Liebert nteleCool 2, InteleCool 2 User Manual

Page 1
Precision Cooling For Business-Critical Continuity™
Liebert InteleCool®2
User Manual - Outdoor Wall-Mount Air Conditioner, 1.5 - 5 Tons, 50 & 60 Hz
Page 2
Page 3
TABLE OF CONTENTS
1.0 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3 Optional Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3.1 Refrigeration System Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.4 Ancillary Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.5 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.0 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.1 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1.1 Room Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1.2 Location Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1.3 Equipment Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Unit Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Piping Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.4 Ducting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5 Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5.1 Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5.2 Control Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.6 Outside Air Damper - Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.7 Economizer - Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.0 CHECKLIST FOR COMPLETE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
4.0 STARTUP PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
5.0 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.1 Compressorized Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
5.2 Economizer Cooling—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.2.1 Enthalpy Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.2.2 Actuator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.3 Heating - Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
5.4 Unit Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.4.1 Remote Control Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.4.2 High Pressure (Standard) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.4.3 Refrigeration Control Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5.4.4 Anti-Short Cycle Timer - Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.4.5 Heater Protection - With Optional Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.4.6 Lockout Relay - Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.4.7 Common Alarm - Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Page 4
6.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
6.1 Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.2 Blower Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.3 Economizer—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.4 Heat. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.5 Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.5.1 Refrigerant Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6.5.2 Discharge Pressure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.5.3 Thermostatic Expansion Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.5.4 Air-Cooled Condenser. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.6 Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.6.1 Compressor Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
7.0 SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
7.1 Dimensional Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
7.2 Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
8.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
9.0 MAINTENANCE INSPECTION CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
10.0 PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
Page 5
FIGURES
Figure i Model number designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iv
Figure 1 Unit mounting dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 2 Low volt wiring terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 3 Mounting minimum position potentiometer on actuator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 4 Refrigeration system. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 5 Enthalpy control setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 6 Dimensional data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 7 Condenser/piping assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Figure 8 Evaporator blower. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Figure 9 Evaporator coil and expansion valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Figure 10 Electric panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Figure 11 Heater assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Figure 12 Economizer assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Figure 13 Common alarm assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Figure 14 Soft start device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
TABLES
Table 1 Mounting dimensional data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 2 Operating modes/contact closures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Table 3 Recommended applications for control options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Table 4 Pressure information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Table 5 Liebert InteleCool2 dimensions, in. (mm) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 6 Technical data, 60 Hz - Standard ambient condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 7 Technical data, 60 Hz - Standard ambient condenser, continued . . . . . . . . . . . . . . . . . . . . . . . . . 21
Table 8 Technical data, 50 Hz - Standard ambient condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Table 9 Technical data, 50 Hz - Standard ambient condenser, continued . . . . . . . . . . . . . . . . . . . . . . . . . 23
Table 10 Technical data, 60 Hz - High ambient condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table 11 Technical data, 60 Hz - High ambient condenser, continued . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table 12 Technical data, 50 Hz - High ambient condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Table 13 Technical data, 50 Hz - High ambient condenser, continued . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 14 Optional heater capacity, 60 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 15 Optional heater capacity, 50 Hz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 16 Electrical data, 60 Hz - amps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 17 Electrical data, 50 Hz - amps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Table 18 Troubleshooting guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Table 19 Refrigeration system parts, 1.5 and 2 ton units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Table 20 Refrigeration system parts, 3 ton units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Table 21 Refrigeration system parts, 4-ton units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 22 Refrigeration system parts, 5-ton units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Table 23 Electric panel, 1.5- and 2-ton units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Table 24 Electric panel parts, 3-ton units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Table 25 Electric panel parts, 4-ton unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Table 26 Electric panel parts, 5-ton unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Table 27 Motor parts, heater, Economizer, 1.5- and 2-ton units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Table 28 Motor parts, heater, Economizer, 3-ton units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Table 29 Motor parts, heater, Economizer, 4-ton units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Table 30 Motor parts, heater, Economizer, 5-ton units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
iii
Page 6
Figure i Model number designation
External Telecommunication
0=Standard Supply & Return
Openings
3=4 or 5 Ton Unit With 3 Ton
Supply & Return Openings
ET 0 36 7 R P F B T
Nominal Btuhs (1000)
7 = Scroll Compressor
with POE oil, R-407C
R = Right Compressor L = Left Compressor
P = 208/230V – 1 ph - 60 Hz S = 220/240 – 1 ph - 50 Hz A = 460V – 3 ph - 60 Hz Y = 208/230V – 3 ph - 60 Hz N = 200/230 – 3 ph - 50 Hz M = 380/415V – 3 ph - 50 Hz
0 = Standard F = Fixed Outside Air Damper E = Economizer
0 = No Heat A = 5 kW Heat B = 10 kW Heat C = 15 kW Heat
T = Tan, Painted Steel Panels C = Custom Color, Painted Steel Panels A = Aluminum Panels
iv
Page 7
1.0 INTRODUCTION
1.1 General
The Liebert InteleCool2 Environmental Control System was designed for convenience and dependabil­ity in unmanned and remote locations typical of the telecommunications industry. Ease of installation, operation and service coupled with the use of high quality, high reliability components make the Liebert InteleCool2 ideally suited for maintaining an environment for sensitive electronic equipment. Standard units are NRTL-C listed/certified to meet U.S. and Canadian safety standards, and MEA listed for New York City applications. These agency listings insure fast, hassle-free inspection and building code approvals.
Self-Contained
The Liebert InteleCool2 product is completely self-contained. All components are enclosed in the weatherproof cabinet.
Space Savings
The Liebert InteleCool2 does not use any of the valuable floor space inside the secure space. Instead, it is mounted on the outside wall. No additional space is required outside or on a roof.
Easy to Install
The Liebert InteleCool2 is assembled, wired, piped, charged with refrigerant, and fully factory tested as a system to ensure trouble free installation and start-up.
1.2 Standard Features
Scroll Compressor
The quiet and efficient scroll compressor features a suction gas cooled motor, internal centrifugal oil pump, vibration isolating mountings and internal thermal overloads.
Refrigeration System
The refrigeration circuit includes a liquid line filter drier, an externally equalized expansion valve, and a high-pressure switch. The system is charged with R-407C refrigerant at the factory.
Evaporator Coil
The evaporator coil is constructed of mechanically expanded copper tubes in enhanced surface alumi­num fins. A coated, galvanized steel condensate drain pan is provided.
Condenser Coil
The air-cooled condenser coil is constructed of mechanically expanded copper tubes in enhanced sur­face aluminum fins. Components rated for up to 110°F (43°C) ambient.
Evaporator Blower
Evaporator air is supplied by a direct drive blower package. Fans are centrifugal, double width, dou­ble inlet.
Filter
The filter is 2 inches deep, pleated, MERV 7 efficiency based on ASHRAE standard 52.2 (20% based on ASHRAE standard 52.1). Located within the cabinet, the filter is serviceable from the front of the unit.
Cabinet
The exterior cabinet is constructed of painted steel. Internal structural parts (including base) are hot dipped galvanized steel. The evaporator compartment is insulated with 1/2" thick, 2 lb. density, neo­prene-faced, fiberglass insulation.
Control Interface
The unit is supplied with customary HVAC wiring designations (R, G, W, Y) inside the low voltage partition of the unit electric box. The control interface can be provided by sources ranging from a wall mounted thermostat, a Liebert control and monitoring system or a third party building management control.
Introduction
1
Page 8
1.3 Optional Features
4 or 5 Ton Unit With 3 Ton Openings
The 4 or 5 ton units with 3 ton supply and return openings are designed to replace 3 ton wall mounted air conditioners using existing wall openings. The economizer/fresh air option is not available. Return filter is located in the return air grille and must be selected from accessory equipment.
Compressor Location
The standard compressor location is on the right when viewing the unit when it is mounted on the wall. The optional compressor location is on the left, to improve serviceability of the compressor when the unit is installed as one unit of a pair.
Compressor Crankcase Heater
An optional compressor crankcase heater is available for use with the scroll compressor but is not required because the refrigerant charge of the Liebert InteleCool2 unit with scroll compressor is less than the compressor critical charge.
High Ambient Condenser
This option is provided for applications where the ambient temperature exceeds the normal design capabilities of the units. It consists of a condenser motor and fan blades which are sized to provide additional airflow across the condenser coil. Designed for applications up to 120°F (49°C) ambient.
Heat
Heat is provided in a single stage from an open wire electric resistance element. Heating capacity options available are 5 kW, 10 kW, and 15 kW depending on unit model size.
Introduction
Economizer
The Economizer allows outside air to be introduced to the space through the evaporator filter when conditions are favorable for Economizer cooling. It contains a modulating damper, spring return direct drive actuator, enthalpy control for switchover, outside air hood and a mixed air controller set at 55°F (12.8°C). Mechanical cooling and Economizer operation do not operate simultaneously.
Fresh Air Damper
Allows outside air to be brought in to meet indoor air requirements. Air is drawn in through the evap­orator filter. The amount of air to be introduced to the space is field selectable.
Panel Colors
Optional color choices for the steel panels are almond (light tan, the color option for the original Liebert InteleCool), desert brown, or bright white.
Lockout Relay
The lockout relay latches the detection of a high-pressure condition in the refrigeration circuit and prohibits operation of the compressor until the abnormal pressure conditions are acknowledged. The lockout relay is reset by cycling the unit main power or by changing the setpoint on the thermostat to temporarily eliminate a call for cooling. A normally open set of contacts is provided to terminals 2 and 3 of the customer terminal strip for monitoring the status of the lock out relay when this option is sup­plied without the Common Alarm option.
Common Alarm
The common alarm provides the necessary components to detect high pressure, low pressure, high temperature, or loss of indoor airflow, and to provide a customer signal via a contact closure. To detect low pressure, the optional low pressure switch with bypass, T-pack1 or T-pack2 must also be selected.
Soft Start
Provides a PTC resistor to assist the start of the compressor motor in low voltage operation. Available only on single phase units.
1.3.1 Refrigeration System Options
Low Pressure Switch and Low Pressure Bypass Timer
Low Pressure Switch: Used to protect the Liebert InteleCool2 if the evaporator blower fails, the air filter becomes clogged, the refrigeration circuit malfunctions or if there is loss of refrigerant. The low
2
Page 9
pressure switch is activated when the suction pressure drops below its cutout setting. When acti­vated, the low pressure switch inhibits operation of the compressor and condenser fan. The switch will automatically reset once the system pressure rises above its cut-in setting.
