriate evaporator section up to 105°F (41°C) outside ambient
temperature.
™
, Liebert Mini-Mate2™ or Liebert Challenger 3000™ is an effective solution for your
™
flood-back head pressure control. These models are designed to provide catalog capacity of
Product Description
1.1.3Liebert Quiet-Line™ Models
These models contain similar components to the base models except the coils and fans are sized to
provide catalog capacity of the appropriate evaporator section up to 95°F (35°C) outside ambient
temperature with a noise level of less than 58 dBA.
1.2Optional Equipment
1.2.1Coated Coil
This option provides a phenolic coating for the condenser coil (extended lead time is required for this
option; consult factory).
Pre-Charged Refrigeration Line Sets
For efficient condenser/evaporator connection, factory pre-charged line sets with quick connect
fittings are available in 15-ft. and 30-ft. (4.5m and 9m) lengths. Each set includes an insulated copper
suction line and copper liquid line, both charged with R-407C refrigerant and sealed. Line sets are
only available for 1 to 3.5 Ton Units.
1.2.2Refrigerant Line Sweat Adapter Kit
This kit includes the compatible fittings required (two for the insulated suction line and two for the
liquid line) when using field-supplied interconnecting refrigerant lines instead of the pre-charged line
sets.
1.2.3277V Step-Down Transformer
A 37.5A, 277V step-down transformer is available for 1-to 3-Ton 60Hz condensing units needing
277/1/60 input power. Apply this transformer to a 208/230/1/60 condensing unit. The transformer is
coated with epoxy and contained in an enclosed, non-ventilated electrical box with adaptable
mounting brackets.
1
2.0INSTALLATION
Read this entire installation section before starting installation. This section details dimensional,
electrical and piping information and specifications that affect the placement of the PFH unit in
relation the connected evaporator unit, other outside units, barriers and walls.
Be particularly mindful of service and airflow clearances and maximum equivalent piping distances
and in elevation differences between PFH and connected evaporator unit. Consult and confirm
applications with your Emerson Network Power representative when applications exceed any of these
specifications.
2.1Equipment Inspection
When the unit arrives, inspect all items for any visible or concealed damage. Report any damage to
the carrier immediately and file a damage claim; send a copy of the claim to Emerson Network Power
or your local Emerson sales representative.
If possible, maintain equipment and packaging until it is at the installation location.
2.2Location Considerations
To ensure an adequate air supply, locate all condensing units in a clean-air area, away from loose dirt
and debris that can clog the coil. Avoid ground-level sites with public access or areas that are exposed
to heavy snow accumulation. Locate unit to allow maximum security and maintenance accessibility.
Installation
Do not locate condensing units near steam, hot air or fume exhausts. Do locate units at least 18 in.
(457mm) from walls, obstructions or adjacent units. For multiple unit installations, space unit so that
the hot condenser exhaust air is not directed toward the condenser air inlet of an adjacent unit.
Install a solid base at least 2 in. (51mm) higher than the surrounding grade and 2 in. (51mm) larger
than condensing unit base dimensions and capable of supporting the condenser’s weight.
2
2.3Dimensional Data
Figure 1Dimensions, horizontal air discharge
Installation
Fan Rotation
CCW
(left side)
Left Air Intake
Shaded area
indicates a minimum
clearance of 18" (457mm)
for proper air flow
Table 1Cabinet and floor planning data, horizontal air discharge
60Hz50HzABC
PFH014A-L—
PFH027A-L—
PFH027A-H—
PFHZ27A-L—
PFH037A-LPFH036A-L
PFH042A-LPFH041A-L
PFH037A-HPFH036A-H
PFHZ37A-LPFHZ36A-L
PFH042A-HPFH041A-H
PFHZ42A-LPFHZ41A-L
PFH067A-LPFH066A-L
Source: DPN000130, Rev. 1
Removable (right) panel
for access to
A
refrigeration component
B
C
C
Removable panel for access
to high-voltage and low-voltage
connections and refrigeration
components
Model NumbersDimensional Data, in. (mm)
40 (1016)23-1/2 (597)18 (457)200 (91)PFH020A-L—
48 (1219)31 (787)18 (457)241 (109)
53 (1343)36-1/4 (918)18 (457)351 (159)
Right Air Discharge
Shaded area
indicates a minimum
clearance of 18" (457mm)
for proper air flow.
Shaded area
indicates a recommended
clearance of 24" (610mm)
for component access and
removal.
DPN000130
Rev. 1
Net Weight
lb. (kg)
3
Figure 2Dimensions, top air discharge
Guard Height
Fan Rotation
CW
Shaded area
indicates a minimum
clearance of 18" (457mm)
for proper air flow.
Shaded area
indicates a minimum
clearance of 18" (457mm)
for proper air flow
Shaded area
indicates a recommended
clearance of 24" (610mm)
for component access and
removal.
DPN000131
Rev. 0
Removable panel for access
to high-voltage and low-voltage
connections and refrigeration
components
To p A ir
Discharge
Right Air Intake
Left Air
Intake
4-23/32"
(120mm)
36-1/8"
(918mm)
25-3/32"
(637mm)
46-7/32"
(1174mm)
2"
(51mm)
2"
(51mm) typ.
2"
(51mm)
2"
(51mm)
53-3/16"
(1351mm)
4"
(102mm) typ.
32-1/8"
(816mm)
FOOTPRINT DIMENSIONS
1/2" Bolt-Down Holes
(6 places)
Installation
Table 2Electrical and piping connections, top air discharge