Liebert NX 1+1 User Manual

LIEBERT NX 1+1 SYSTEM
PRODUCT SPECIFICATION AND INSTALLATION SHEET
+

General

The Liebert NX UPS uses intelligent and reliable decentralized technology to achieve parallel opera­tion of two modules of the same rating.
The 1+1 system is used to:
• Increase serviceability and allow the execution of maintenance operations and reparations without affecting the ordinary operating conditions of the system (depending on the redundancy level).
CAUTION
!
An external maintenance cabinet is strongly recommended to maintain the power supply to load in case of complete maintenance.

Conditions for Parallel System

1. Each UPS module should have the same rating, the same firmware and hardware version.
2. Each UPS module must have the same bypass source.
3. The outputs of all UPS modules are connected altogether.
4. The main inputs can be from different sources, but the phase rotation sequence of main inputs, bypass inputs and outputs must be correct and the same.
5. The parallel logic cable and load sharing cable must be connected in a ring correctly (See Figure 2)

Features of Parallel System

1. The hardware and firmware for parallel UPS module operation is standard in the Liebert NX, and the configuration can be set up by changing the settings in configuration software.
2. It is easy to install the parallel cables in a ring, providing high reliability and redundancy. And the intelligent paralleling logic provides the user with maximum flexibility. For example, shutting down or starting up the UPS modules in the parallel system can be done in any sequence. If an overload transfer occurs, the whole system can recover automatically from bypass mode after the overload is cleared.
3. The total load of the parallel system can be queried from each module’s liquid crystal display screen.
4. Optional monitoring background software can treat the entire parallel system as a big single-module UPS, and provide corresponding management. It can also get the information for all modules by connecting to just one of the modules.
1

Figure 1 '1+1' System block diagram

Supplied by Others
Input Utility
Supply A B C
UPS1 UPS2
Charger Charger
Inverter Inverter
NN
CB1 CB1
SW1-C SW1-C
Static
Switch
Battery 2Battery 1
SW1-D SW1-D
SW1-A SW1-A
Q1EXT Q2EXT
Distribution Panel
Input Utility
Supply A B C
FuseFuse
RectifierRectifier
Static
Switch
A B CA B C
QBYPQUPS
To L o ad

Operating Principles

Redundancy Paralleling
The redundancy parallel system can noticeably improve system reliability. In normal condition, nei­ther UPS module works at full load. That means that even if the load is increased, the system will not transfer to bypass. And when a UPS module shuts down due to any failure, the remaining UPS module can still power and protect the load. When redun­dancy is lost due to module failure or load increase, the parallel system will trigger an alarm.

Operation Modes Summary

The parallel system also has operation modes such as normal, battery, bypass and maintenance bypass. All UPS modules in the 1+1 parallel system operate in coordination.
Normal Mode Operation
The load is powered by the inverters of all the UPS modules in the system. If the frequency of bypass is within the synchronous range, the inverter will be synchronized with the bypass. Otherwise, the system will operate at nominal frequency.
Battery Mode Operation
The batteries of all UPS modules power the load through their inverters. The system operates at nominal frequency.
Bypass Mode Operation
The condition to transfer to bypass mode is the same as that for a single module system. The bypass of all the UPS modules powers the load.
Maintenance Bypass Mode Operation
The sequence to transfer to maintenance bypass mode is the same as for transferring a single­module system. The maintenance bypass switches should be switched on as synchronously as possible. Thus the system can be repaired without interrupting the power supply to critical load.

Intermodule Control

Two kinds of signals are used for the parallel cables:
Analog signals—UPS output unbalanced current
Digital signals—control logic signals, parallel
cable status
Parallel control cables should be connected to the parallel board (M3) of all modules and form a ring to provide redundancy as shown in Figure 2.
Two types of Parallel control cables needed:
DB9 for analog signals with one end DB9/F and
one end DB9/M
DB25 for digital signals with one end DB25/F and
one end DB25/M
These come in lengths of 5m, 10m, &15m.
2
Loading...
+ 2 hidden pages