Low Pressure Bypass Timer: Also known as the Condenser Low Ambient Control or Winter Start Option), the low pressure switch is used to start the system when the outdoor temperature is low. A few minutes after startup, the low pressure switch resumes normal operation. This option can be used for applications down to 50°F (10°C). For control down to -20°F (-28.9°C), use the T-pack1 or T-pack2.
T-pack1
This option provides a Low Pressure Switch, a Low Pressure Bypass Timer (described above), and a Fan Cycle Control. This option package is one of the preferred control packages for telecommunica­tion industry applications.
The Fan Cycle Control, also known as the Condenser Fan Cycling Control, consists of a reverse-acting pressure switch. When the outdoor temperature is low, the pressure switch cycles the condenser fan to maintain discharge pressures that will allow the systems to function. It is to be used when the out­door ambient temperature is lower than 50°F (10°C) down to -20°F (-28.9°C).
T-pack2
This option includes a Low Pressure Switch, a Low Pressure Bypass Timer (described above), and an adjustable Fan Cycle Control, which acts as described in the preceding paragraph, except that it is adjustable. This option package is one of the preferred control packages for telecommunication indus­try applications.
1.4 Ancillary Components
Introduction
Wall-Mounted Thermostat
The thermostat provides for heating/cooling application with separate fan control. Supplied with a thermostat sub-base.
Indoor Supply/Return Grilles
The supply grille is an aluminum louvered, double deflection type grille allowing user adjustment of direction of air distribution. The return grille is an aluminum louvered, fixed, single-deflection style grille.
Additional Spare Filters
Additional sets of the MERV 7 efficiency filters based on ASHRAE standard 52.2 (20% based on ASHRAE standard 52.1) may be selected.
1.5 Accessories
Dual Unit Control
The hinged-cover, dual unit control (DUC) has a two-stage heat/cool thermostat with individual heat­ing and cooling setpoints, adjustable interstage differentials, and bimetallic elements. The control features a solid state timer with 1-2-4-8 day sequence. Unit lead selector, Unit 1 & 2 power-on LEDs, Unit 1 or 2 lead unit LEDs, 48 hour program save on loss of power, industry-standard connections and 24V power from each unit. The DUC provides auto sequencing and displays on-status and operat­ing-status parameters.
Tele2 C ontro l
This microprocessor-based controller controls two Liebert InteleCool2 units. The unit has a 10-key keypad, four-row by 20-column LCD, an RS-232 modem port, and an RS-232 terminal port. It allows up to eight customer-selectable, isolated normally open, dry contact alarm inputs. The Tele2 control requires either a THS28-30 or a THS28-60 sensor assembly. Models are available for 120/50-60/1 VAC, 230/50-60/1 VAC or 48 VDC power.
3
Page 10
2.0 INSTALLATION
2.1 Preparation
2.1.1 Room Preparation
The room should be well-insulated and sealed to reduce airborne contaminants from penetrating the site. Outside air may be introduced through the damper option or be used for economized cooling by using the Economizer option. However, uncontrolled outside air should be kept to a minimum. Out­side air adds to the cooling, heating and filtration loads of the site. Doors should be properly sealed to minimize leaks and should not contain grilles.
2.1.2 Location Considerations
The Liebert InteleCool2 unit is field-mounted on an outside wall. Additional framing in the wall may be required to ensure adequate structural support.
The outdoor area near the condenser supply and discharge must also be considered. To assure ade­quate air supply, the unit should be mounted in a clean area, away from loose dirt and foreign matter that may clog the condenser coil. The unit should not be located near steam, hot air, or fume exhausts. Also, the unit should not be mounted closer than 12 feet (3.7 m) from an opposing wall, obstruction or unit. For service clearance, provide 36 inches (914 mm) in front of the unit, and 30 inches (762 mm) on each side. When mounting units side by side, provide a minimum of 36 inches (914 mm) between adja­cent units unless the adjacent units will not be run at the same time. In this case, the units may be placed as close as 18 inches (457 mm) apart. However, this will make the units more difficult to service. In such situations, consider the compressor location option for improved serviceability. Before mount­ing units, check local codes for applicable clearances.
2.1.3 Equipment Inspection
Upon delivery of the unit, inspect all items for visible damage. Concealed damage may be discovered later during installation. Report any damage to the shipper immediately and file a damage claim. Also, forward a copy of the damage claim to your Emerson supplier.
Installation
2.2 Unit Installation
The Liebert InteleCool2 unit is installed against, and through, an outside wall. Two (2) openings in the wall are required for the evaporator supply and return. Provide 1/2" clearance on wall openings for supply and return air. Install the unit in a level position to assure proper refrigerant flow, oil return, and condensate drain. To install the unit, follow the instructions below.
1. Verify that an adequate structural support is provided for the unit.
2. Using a chalk line, mark the outside wall with a level horizontal line, where the bottom of the unit is to rest.
3. Prepare supply and return openings in an outside wall, measuring up from the chalk base line.
4. Prepare mounting holes. The mounting holes may be pilot holes for lag screws or clearance holes for bolts that will extend completely through the wall. Refer to Figure 1 for the location of these holes.
5. Fasten the unit mounting base angle to the outside wall with six 5/16" bolts or lag screws (not supplied), just below chalk line and centered on the opening in the wall.
WARNING
!
Risk of heavy unit330-490 lb. (150-222 kg). Can cause serious injury. Use caution and adequate equipment to safely handle unit.
6. With the unit front panel removed, lift the unit onto the base angle, making certain that the rear unit angle falls behind the turned up front edge of the mounting angle. Insert top and side unit fasteners in holes and tighten, drawing the unit into place. Do not attach ducts to unit prior
to installing unit.
7. Caulk and flash the top and sides as required to form a watertight seal. Top flashing (not factory supplied) is recommended to ensure that water does not run behind unit. All unit tops are sloped to allow water to run off.
4
Page 11
Figure 1 Unit mounting dimensions
J
K
K
11"
(279mm)
11"
(279mm)
A
11"
(279mm)
Installation
P
E
C
F
K
K
DB
G
H
K
See Table 1 below for keys to dimensions.
L
M ref.
N
Wf
Table 1 Mounting dimensional data
Liebert InteleCool2 dimensional data in. (mm)
Model Wf A B C D E F G H J K L M N P
1.5-2 Ton
3 Ton
4-5 Ton
4 or 5 Ton Unit
w/3 Ton
Openings
38-3/4
(984)20(508)20(508)
38-3/4
(984)28(711)28(711)
42-3/4
30-1/4
(1086)
42-3/4 (1086)
(768)
28
(711)28(711)
29-7/8
(759)
9-3/8
9-13/32
(238)
(239)8(203)
5-3/8
5-3/8
(137)
(137)8(203)18(457)14(356)26(660)
6-1/4
6-7/16
(159)
(164)
7-3/8
7-3/8
(187)
(187)8(203)18(457)14(356)
20-3/4
(527)12(305)
9-7/8 (251)30(762)
15-7/8
(403)
25-1/16
(638)
25-25/64
(645)
37-1/2
(952)
5-15/32
(139)12(305)
5-15/32
(139)12(305)
1-45/64
(43)16(406)
1-45/64
(43)16(406)
3-25/32
(96)
3-25/32
(96)
61/64
(24)
61/64
(24)
4-1/2 (114)
4-1/2 (114)
6-1/2 (165)
6-1/2 (165)
37-7/8
(962)
37-7/8
(962)
41-3/4 (1060)
41-3/4 (1060)
2-15/32
(63)
2-15/32
(63)
4-3/8 (111)
4-3/8 (111)
2.3 Piping Connections
The Liebert InteleCool2 is a self-contained, packaged unit. All refrigerant piping connections are made at the factory, so no external condenser is required. The evaporator coil condensate drain is fac­tory-supplied and drains outdoors through the unit base pan. The condensate drain tubing should be checked to be certain that it is placed through the hole provided in the base pan.
5
Page 12
2.4 Ducting
Field-supplied ducting can be attached to the unit duct connection once the unit has been mounted to the outside wall. The total external static pressure for the duct, including grille, must not exceed the values shown in Table 5 and Table 6. Indoor discharge air rates are also given in the same tables.
2.5 Electrical Connections
WARNING
!
Risk of electric shock. Can cause injury and death. Disconnect all local and remote electric power supplies before working within.
Use voltmeter to make sure power is turned off before making any electrical connections.
NOTE
Refer to electrical schematic when making connections.
Each unit is shipped from the factory with all internal wiring completed. Refer to the electrical sche­matic when making connections. Electrical connections to be made at the installation site are: line voltage power supply to the power input and control wiring to remote control (customer-supplied or Emerson option). DO NOT RUN CONTROL WIRING WITH HIGH VOLTAGE!
2.5.1 Power Connections
All power and control wiring and ground connections must be in accordance with the National Electri­cal Code and local codes.
Use copper wiring only. Make sure that all connections are tight.
Make sure that the voltage supplied agrees with the voltage specified on the unit nameplate. The Liebert InteleCool2 comes standard with a factory-installed circuit breaker, accessible through an external access panel. An external, wall-mounted power disconnect switch (field-supplied) may be required for local codes. If necessary, this switch should be wired according to those codes.
For access to the electrical enclosure:
• Remove the screws securing the middle panel and pull the panel down and forward to remove.
• Remove the screws securing the electric box cover and remove cover.
• Verify that the unit wiring is correct for the actual input power. Some units are built with multi­voltage serial tags. The transformer may need to be re-tapped if the actual input voltage is differ­ent (see serial tag and electrical schematic).
Route the supply power to the customer-supplied disconnect switch (if required) and then to the unit circuit breaker inside the unit. Route the conduit to the hole provided in the cabinet. Connect the earth ground to the lug provided near the circuit breaker. Refer to the unit wiring diagram supplied on the inside of the electrical enclosure cover.
Installation
NOTE
The optional three-phase scroll compressor must rotate in the correct direction to ensure proper system operation. Wiring must be phased and connected as shown:
• PHASE “A” to T1 or L1
• PHASE “B” to T2 or L2
• PHASE “C” to T3 or L3
2.5.2 Control Connections
Control wiring will be required for the remote control device. This remote device may be a factory- or field-supplied wall thermostat or similar device. Connections to the unit are made using customary HVAC low volt wiring terminals R, G, W, and Y. For detailed locations of the low volt wiring termi­nals, please refer to the Figure 10 - Electric panels.
6
Page 13
Figure 2 Low volt wiring terminals
Liebert Thermostat
See 2.5.2 - Control Connections for further information, refer to the detailed instructions that ship with the thermostat.
NOTE
This control contains mercury in a sealed tube. Do not place control in the trash at the end of is useful life. If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Contact your local waste management authority for instructions regarding recycling and the proper disposal of this control, or of an old control containing mercury in a sealed tube. If you have questions, call the thermostat manufacturer, Honeywell, at 800-468-1502.
Installation
Dual Unit Control
The Liebert InteleCool Dual Unit Control is designed to control two Liebert InteleCool units in a “lead/lag” fashion. The control contains an electronic timer for switching the operating sequence of two units on a one-, two-, four-, or eight-day basis. It also contains a two-stage heat/two-stage cool thermostat with individual heat and cool set points. Light emitting diodes (LEDs) indicate Lead Unit 1 or 2 and power from Unit 1 or 2. The schedule for lead/lag switchover is adjustable by moving jump­ers on the printed circuit board. A jumper is also used to change lead and lag unit before a scheduled changeover (if necessary for servicing).
NOTICE
The original Dual Unit Control (part # 153054G1, produced through March 2002), is phase sensitive. The latest version Dual Unit Control (Part # 171170G1) is not. Please refer to specific installation instructions supplied with each control. Failure to follow specific instructions may damage the control and/or the unit and void the warranty.
NOTE
This control contains mercury in a sealed tube. Do not place control in the trash at the end of its useful life. If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Contact your local waste management authority for instructions regarding recycling and the proper disposal of this control, or of an old control containing mercury in a sealed tube. If you have questions, call the thermostat manufacturer, Honeywell, at 800-468-1502.
Tele2
Consult the Tele2 user manual for installation instructions.
7
Page 14
2.6 Outside Air Damper - Optional
Units supplied with fixed (non-modulating) outdoor air damper can be adjusted as follows:
1. Remove the screws from the middle panel and remove panel.
2. Loosen the damper plate screws on the backside of the middle panel.
3. Adjust the damper plate to the desired position and tighten damper plate screws.
4. Replace panels.
2.7 Economizer - Optional
Installation
Insert the top flanged edge of the Economizer hood into the Economizer opening on the unit front panel. Next, attach the bottom left and right corner of the hood with screws (supplied).
Adjustment
Units supplied with Economizer requiring outside air can be adjusted as follows:
1. Run motor to fully closed position and disconnect 24 VAC from terminals TR and TR1.
2. Connect minimum position potentiometer to terminals P and P1. (See Figure 3. T and T1 are disconnected.)
3. Reconnect 24 VAC to terminals TR and TR1 and adjust potentiometer for desired minimum position by turning Q709 adjustment screw clockwise to increase minimum position; counterclockwise to decrease minimum position.
Installation
Figure 3 Mounting minimum position potentiometer on actuator
Push onto actuator
8
Page 15
3.0 CHECKLIST FOR COMPLETE INSTALLATION
___ 1. Proper clearance for service access has been maintained.
___ 2. Equipment is level and mounting fasteners are tight.
___ 3. Ducting completed, if required.
___ 4. Line voltage to power wiring matches equipment nameplate.
___ 5. Power wiring connections completed to disconnect switches, including earth ground. Proper
phase rotation has been observed so that scroll compressor will rotate in the correct direction.
___ 6. Power line circuit breakers or fuses have proper ratings for equipment installed.
___ 7. Control wiring connections completed to optional controls.
___ 8. All wiring connections are tight.
___ 9. Foreign materials have been removed from in and around all equipment installed (shipping
materials, construction materials, tools, etc.).
___ 10. Fans and blowers rotate freely without unusual noise.
WARNING
!
Risk of electric shock. Can cause injury and death. Disconnect all local and remote electric power supplies before working within.
Potentially lethal voltages exist within this equipment during operation. Observe all cautions and warnings in this manual. Only qualified service and maintenance personnel should work with this equipment.
Checklist for Complete Installation
9
Page 16
4.0 STARTUP PROCEDURE
Verify that installation is complete by using the Checklist for Complete Installation.
1. Disconnect all power to the Liebert InteleCool2 unit.
2. Adjust remote control to prevent compressor, heat and fan operation.
3. Turn on main breaker and check line voltage on main unit disconnect switch. Line voltage must be within ± 10 volts of nameplate voltage.
4. Turn ON main unit disconnect switch and check secondary voltage at transformer T1. Voltage at T1 must be 24 VAC ±2.5V.
5. From the remote control, verify proper operation in all modes.
6. Make sure all blowers, fans, and the scroll compressor are rotating in the correct direction.
7. Check the current draw on all line voltage components and compare with unit nameplate.
8. Check adjustment of the optional outside air damper for the desired balance between the flow of room air and outdoor air. Use a gauge or non-polluting airflow indicator.
NOTE
If the unit is supplied with crankcase heaters, Emerson recommends that the high voltage be applied between four and six hours before start-up.
Startup Procedure
10
Page 17
5.0 OPERATION
5.1 Compressorized Cooling
Compressorized cooling is provided by a high efficiency system consisting of a compressor, thermo­static expansion valve, evaporator, and condenser coil.
The Liebert InteleCool2 uses R-407C refrigerant in a conventional vapor-compression refrigeration cycle. Heat is removed from the air in the space by blowing the air across the evaporator coil. As heat is transferred to the refrigerant in the evaporator, the refrigerant boils and turns to a warm vapor. The refrigerant vapor enters the compressor and is compressed, resulting in high pressure and tem­perature. After entering the condenser, the hot vapor is condensed to a liquid by the air blown across the condenser coil. Liquid refrigerant then passes through the thermal expansion valve and into the evaporator. The expansion reduces the pressure and temperature to complete the cycle.
Figure 4 Refrigeration system
Evaporator
Operation
Thermal expansion valve (not shown)
Liquid line
Filter drier
Scroll Compressor (Optional compressor location available on opposite side of unit)
Liquid line
Condenser
Note: System is factory-piped and charged.
11
Page 18
5.2 Economizer Cooling—Optional
The Economizer mode uses outside air to cool the room when the outside air temperature is cool enough to allow for economical cooling. Components include the damper, spring return direct drive actuator, enthalpy sensor and actuator control board with an integral mixed air sensor. Economizer operation is enabled when the outside conditions meet required temperature and humidity as set on the enthalpy sensor. If outdoor conditions are favorable on a call for cooling, the damper actuator will open the Economizer damper. The damper position will be controlled based on the mixed air tempera­ture in the evaporator section. The factory set mixed air temperature target is 50-56°F (10-13°C).
The amount of damper opening depends on the cooling capacity of the outside air; the cooler the out­side air, the less that is needed to cool the room, and so a smaller damper opening is required. As the outside air temperature rises, the damper will open wider since more of that air is required to keep the room at the same temperature.
The Economizer and compressorized cooling will never operate at the same time. If outdoor conditions meet the required enthalpy sensor setpoint during a cooling cycle, the unit will automatically shut down the compressor and begin using outside air.
5.2.1 Enthalpy Sensor
The enthalpy sensor responds to the total heat content of the outdoor air to provide changeover from compressorized cooling to free-cooling operation. The changeover point is factory set (at the “D” posi­tion). This setting will ensure rated capacity when the outdoor conditions allow for Economizer cooling.
Figure 5 Enthalpy control setting
70
Operation
5.2.2 Actuator
The Economizer actuator is mounted in the lower part of the Economizer section below the electric box. It is accessible by opening the lower front panel. The actuator is a 24 VAC, spring return device that will fully close the Economizer damper. The actuator has internal controls that allow it to oper­ate based on signals from the enthalpy control and mixed air sensor.
65
60
Enthalpy Control
55
50
Temperature (DB°F)
45
40
10 20 30 40 50 60 70 80 90
Operating Range
Outdoor Relative Humidity (%RH)
5.3 Heating - Optional
On units supplied with optional resistance heating, a call for heating closes the heat relay and ener­gizes the evaporator fan and resistive elements.
12
Page 19
5.4 Unit Controls
5.4.1 Remote Control Interface
Control connections to the Liebert InteleCool2 unit use customary HVAC terminal designations R, G, W & Y. Contact closures between the 24 VAC (R) and different control connections supply control volt­age to the electric panel components responsible for the desired function. Operating modes are con­trolled by contact closures as follows:
Table 2 Operating modes/contact closures
Connection Operating Mode
R 24 VAC
G Evaporator Fan
WHeating
Y Cooling (compressorized or Economizer)
Wall-mounted thermostats are to be low voltage, snap action or mercury type. Un-manned sites should use a HEAT/COOL/AUTO type subbase to provide automatic switchover during climate changes.
5.4.2 High Pressure (Standard)
The high pressure switch is mounted in the liquid line. Electrically, it is connected in series with the compressor start circuit, which will shut down the compressor and condenser fan if the liquid pres­sure exceeds 400 PSIG (2758 kPa). This protects the Liebert InteleCool2 in the event of condenser motor failure or condenser coil blockage.
The pressure switch is an auto reset device. When the system pressure drops below 300 PSIG (2069 kPa), the switch will reset. (An optional lockout relay is available which allows the switch to be used as a manual reset safety.) If the call for cooling is present, the compressor start circuit will be energized and the compressor will start after the 3 minute anti-short cycle time.
Operation
5.4.3 Refrigeration Control Options
Please review the following table for the recommended control options based on the site ambient and your need for year-round operation.
Table 3 Recommended applications for control options
Application Unit Options Min ambient Max ambient
General Standard None 50°F (10°C) 110°F (43°C)
General Standard
General Standard T-pack1 or T-pack2 -20°F (-28.9°C) 110°F (43°C)
Telecom/365-day operation Standard T-pack1 or T-pack2 -20°F (-28.9°C) 110°F (43°C)
General Standard High ambient 50°F (10°C) 120°F (49°C)
General Standard
Telecom/365-day operation Standard High ambient with T-pack1 or T-pack2 -20°F (-28.9°C) 120°F (49°C)
Low Pressure Switch and Low Pressure Bypass Timer (Winter Start)
Low Pressure Switch—The low pressure switch is mounted in the compressor suction line. Electri­cally, it is connected in series with the compressor start circuit, which will shut down the compressor and condenser fan if the suction pressure drops below 35 PSIG (241 kPa). The switch will automati­cally reset once the system pressure rises above its cut-in setting (60 psig, ±5 psig [414 kPa, ±34 kPa]). This protects the Liebert InteleCool2 in the event the evaporator fan fails, the filter becomes clogged or there is a loss of refrigerant. If the call for cooling is present, the compressor will start after the 3 minute anti-short cycle time.
Low Pressure Bypass Timer—A low ambient temperature start relay is included with the low pressure option. This relay locks out (ignores) the low pressure switch on start-up until the system pressure stabilizes. This bypass relay is adjustable and should be set for 3 minutes greater than the anti-short cycle timer setting. This option can be used for applications down to 50°F (10°C). For con­trol down to -20°F (-28.9°C), use the T-pack1 and T-pack2 options, which include fan cycle control.
Low pressure with low pressure bypass timer
High ambient, low pressure with low pressure bypass timer
50°F (10°C) 110°F (43°C)
50°F (10°C) 120°F (49°C)
13
Page 20
T-pack1 package
Includes a low pressure switch, low pressure bypass timer (described above) and fan cycle control.
Fan Cycle Control—Condenser Fan Cycling Control; allows the Liebert InteleCool2 unit to provide cooling to the space when the outdoor ambient temperature is lower than 50°F (10°C) and down to
-20°F (-28.9°C). The control uses a reverse acting pressure switch mounted on the discharge line that
cycles the condenser fan in response to the discharge pressure. On a call for cooling, when the dis­charge pressure increases to 250 PSIG (1723 kPa), the switch will close and start the condenser fan. When the pressure drips below 170 PSIG (1172 kPa) the switch will open and stop the condenser fan. During low outdoor temperatures, the pressure switch cycles the condenser fan to maintain discharge pressure that will allow the system to function.
NOTE
During normal operation in low ambient conditions, the condenser fan will cycle frequently.
T-pack2 package
Includes a low pressure switch, low pressure bypass timer and an adjustable fan cycle control. See descriptions above.
5.4.4 Anti-Short Cycle Timer - Standard
The anti-short cycle timer protects the compressor from continuous ON-OFF operation and restarts after momentary power failures. The timer used is adjustable and is set to a minimum of 3 minutes. On start-up, or any call for cooling after an off cycle of more than 3 minutes, the compressor will start immediately.
Operation
5.4.5 Heater Protection - With Optional Heat
On units supplied with resistance heating, an auto reset heater safety and a one time (replaceable) thermal link protects the unit wiring and prevents excessive heat conditions caused by a dirty air fil­ter or fan failure.
5.4.6 Lockout Relay - Optional
The lockout relay latches the detection of a high-pressure condition in the refrigeration circuit and prohibits operation of the compressor until the abnormal pressure conditions are acknowledged. The lockout relay is reset by cycling the unit main power or by changing the setpoint on the thermostat to temporarily eliminate a call for cooling. A normally open set of contacts is provided to terminals 2 and 3 of the customer terminal strip for monitoring the status of the lock out relay when this option is sup­plied without the Common Alarm option.
5.4.7 Common Alarm - Optional
Alarm components are an evaporator air sail switch, evaporator high temperature switch, control relays and an adjustable time delay relay with two normally open and two normally closed alarm con­tacts. The alarm contacts will activate in the event of a loss of airflow across the evaporator blower, high evaporator temperature or in the event that the compressor is not functioning due to an abnor­mal pressure condition. The adjustable time delay relay can be adjusted for a delay of up to 90 sec­onds to eliminate nuisance tripping of the alarm contacts. To detect low pressure, the optional low pressure switch with bypass, T-pack1 or T-pack2 must also be selected.
14
Page 21
6.0 MAINTENANCE
WARNING
!
Risk of electric shock. Can cause injury and death. Disconnect all local and remote electric power supplies before working within.
Potentially lethal voltages exist within this equipment during operation. Observe all cautions and warnings in this manual. Only qualified service and maintenance personnel should work with this equipment.
6.1 Filters
Replaceable evaporator air filter(s) are supplied with the unit. The filter(s) are easily serviceable from the outside, through the top front access panel.
Filters are usually the most neglected item in an environmental control system. To maintain efficient operation, they should be checked monthly and changed as required. Units supplied with Economiz­ers may require replacement filters more frequently because of airborne dust and organic materials.
Filters can be replaced from the front by opening the lower front access panel.
WARNING
!
Risk of electric shock. Can cause injury and death. Disconnect all local and remote electric power supplies before replacing filters.
Maintenance
6.2 Blower Package
Periodic checks of the blower package include: blower wheels, housings, motor and motor mounting bracket. With the power off, inspect and remove any debris from the wheels and housings. Also check to see that they are tightly mounted on the motor shaft and rotate freely without rubbing against the housing.
WARNING
!
Risk of electric shock. Can cause injury and death. Disconnect all local and remote electric power supplies before inspecting the blower equipment.
6.3 Economizer—Optional
Each month, the Economizer should be inspected and any debris removed from the intake hood, damper blade and enthalpy sensor.
6.4 Heat
Heaters can be serviced and/or removed from inside through the discharge opening or from outside by removing the top.
WARNING
!
Risk of electric shock. Can cause injury and death. Disconnect all local and remote electric power supplies before working on the heaters.
6.5 Refrigeration System
Each month, the components of the refrigeration system should be inspected for proper function and signs of wear. Since, in most cases, evidence of malfunction is present prior to component failure, peri­odic inspections can be a major factor in the prevention of most system failures.
6.5.1 Refrigerant Lines
Check all refrigerant lines and capillaries for vibration isolation, and support as necessary. Visually inspect all refrigerant lines for leaks.
15
Page 22
6.5.2 Discharge Pressure
Discharge pressure can be increased or decreased by load conditions or condenser efficiency. The high-pressure switch will shut the compressor/contactor at its cut-out setting of 400 PSIG (2758 kPa). See 5.4.2 - High Pressure (Standard).
6.5.3 Thermostatic Expansion Valve
The thermostatic expansion valve (TEV) keeps the evaporator supplied with enough refrigerant to satisfy load conditions. It does not turn the compressor on or off, but maintains proper refrigerant super heat in the suction gas to the compressor.
Determine TEV operation by measuring superheat. If too little refrigerant is being fed to the evapora­tor, the superheat will be high; if too much refrigerant is being supplied, the superheat will be low. The correct superheat setting is between 10° and 20°F (5.5° and 11.1°C), under normal load condi­tions and “steady-state” operation. Some models of Liebert InteleCool2 will be supplied with a non­adjustable expansion valve, so no adjustments are possible.
To adjust the superheat setting when an adjustable valve is used:
1. Remove the valve cap from the base of the valve.
2. Turn the adjustment stem counter-clockwise to lower the superheat.
3. Turn the adjustment stem clockwise to increase the superheat.
NOTE
Make no more than 1/4 turn of the stem at a time. As long as 30 minutes may be required for the new balance to take place.
Maintenance
To determine superheat:
1. Measure the temperature of the suction line at the point where the TEV bulb is clamped.
2. Obtain the gauge pressure at the compressor suction valve.
3. Add the estimated pressure drop between bulb location and the suction valve.
4. Convert the sum of the two pressures to the saturated temperature.
5. Subtract this temperature from the actual suction line temperature. The difference is superheat.
6.5.4 Air-Cooled Condenser
Restricted airflow through the condenser coil will reduce the operating efficiency of the unit and can result in high compressor head pressure and loss of cooling.
Clean the condenser coil each time the evaporator filters are replaced. Check for bent or damaged coil fins and repair as needed. Check all refrigerant lines for leaks. Clean the condenser coil of all debris that will inhibit airflow. This can be done with compressed air or commercial coil cleaner.
6.6 Compressor
Infrequently, a fault in the motor insulation may result in a motor burn. However, in a properly installed system, burnouts rarely occur. Of those that do, most are the result of mechanical or lubrica­tion failures, resulting in the burnout as a secondary consequence.
If the problems that can cause compressor failures are detected and corrected early, a large percent­age can be prevented. Periodic maintenance inspections by alert service personnel on the lookout for abnormal operation can be a major factor in reducing maintenance costs. It is easier and far less costly to take the steps necessary to ensure proper system operation than it is to allow a compressor to fail and require replacement.
When troubleshooting a compressor, check all electrical components for proper operation, including all fuses and circuit breakers and pressure switch operation.
If a compressor failure has occurred, determine whether it is an electrical or mechanical failure.
16
Page 23
Maintenance
Mechanical Failure
A mechanical compressor failure will not be indicated by a burned odor. The motor will attempt to run. If you have determined that a mechanical failure has occurred, the compressor must be replaced.
Electrical Failure
An electrical failure will be indicated by a distinct pungent odor. If a severe burnout has occurred, the oil will be black and acidic. If a burnout does occur, correct the problem that caused the burnout and clean the system thoroughly using the proper procedure. It is important to note that successive burn­outs of the same system are usually caused by improper cleaning.
NOTICE
Risk of contaminated system. Can cause equipment damage. Damage to a replacement compressor caused by improper system cleaning constitutes abuse
under the terms of the warranty, and the WARRANTY WILL BE VOIDED.
There are two kits that can be used with a complete compressor burnout: Sporlan System Cleaner and Alco Dri-Kleener. Whichever kit is used, follow the manufacturer’s procedure.
CAUTION
!
Risk of caustic material. Can cause personal injury. Avoid skin contact with the refrigerant and oils. Severe burns will result. Use long rubber
gloves when handling contaminated parts.
6.6.1 Compressor Replacement
Replacement compressors are available from your Emerson supplier. They will be shipped in a reus­able crate to the job site as required by the service contractor.
Upon shipping a replacement compressor, the service contractor will be billed in full for the compres­sor until the failed compressor has been returned to the factory.
The compressor should be returned in the same container used for shipping to the job. The possible damage causes or conditions that were found should be recorded by marking the compressor return tag.
1. Disconnect power.
2. Attach suction and discharge gauges to access fittings.
3. Recover refrigerant using standard recovery procedures and equipment. Use a filter drier when charging the system with recovered refrigerant.
CAUTION
!
Risk of explosive discharge of refrigerant. Can cause personal injury or equipment damage. Do not loosen any refrigeration or electrical connections before relieving system pressure from
both sides of the compressor.
NOTE
Release of refrigerant to the atmosphere is harmful to the environment and is unlawful. Refrigerant must be recycled or discarded in accordance with federal, state, and local regulations.
17
Page 24
Maintenance
4. Disconnect all electrical connections.
5. Remove failed compressor.
NOTE
The optional three-phase scroll compressor must rotate in the correct direction to ensure proper system operation. Wiring must be phased and connected as shown:
• PHASE “A” to T1 or Ll
• PHASE “B” to T2 or L2
• PHASE “C” to T3 or L3
6. Install replacement compressor and make all connections.
7. Pressurize and leak test the system at approximately 150 PSIG (1034 kPa) pressure.
8. Follow manufacturer’s instructions for cleanout kits.
9. Connect a vacuum pump to both the high and low sides of the system through properly sized connections. Evacuate the system twice to 1500 microns, and the third time to 500 microns. Break the vacuum each time with dry nitrogen to 2 PSIG (13.8 kPa).
10. Charge the system with refrigerant. Refer to unit serial tag for refrigerant charge amount.
11. Apply power and operate system. Check for proper operation. Suction and discharge pressures will vary with load conditions and coil efficiency. The low pressure switch will shut the compressor down if the suction pressure falls below the cutout setting. Conversely, the high pressure switch will shut down the compressor if the discharge pressure exceeds the cutout setting. High suction pressure reduces the ability of the refrigerant to cool compressor components and can result in compressor damage. Refer to Table 4.
NOTE
High side gauge port is a liquid line connection. Proper procedures should be followed when installing and removing gauges. A 6-foot (1.8 m) hose can hold up to 3 oz (0.1 l) of refrigerant. Be sure to purge high side to low prior to removal.
Table 4 Pressure information
Design Pressures psig (kPA)
Suction 35 (241) 90 (620)
95°F (35°C) Ambient 250-290 (1723-2000)
High Pressure Cutout 400 (2756)
Based on indoor conditions of 80°F (26.7°C), 50% RH, with clean filter(s).
Minimum
psig (kPa)
R-407C
Liquid (Approx.) PSIG (kPa)
Maximum 360-380 (2480-2618)
Maximum
psig (kPa)
R-407C
18
Page 25
7.0 SPECIFICATIONS
7.1 Dimensional Data
Figure 6 Dimensional data
Ws
J
4"
(102mm)
2-1/4"
(58mm)
Entrance for high
volt connections
E
A
supply
Specifications
Wu
F
K
G
B
return
H
Shaded areas indicate a recommended clearance of 34" (864mm) in front and 30" (762mm) each side, or 36" (914mm) when mounted adjacent to another unit, for component access. For recommended minimum clearances, refer to 2.1.2 - Location Con­siderations.
See Table 5 below for dimensions.
Wf
2-1/4"
(58mm)
Table 5 Liebert InteleCool2 dimensions, in. (mm)
Dimensions, in. (mm)
Model Wu Ws Wf A B C D E F G H J K L
37-1/8
17-3/4
1.5/2 Ton
3 Ton
4/5 Ton
4 or 5 Ton Unit
w/ 3 Ton Openings41(1041)
(943)
37-1/8
(943)
41
(1041)
38-3/4
(451)
(984)20(508)20(508)
17-3/4
38-3/4
(451)
(984)28(711)28(711)
22-1/2
42-3/4
(572)
(1086)
22-1/2
42-3/4
(572)
(1086)28(711)28(711)
30-1/4
(768)
29-7/8
(759)
9-3/8
9-13/32
(238)
(239)8(203)
5-3/8
5-3/8
(137)
(137)8(203)18(457)14(356)26(660)
6-1/4
6-7/16
(159)
(164)
7-3/8
7-3/8
(187)
(187)8(203)18(457)14(356)
20-3/4
(527)12(305)
9-7/8 (251)30(762)
15-7/8
(403)
25-1/16
(638)
25-25/64
(645)83(2108)44(1118)
37-1/2
(952)83(2108)44(1118)
69-3/4 (1772)
69-3/4 (1772)
1-11/16"
C
(43mm)
Entrance
for low volt
connections
L
D
36-3/16
36-3/16
(919)
(919)
31-5/8
(803)
31-5/8
(803)
39-1/2 (1003)
39-1/2 (1003)
19
Page 26
Specifications
7.2 Technical Data
Table 6 Technical data, 60 Hz - Standard ambient condenser
Model ET018 ET024 ET036
Compressor type Scroll Scroll Scroll
Net capacity data based on 80°F (26.6°C) DB/67°F (19.4°C) WB indoor ambient - BTUH (kW)*
Outdoor ambient
85°F
(29.4°C)
95°F
(35.0°C)
105°F
(40.6°C)
110°F
(43°C)**
Net capacity data based on 75°F (23.9°C) DB/62.5°F (16.9°C) WB indoor ambient - BTUH (kW)*
Outdoor ambient
85°F
(29.4°C)
95°F
(35.0°C)
105°F
(40.6°C)
110°F
(43°C)**
Evaporator Air Flow - Dry Coil
External Static Pressure CFM (m
0.0 - IN WG (0.0 Pa) 870 (1480) 930 (1580) 1300 (2210)
0.1 - IN WG (25 Pa) 830 (1410) 880 (1500) 1220 (2070)
0.2 - IN WG (50 Pa) 780 (1320) 840 (1430) 1130 (1920)
0.3 - IN WG (75 Pa) 750 (1260) 800 (1360) 1030 (1750)
0.4 - IN WG (100 Pa) 670 (1140) 730 (1240) 920 (1560)
0.5 - IN WG (125 Pa) 590 (1000) 650 (1100) 820 (1390)
Evaporator Air Flow - Wet Coil
External Static Pressure CFM (m
0.0 - IN WG (0.0 Pa) 850 (1440) 910 (1550) 1200 (2040)
0.1 - IN WG (25 Pa) 810 (1380) 860 (1460) 1120 (1900)
0.2 - IN WG (50 Pa) 770 (1310) 820 (1390) 1030 (1750)
0.3 - IN WG (75 Pa) 720 (1220) 780 (1320) 940 (1600)
0.4 - IN WG (100 Pa) 650 (1100) 710 (1210) 850 (1440)
0.5 - IN WG (125 Pa) 570 (970) 620 (1050) 750 (1270)
Evaporator
Motor Hp (kW) 0.25 (0.19) 0.25 (0.19) 0.25 (0.19)
Filter Sizes - Quantity in. (cm)
Drain Connection - ID in. 3/4 3/4 3/4
Weight w/o Economizer Ib (kg) 330 (150) 330 (150) 330 (150)
Weight w/ Economizer Ib (kg) 350 (159) 350 (159) 350 (159)
* Based on rated airflow at 0.2 IN WG (50 Pa) external static and no outside air. ** For applications above 110°F (43°C) use high ambient option.
Total 19400 (5.7) 22300 (6.5) 34400 (10.1)
Sensible 15800 (4.6) 17200 (5.0) 24300 (7.1)
Total 18500 (5.4) 21400 (6.3) 32900 (9.6)
Sensible 15500 (4.5) 16900 (5.0) 23800 (6.9)
Total 17500 (5.1) 20400 (6.0) 31300 (9.1)
Sensible 15200 (4.5) 16600 (4.9) 23100 (6.8)
Total 17000 (5.0) 19800 (5.8) 29500 (8.6)
Sensible 15800 (4.7) 16200 (4.8) 22600 (6.7)
Total 17900 (5.3) 20700 (6.1) 32100 (9.4)
Sensible 15200 (4.5) 16700 (4.9) 23800 (7.0)
Total 17000 (4.9) 19900 (5.8) 30700 (9.0)
Sensible 14900 (4.4) 16400 (4.8) 23100 (6.8)
Total 16400 (4.8) 18900 (5.5) 29300 (8.6)
Sensible 15600 (4.6) 16000 (4.7) 22500 (6.6)
Total 15700 (4.6) 18300 (5.4) 27600 (8.1)
Sensible 14900 (4.3) 15800 (4.6) 21900 (6.4)
3
/hr)
3
/hr)
16 x 32.5 x 2 - one
(40.6 x 82.5 x 5)
16 x 32.5 x 2 - one
(40.6 x 82.5 x 5)
16 x 32.5 x 2 - one
(40.6 x 82.5 x 5)
20
Page 27
Table 7 Technical data, 60 Hz - Standard ambient condenser, continued
Model ET048, ET348 ET060, ET360
Compressor Type Scroll Scroll
Net capacity data based on 80°F (26.6°C) DB/67°F (19.4°C) WB indoor ambient - BTUH (kW)*
Outdoor ambient
85°F
(29.4°C)
95°F
(35.0°C)
105°F
(40.6°C)
110°F
(43°C)**
Net capacity data based on 75°F (23.9°C) DB/62.5°F (16.9°C) WB indoor ambient - BTUH (kW)*
Outdoor ambient
85°F
(29.4°C)
95°F
(35.0°C)
105°F
(40.6°C)
110°F
(43°C)**
Evaporator Air Flow - Dry Coil (Derate ESP by 0.2 - IN WG (50 Pa) for ET348 and ET360)
External Static Pressure CFM (m
0.0 - IN WG (0.0 Pa) 2030 (3450) 2030 (3450)
0.1 - IN WG (25 Pa) 1910 (3240) 1910 (3240)
0.2 - IN WG (50 Pa) 1770 (3010) 1770 (3010)
0.3 - IN WG (75 Pa) 1650 (2800) 1650 (2800)
0.4 - IN WG (100 Pa) 1520 (2580) 1520 (2580)
0.5 - IN WG (125 Pa) 1390 (2360) 1390 (2360)
Evaporator Air Flow - Wet Coil (Derate ESP by 0.2 - IN WG (50 Pa) for ET348 and ET360)
External Static Pressure CFM (m
0.0 - IN WG (0.0 Pa) 1800 (3060) 1800 (3060)
0.1 - IN WG (25 Pa) 1680 (2850) 1680 (2850)
0.2 - IN WG (50 Pa) 1580 (2680) 1580 (2680)
0.3 - IN WG (75 Pa) 1470 (2500) 1470 (2500)
0.4 - IN WG (100 Pa) 1360 (2310) 1360 (2310)
0.5 - IN WG (125 Pa) 1250 (2120) 1250 (2120)
Evaporator
Motor Hp (kW) 0.50 (0.37) 0.50 (0.37)
Filter Sizes - Quantity in. (cm)
Drain Connection - ID in. 3/8 3/8
Weight - w/o Economizer Ib/kg 470 (213) 470 (213)
Weight - with Economizer Ib/kg 490 (222) 490 (222)
* Based on rated airflow at 0.2 IN WG (50 Pa) external static and no outside air. ** For applications above 110°F (43°C) use high ambient option.
Total 47900 (14.0) 56900 (16.7)
Sensible 35400 (10.4) 38800 (11.4)
Total 45600 (13.4) 53800 (15.8)
Sensible 34600 (10.2) 37700 (11.1)
Total 43100 (12.6) 50700 (14.9)
Sensible 33800 (9.9) 36800 (10.8)
Total 41800 (12.3) 48600 (14.2)
Sensible 33100 (9.7) 35800 (10.5)
Total 44500 (13.0) 52200 (15.3)
Sensible 35000 (10.3) 38200 (11.2)
Total 42300 (12.4) 49800 (14.6)
Sensible 34100 (10.0) 36900 (10.8)
Total 39900 (11.7) 47300 (13.9)
Sensible 33100 (9.7) 35700 (10.4)
Total 38700 (11.3) 44700 (13.1)
Sensible 32600 (9.6) 34900 (10.2)
3
/hr)
3
/hr)
21 x 36.25 x 2 - one
(53.3 x 92 x 5)
21 x 36.25 x 2 - one
(53.3 x 92 x 5)
Specifications
21
Page 28
Specifications
Table 8 Technical data, 50 Hz - Standard ambient condenser
Model ET017 ET023 ET035
Compressor type Scroll Scroll Scroll
Net capacity data based on 26.6°C (80°F) DB/19.4°C (67°F) WB indoor ambient - kW (BTUH)*
Outdoor ambient
29.4°C (85°F)
35.0°C (95°F)
40.6°C
(105°F)
43°C
(110°F**)
Net capacity data based on 23.9°C (75°F) DB 16.9°C (62.5°F) WB indoor ambient - kW (BTUH)*
Outdoor ambient
29.4°C (85°F)
35.0°C (95°F)
40.6°C
(105°F)
43°C
(110°F**)
Evaporator Air Flow - Dry Coil
External Static Pressure m
0.0 Pa (0.0 - IN WG) 1230 (720) 1320 (770) 1840 (1080)
25 Pa (0.1 - IN WG) 1170 (690) 1240 (730) 1730 (1020)
50 Pa (0.2 - IN WG) 1100 (650) 1190 (700) 1600 (940)
75 Pa (0.3 - IN WG) 1060 (620) 1130 (670) 1460 (860)
100 Pa (0.4 - IN WG) - - -
125 Pa (0.5 - IN WG) - - -
Evaporator Air Flow - Wet Coil
External Static Pressure m
0.0 Pa (0.0 - IN WG) 1200 (710) 1290 (760) 1700 (1000)
25 Pa (0.1 - IN WG) 1150 (670) 1220 (720) 1590 (930)
50 Pa (0.2 - IN WG) 1090 (640) 1160 (680) 1460 (860)
75 Pa (0.3 - IN WG) 1020 (600) 1100 (650) 1330 (780)
100 Pa (0.4 - IN WG) - - -
125 Pa (0.5 - IN WG) - - -
Evaporator
Motor kW (Hp) 0.19 (0.25) 0.19 (0.25) 0.19 (0.25)
Filter Sizes - Quantity cm (in.)
Drain Connection - ID in. 3/4 3/4 3/4 (1.9)
Weight - w/o Economizer kg (Ib) 150 (330) 150 (330) 150 (330)
Weight - with Economizer kg (Ib) 159 (350) 159 (350) 159 (350)
* Based on rated airflow at 50 Pa (0.2 IN WG) external static and no outside air. ** For applications above 43°C (110°F) use high ambient option.
Total 5.6 (19200) 6.3 (21500) 8.3 (28200)
Sensible 4.2 (14500) 4.6 (15800) 6.2 (21300)
Total 5.3 (18200) 6.0 (20500) 7.8 (26600)
Sensible 4.1 (14200) 4.5 (15400) 6.1 (20700)
Total 5.1 (17400) 5.7 (19500) 7.3 (24900)
Sensible 4.1 (13900) 4.4 (15000) 5.9 (20000)
Total 4.8 (16300) 5.4 (18400) 7.0 (23900)
Sensible 4.0 (13500) 4.3 (14600) 5.8 (19700)
Total 5.2 (18000) 5.9 (20000) 7.7 (26200)
Sensible 4.1 (14000) 4.5 (15300) 6.2 (21000)
Total 5.0 (17100) 5.6 (19100) 7.2 (24700)
Sensible 4.1 (13800) 4.4 (14900) 6.0 (20400)
Total 4.8 (16200) 5.3 (18100) 6.8 (23300)
Sensible 4.0 (13400) 4.3 (14600) 5.8 (19700)
Total 4.5 (15200) 5.0 (17000) 6.5 (22100)
Sensible 3.9 (13100) 4.1 (14100) 5.7 (19400)
3
/hr (CFM)
3
/hr (CFM)
40.6 x 82.5 x 5 - one (16 x 32.5 x 2)
40.6 x 82.5 x 5 - one (16 x 32.5 x 2)
16 x 32.5 x 2 - one
(40.6 x 82.5 x 5)
22
Page 29
Table 9 Technical data, 50 Hz - Standard ambient condenser, continued
Model ET047, ET347 ET059, ET359
Compressor type Scroll Scroll
Net capacity data based on 26.6°C (80°F) DB/19.4°C (67°F) WB indoor ambient - kW (BTUH)*
Outdoor ambient
29.4°C (85°F)
35.0°C (95°F)
40.6°C
(105°F)
43°C
(110°F**)
Net capacity data based on 23.9°C (75°F) DB/16.9°C (62.5°F) WB indoor ambient - kW (BTUH)*
Outdoor Ambient
29.4°C (85°F)
35.0°C (95°F)
46.1°C
(115°F)**
43°C
(110°F**)
Evaporator Air Flow - Dry Coil (Derate ESP by 0.15 - IN WG (50 Pa) for ET347 and ET359)
External Static Pressure m
0.0 Pa (0.0 - IN WG) 2870 (1690) 2870 (1690)
25 Pa (0.1 - IN WG) 2700 (1590) 2700 (1590)
50 Pa (0.2 - IN WG) 2500 (1470) 2500 (1470)
75 Pa (0.3 - IN WG) 2330 (1370) 2330 (1370)
100 Pa (0.4 - IN WG) - -
125 Pa (0.5 - IN WG) - -
Evaporator Air Flow - Wet Coil (Derate ESP by 0.15 - IN WG (50 Pa) for ET347 and ET359)
External Static Pressure m
0.0 Pa (0.0 - IN WG) 2550 (1500) 2550 (1500)
25 Pa (0.1 - IN WG) 2380 (1400) 2380 (1400)
50 Pa (0.2 - IN WG) 2240 (1320) 2240 (1320)
75 Pa (0.3 - IN WG) 2070 (1220) 2070 (1220)
100 Pa (0.4 - IN WG) - -
125 Pa (0.5 - IN WG) - -
Evaporator
Motor kW (Hp) 0.37 (0.50) 0.37 (0.50)
Filter Sizes - Quantity cm (in.)
Drain Connection - ID in. 3/4 3/4
Weight - w/o Economizer kg (lb) 213 (470) 213 (470)
Weight - with Economizer kg (lb) 222 (490) 222 (490)
* Based on rated airflow at 50 Pa (0.2 IN WG) external static and no outside air. ** For applications above 43°C (110°F) use high ambient option.
Total 11.8 (40400) 14.2 (48500)
Sensible 8.7 (29900) 9.6 (33100)
Total 11.2 (38300) 13.6 (46600)
Sensible 8.6 (29300) 9.5 (32400)
Total 10.6 (36200) 12.9 (44400)
Sensible 8.4 (28600) 9.2 (31600)
Total 10.2 (35100) 12.4 (42200)
Sensible 8.2 (27900) 9.0 (30900)
Total 10.9 (37400) 13.3 (45500)
Sensible 8.6 (29200) 9.5 (32400)
Total 10.4 (35500) 12.7 (43600)
Sensible 8.4 (28400) 9.2 (31600)
Total 9.9 (33600) 12.2 (41600)
Sensible 8.1 (27700) 9.0 (30900)
Total 9.5 (32500) 11.5 (39300)
Sensible 8.0 (27200) 8.8 (30000)
3
/hr (CFM)
3
/hr (CFM)
53.3 x 92 x 5 - one (21 x 36.25 x 2)
53.3 x 92 x 5 - one (21 x 36.25 x 2)
Specifications
23
Page 30
Specifications
Table 10 Technical data, 60 Hz - High ambient condenser
Model ET018 ET024 ET036
Compressor type Scroll Scroll Scroll
Net capacity data based on 80°F (26.6°C) DB/67°F (19.4°C) WB indoor ambient - BTUH (kW)*
Outdoor ambient
85°F
(29.4°C)
95°F
(35.0°C)
105°F
(40.6°C)
115°F
(46.1°C)
Net capacity data based on 75°F (23.9°C) DB/62.5°F (16.9°C) WB indoor ambient - BTUH (kW)*
Outdoor ambient
85°F
(29.4°C)
95°F
(35.0°C)
105°F
(40.6°C)
115°F
(46.1°C)
Evaporator Air Flow - Dry Coil
External Static Pressure CFM (m
0.0 - IN WG (0.0 Pa) 870 (1480) 930 (1580) 1300 (2210)
0.1 - IN WG (25 Pa) 830 (1410) 880 (1500) 1220 (2070)
0.2 - IN WG (50 Pa) 780 (1320) 840 (1430) 1130 (1920)
0.3 - IN WG (75 Pa) 750 (1260) 800 (1360) 1030 (1750)
0.4 - IN WG (100 Pa) 670 (1140) 730 (1240) 920 (1560)
0.5 - IN WG (125 Pa) 590 (1000) 650 (1100) 820 (1390)
Evaporator Air Flow - Wet Coil
External Static Pressure CFM (m
0.0 - IN WG (0.0 Pa) 850 (1440) 910 (1550) 1200 (2040)
0.1 - IN WG (25 Pa) 810 (1380) 860 (1460) 1120 (1900)
0.2 - IN WG (50 Pa) 770 (1310) 820 (1390) 1030 (1750)
0.3 - IN WG (75 Pa) 720 (1220) 780 (1320) 940 (1600)
0.4 - IN WG (100 Pa) 650 (1100) 710 (1210) 850 (1440)
0.5 - IN WG (125 Pa) 570 (970) 620 (1050) 750 (1270)
Evaporator
Motor Hp (kW) 0.25 (0.19) 0.25 (0.19) 0.25 (0.19)
Filter Sizes - Quantity in. (cm)
Drain Connection - ID in. 3/4 3/4 3/4
Weight w/o Economizer Ib (kg) 330 (150) 330 (150) 330 (150)
Weight w/ Economizer Ib (kg) 350 (159) 350 (159) 350 (159)
* Based on rated airflow at 0.2 IN WG (50 Pa) external static and no outside air.
Total 19600 (5.7) 22600 (6.6) 34400 (10.1)
Sensible 15800 (4.6) 17200 (5.0) 24400 (7.2)
Total 18700 (5.5) 21700 (6.4) 32900 (9.6)
Sensible 15500 (4.5) 16900 (5.0) 23800 (6.9)
Total 17700 (5.2) 20700 (6.1) 31300 (9.1)
Sensible 15200 (4.5) 16600 (4.9) 23100 (6.8)
Total 16700 (4.9) 19600 (5.7) 29500 (8.6)
Sensible 15800 (4.7) 16200 (4.8) 22600 (6.7)
Total 18100 (5.3) 20800 (6.1) 32100 (9.4)
Sensible 15200 (4.5) 16800 (4.9) 24100 (7.1)
Total 17200 (5.0) 20000 (5.9) 30700 (9.0)
Sensible 14900 (4.4) 16500 (4.8) 23400 (6.9)
Total 16400 (4.8) 19000 (5.6) 29300 (8.6)
Sensible 15600 (4.6) 16100 (4.7) 22600 (6.6)
Total 15700 (4.6) 18000 (5.3) 27600 (8.1)
Sensible 14900 (4.3) 15700 (4.6) 21900 (6.4)
3
/hr)
3
/hr)
16 x 32.5 x 2 - one
(40.6 x 82.5 x 5)
16 x 32.5 x 2 - one
(40.6 x 82.5 x 5)
16 x 32.5 x 2 - one
(40.6 x 82.5 x 5)
24
Page 31
Table 11 Technical data, 60 Hz - High ambient condenser, continued
Model ET048, ET348 ET060, ET360
Compressor Type Scroll Scroll
Net capacity data based on 80°F (26.6°C) DB/67°F (19.4°C) WB indoor ambient - BTUH (kW)*
Outdoor ambient
85°F
(29.4°C)
95°F
(35.0°C)
105°F
(40.6°C)
115°F
(46.1°C)
Net capacity data based on 75°F (23.9°C) DB/62.5°F (16.9°C) WB indoor ambient - BTUH (kW)*
Outdoor ambient
85°F
(29.4°C)
95°F
(35.0°C)
105°F
(40.6°C)
115°F
(46.1°C)
Evaporator Air Flow - Dry Coil (Derate ESP by 0.2 - IN WG (50 Pa) for ET348 and ET360)
External Static Pressure CFM (m
0.0 - IN WG (0.0 Pa) 2030 (3450) 2030 (3450)
0.1 - IN WG (25 Pa) 1910 (3240) 1910 (3240)
0.2 - IN WG (50 Pa) 1770 (3010) 1770 (3010)
0.3 - IN WG (75 Pa) 1650 (2800) 1650 (2800)
0.4 - IN WG (100 Pa) 1520 (2580) 1520 (2580)
0.5 - IN WG (125 Pa) 1390 (2360) 1390 (2360)
Evaporator Air Flow - Wet Coil (Derate ESP by 0.2 - IN WG (50 Pa) for ET348 and ET360)
External Static Pressure CFM (m
0.0 - IN WG (0.0 Pa) 1800 (3060) 1800 (3060)
0.1 - IN WG (25 Pa) 1680 (2850) 1680 (2850)
0.2 - IN WG (50 Pa) 1580 (2680) 1580 (2680)
0.3 - IN WG (75 Pa) 1470 (2500) 1470 (2500)
0.4 - IN WG (100 Pa) 1360 (2310) 1360 (2310)
0.5 - IN WG (125 Pa) 1250 (2120) 1250 (2120)
Evaporator
Motor Hp (kW) 0.50 (0.37) 0.50 (0.37)
Filter Sizes - Quantity in. (cm)
Drain Connection - ID in. 3/8 3/8
Weight - w/o Economizer Ib/kg 470 (213) 470 (213)
Weight - with Economizer Ib/kg 490 (222) 490 (222)
* Based on rated airflow at 0.2 IN WG (50 Pa) external static and no outside air.
Total 49200 (14.4) 59000 (17.3)
Sensible 35800 (10.5) 39600 (11.6)
Total 46900 (13.8) 55900 (16.4)
Sensible 35000 (10.3) 38400 (11.3)
Total 44400 (13.0) 52700 (15.5)
Sensible 34100 (10.0) 37100 (10.9)
Total 41800 (12.3) 49100 (14.4)
Sensible 33100 (9.7) 35800 (10.5)
Total 45500 (13.3) 54000 (15.8)
Sensible 35400 (10.4) 38900 (11.4)
Total 43400 (12.7) 51200 (15.0)
Sensible 34500 (10.1) 37700 (11.1)
Total 41100 (12.1) 48100 (14.1)
Sensible 33600 (9.9) 36500 (10.7)
Total 38700 (11.3) 44800 (13.1)
Sensible 32600 (9.6) 35100 (10.3)
3
/hr)
3
/hr)
21 x 36.25 x 2 - one
(53.3 x 92 x 5)
21 x 36.25 x 2 - one
(53.3 x 92 x 5)
Specifications
25
Page 32
Specifications
Table 12 Technical data, 50 Hz - High ambient condenser
Model ET017 ET023 ET035
Compressor type Scroll Scroll Scroll
Net capacity data based on 26.6°C (80°F) DB/19.4°C (67°F) WB indoor ambient - kW (BTUH)*
Outdoor ambient
29.4°C (85°F)
35.0°C (95°F)
40.6°C
(105°F)
(46.1°C)
115°F
Net capacity data based on 23.9°C (75°F) DB 16.9°C (62.5°F) WB indoor ambient - kW (BTUH)*
Outdoor ambient
29.4°C (85°F)
35.0°C (95°F)
40.6°C
(105°F)
(46.1°C)
115°F
Evaporator Air Flow - Dry Coil
External Static Pressure m
0.0 Pa (0.0 - IN WG) 1230 (720) 1320 (770) 1840 (1080)
25 Pa (0.1 - IN WG) 1170 (690) 1240 (730) 1730 (1020)
50 Pa (0.2 - IN WG) 1100 (650) 1190 (700) 1600 (940)
75 Pa (0.3 - IN WG) 1060 (620) 1130 (670) 1460 (860)
100 Pa (0.4 - IN WG) - - -
125 Pa (0.5 - IN WG) - - -
Evaporator Air Flow - Wet Coil
External Static Pressure m
0.0 Pa (0.0 - IN WG) 1200 (710) 1290 (760) 1700 (1000)
25 Pa (0.1 - IN WG) 1150 (670) 1220 (720) 1590 (930)
50 Pa (0.2 - IN WG) 1090 (640) 1160 (680) 1460 (860)
75 Pa (0.3 - IN WG) 1020 (600) 1100 (650) 1330 (780)
100 Pa (0.4 - IN WG) - - -
125 Pa (0.5 - IN WG) - - -
Evaporator
Motor kW (Hp) 0.19 (0.25) 0.19 (0.25) 0.19 (0.25)
Filter Sizes - Quantity cm (in.)
Drain Connection - ID in. 3/4 3/4 3/4 (1.9)
Weight - w/o Economizer kg (Ib) 150 (330) 150 (330) 150 (330)
Weight - with Economizer kg (Ib) 159 (350) 159 (350) 159 (350)
* Based on rated airflow at 50 Pa (0.2 IN WG) external static and no outside air.
Total 5.6 (19200) 6.4 (21900) 8.6 (29200)
Sensible 4.2 (14500) 4.6 (15800) 6.3 (21600)
Total 5.3 (18200) 6.1 (20800) 8.1 (27700)
Sensible 4.1 (14200) 4.5 (15400) 6.2 (21100)
Total 5.1 (17400) 5.7 (19600) 7.6 (26000)
Sensible 4.1 (13900) 4.4 (15000) 6.0 (20500)
Total 4.8 (16300) 5.4 (18300) 7.1 (24100)
Sensible 4.0 (13500) 4.3 (14600) 5.8 (19800)
Total 5.2 (18000) 5.9 (20200) 7.9 (27100)
Sensible 4.1 (14000) 4.5 (15400) 6.3 (21400)
Total 5.0 (17100) 5.6 (19200) 7.5 (25600)
Sensible 4.1 (13800) 4.4 (15000) 6.1 (20800)
Total 4.8 (16200) 5.3 (18100) 7.1 (24100)
Sensible 4.0 (13400) 4.3 (14600) 5.9 (20200)
Total 4.5 (15200) 4.9 (17000) 6.5 (22300)
Sensible 3.9 (13100) 4.1 (14100) 5.7 (19500)
3
/hr (CFM)
3
/hr (CFM)
40.6 x 82.5 x 5 - one (16 x 32.5 x 2)
40.6 x 82.5 x 5 - one (16 x 32.5 x 2)
16 x 32.5 x 2 - one
(40.6 x 82.5 x 5)
26
Page 33
Table 13 Technical data, 50 Hz - High ambient condenser, continued
Model ET047, ET347 ET059, ET359
Compressor type Scroll Scroll
Net capacity data based on 26.6°C (80°F) DB/19.4°C (67°F) WB indoor ambient - kW (BTUH)*
Outdoor ambient
29.4°C (85°F)
35.0°C (95°F)
40.6°C
(105°F)
(46.1°C)
115°F
Net capacity data based on 23.9°C (75°F) DB/16.9°C (62.5°F) WB indoor ambient - kW (BTUH)*
Outdoor Ambient
29.4°C (85°F)
35.0°C (95°F)
46.1°C
(115°F)**
(46.1°C)
115°F
Evaporator Air Flow - Dry Coil (Derate ESP by 0.15 - IN WG (50 Pa) for ET347 and ET359)
External Static Pressure m
0.0 Pa (0.0 - IN WG) 2870 (1690) 2870 (1690)
25 Pa (0.1 - IN WG) 2700 (1590) 2700 (1590)
50 Pa (0.2 - IN WG) 2500 (1470) 2500 (1470)
75 Pa (0.3 - IN WG) 2330 (1370) 2330 (1370)
100 Pa (0.4 - IN WG) - -
125 Pa (0.5 - IN WG) - -
Evaporator Air Flow - Wet Coil (Derate ESP by 0.15 - IN WG (50 Pa) for ET347 and ET359)
External Static Pressure m
0.0 Pa (0.0 - IN WG) 2550 (1500) 2550 (1500)
25 Pa (0.1 - IN WG) 2380 (1400) 2380 (1400)
50 Pa (0.2 - IN WG) 2240 (1320) 2240 (1320)
75 Pa (0.3 - IN WG) 2070 (1220) 2070 (1220)
100 Pa (0.4 - IN WG) - -
125 Pa (0.5 - IN WG) - -
Evaporator
Motor kW (Hp) 0.37 (0.50) 0.37 (0.50)
Filter Sizes - Quantity cm (in.)
Drain Connection - ID in. 3/4 3/4
Weight - w/o Economizer kg (lb) 213 (470) 213 (470)
Weight - with Economizer kg (lb) 222 (490) 222 (490)
* Based on rated airflow at 50 Pa (0.2 IN WG) external static and no outside air. ** For applications above 43°C (110°F) use high ambient option.
Total 12.1 (41400) 14.6 (50000)
Sensible 8.8 (30000) 9.7 (33200)
Total 11.5 (39500) 13.8 (47400)
Sensible 8.6 (29300) 9.5 (32400)
Total 10.9 (37400) 13.1 (44700)
Sensible 8.4 (28600) 9.2 (31600)
Total 10.3 (35200) 12.4 (42200)
Sensible 8.2 (27900) 9.0 (30900)
Total 11.2 (38400) 13.4 (45800)
Sensible 8.7 (29600) 9.6 (32700)
Total 10.7 (36500) 12.7 (43600)
Sensible 8.4 (28800) 9.3 (31700)
Total 10.1 (34600) 12.2 (41600)
Sensible 8.2 (28100) 9.0 (30900)
Total 9.6 (32600) 11.5 (39300)
Sensible 8.0 (27200) 8.8 (30000)
3
/hr (CFM)
3
/hr (CFM)
53.3 x 92 x 5 - one (21 x 36.25 x 2)
53.3 x 92 x 5 - one (21 x 36.25 x 2)
Specifications
27
Page 34
Table 14 Optional heater capacity, 60 Hz
Heater Capacity - kW
Nominal Heater Rating
5 kW
Capacity @ 208V-1ph 3.756 3.756 3.756 3.756 3.756 Capacity @ 230V-1ph 4.592 4.592 4.592 4.592 4.592 Capacity @ 240V-1ph 5.000 5.000 5.000 5.000 5.000 Capacity @ 208V-3ph n/a 3.756 3.756 3.756 3.756 Capacity @ 230V-3ph n/a 4.592 4.592 4.592 4.592 Capacity @ 240V-3ph n/a 5.000 5.000 5.000 5.000 Capacity @ 460V-3ph n/a 4.592 4.592 4.592 4.592 Capacity @ 480V-3ph n/a 5.000 5.000 5.000 5.000
10 kW
Capacity @ 208V-1ph 7.511 7.511 7.511 7.511 7.511 Capacity @ 230V-1ph 9.184 9.184 9.184 9.184 9.184 Capacity @ 240V-1ph 10.000 10.000 10.000 10.000 10.000 Capacity @ 208V-3ph n/a 7.511 7.511 7.511 7.511 Capacity @ 230V-3ph n/a 9.184 9.184 9.184 9.184 Capacity @ 240V-3ph n/a 10.000 10.000 10.000 10.000 Capacity @ 460V-3ph n/a 9.184 9.184 9.184 9.184 Capacity @ 480V-3ph n/a 10.000 10.000 10.000 10.000
15 kW
Capacity @ 208V-1ph n/a n/a 11.267 11267 11267 Capacity @ 230V-1ph n/a n/a 13.776 13776 13776 Capacity @ 240V-1ph n/a n/a 15.000 15.000 15.000 Capacity @ 208V-3ph n/a n/a 11.267 11.267 11.267 Capacity @ 230V-3ph n/a n/a 13.776 13.776 13.776 Capacity @ 240V-3ph n/a n/a 15.000 15.000 15.000 Capacity @ 460V-3ph n/a n/a 13.776 13.776 13.776 Capacity @ 480V-3ph n/a n/a 15.000 15.000 15.000
1.5 Ton 2 Ton 3 Ton 4 Ton 5 Ton
Specifications
Table 15 Optional heater capacity, 50 Hz
Heater Capacity - kW
Nominal Heater Rating
5 kW
Capacity @ 220V-1ph 4.201 4.201 4.201 4.201 4.201 Capacity @ 240V-1ph 5.000 5.000 5.000 5.000 5.000 Capacity @ 200V-3ph 3.472 3.472 3.472 3.472 3.472 Capacity @ 230V-3ph n/a 4.592 4.592 4.592 4.592 Capacity @ 240V-3ph n/a 5.000 5.000 5.000 5.000 Capacity @ 380V-3ph n/a 4.192 4.192 4.192 4.192 Capacity @ 415V-3ph n/a 5.000 5.000 5.000 5.000
10 kW
Capacity @ 220V-1ph 8.403 8.403 8.403 8.403 8.403 Capacity @ 240V-1ph 10.000 10.000 10.000 10.000 10.000 Capacity @ 200V-3ph n/a 6.944 6.944 6.944 6.944 Capacity @ 230V-3ph n/a 9.184 9.184 9.184 9.184 Capacity @ 240V-3ph n/a 10.000 10.000 10.000 10.000 Capacity @ 380V-3ph n/a 8.384 8.384 8.384 8.384 Capacity @ 415V-3ph n/a 10.000 10.000 10.000 10.000
15 kW
Capacity @ 220V-1ph n/a n/a 12.604 12.604 12.604 Capacity @ 240V-1ph n/a n/a 15.000 15.000 15.000 Capacity @ 200V-3ph n/a n/a 10.417 10.417 10.417 Capacity @ 230V-3ph n/a n/a 13.776 13.776 13.776 Capacity @ 240V-3ph n/a n/a 15.000 15.000 15.000 Capacity @ 380V-3ph n/a n/a 12.577 12.577 12.577 Capacity @ 415V-3ph n/a n/a 15.000 15.000 15.000
1.5 Ton 2 Ton 3 Ton 4 Ton 5 Ton
28
Page 35
Specifications
Table 16 Electrical data, 60 Hz - amps
15 kW Heat*
No Heat 5 kW Heat 10 kW Heat
Model Volts Phase
FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
ET0187 208/230 1 14.5 17.2 25 23.4 29.3 30 44.4 55.5 60 NA
ET0247 208/230 1 15.2 18.1 30 23.4 29.3 30 44.4 55.5 60 NA
ET0247 208/230 3 11.7 13.7 20 14.4 18 20 26.4 33 35 NA
ET0247 460 3 5.9 6.9 15 7.3 9.1 15 13.3 16.6 20 NA
ET0367 208/230 1 19.5 23.4 40 23.4 29.3 40 44.4 55.5 60 44.4 55.5 60 21 26.3 30
ET0367 208/230 3 15.2 18.1 30 15.2 18.1 30 26.4 33 35 38.4 48 50
ET0367 460 3 7.7 9.1 15 7.7 9.1 15 13.3 16.6 20 19.3 24.1 25
ET0487 ET3487
ET0487 ET3487
ET0487 ET3487
ET0607 ET3607
ET0607 ET3607
ET0607 ET3607
* 15 kW heat option @ 208/230 - 1 phase requires two electrical feeds. Circuit 1 supplies the compressor, condenser, 10 kW heat and the evaporator motor. Circuit 2 supplies the remaining 5 kW heat.
208/230 1 31.9 38 50 31.9 38 50 46.2 57.8 60 46.2 57.8 60 21 26.3 30
208/230 3 21.9 25.5 35 21.9 25.5 35 28.2 35.3 35 40.2 50.3 60
460 3 11 12.8 20 11 12.8 20 14.1 17.6 20 20.1 25.1 30
208/230 1 37.7 45.2 60 37.7 45.2 60 46.2 57.8 60 46.2 57.8 60 21 26.3 30
208/230 3 28.3 33.5 50 28.3 33.5 50 28.3 35.3 50 40.2 50.3 50
460 3 13.8 16.3 25 13.8 16.3 25 14.1 17.6 25 20.1 25.1 30
Circ1 Circ2
29
Page 36
Specifications
Table 17 Electrical data, 50 Hz - amps
15 kW Heat*
No Heat 5 kW Heat 10 kW Heat
Model Volts Phase
FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD FLA WSA OPD
ET0177 220/240 1 13.8 16.3 25 23.4 29.3 30 44.4 55.5 60 NA
ET0237 220/240 1 15.2 18.1 30 23.4 29.3 30 44.4 55.5 60 NA
ET0237 380/415 3 6.3 7.4 15 8.3 10.4 15 15.3 19.1 20 NA
ET0357 220/240 1 17.4 20.8 35 23.4 29.3 35 44.4 55.5 60 44.4 55.5 60 21 26.3 30
ET0357 200/230 3 14.5 17.2 25 14.5 18 25 26.4 33 35 38.4 48 50
ET0357 380/415 3 7.7 9.1 15 8.3 10.4 15 15.3 19.1 20 22.3 27.9 30
ET0477 ET3477
ET0477 ET3477
EF0597 ET3597
ET0597 ET3597
* 15 kW heat option @ 220/240 - 1 phase requires two electrical feeds. Circuit 1 supplies the compressor, condenser, 10 kW heat and the evaporator motor. Circuit 2 supplies the remaining 5 kW heat.
200/230 3 21.9 25.5 35 21.9 25.5 35 28.2 35.3 35 40.2 50.3 60
380/415 3 11 12.8 20 11 12.8 20 16.1 20.1 25 23.1 28.9 30
200/230 3 28.3 33.5 50 28.3 33.5 50 28.3 35.3 50 40.2 50.3 50
380/415 3 13.8 16.3 25 13.8 16.3 25 16.1 20.1 20 23.1 28.9 30
Circ1 Circ2
30
Page 37
8.0 TROUBLESHOOTING
Table 18 Troubleshooting guide
Problem Probable Cause Remedy
Unit will not start No power to unit Check voltage to input circuit breaker.
Control voltage circuit breaker open
Shut off by external thermostat or stat is defective
No cooling Low refrigerant
Unit cycles on high pressure switch
Heat does not operate No voltage output
charge
Compressor contactor not pulling in
No output from thermostat
Loss or restriction of air flow
Defective fan cycling control
from thermostat
Fuseable link blown Check for open and replace.
Bad contactor Check for open and replace.
Locate short and reset breaker.
Check operation of thermostat.
Check with gauges.
Check voltage at contactor. If not present refer to print and determine voltage loss. Check enthalpy sensor for full CCW or D setting.
Check operation of stat. Should have voltage output to Y terminal during cooling.
Check condenser blower assembly for proper operation. Check for dirty coil or inlet grille restriction.
Switch should make @ 240 PSIG ±10 (1655 kPa ±68.9). (Check settings on adjustable switch when supplied.)
Check stat for proper output to W terminal.
Troubleshooting
31
Page 38
9.0 MAINTENANCE INSPECTION CHECKLIST
Liebert InteleCool2
Date:__________________________ Prepared by:___________________________________
Model #:________________________ Serial #: ______________________________________
Monthly
Filters
___ 1. Unrestricted air flow
___ 2. Check filter
___ 3. Wipe section clean
Fan Section
___ 1. Impellers free of debris
___ 2. Bearings free
Economizer
___ 1. Check damper for tightness and wear
Semiannually
Maintenance Inspection Checklist
Compressor Section
___ 1. Check for leaks
___ 2. Vibration isolation
Air Cooled Condenser
___ 1. Condenser coil clean
___ 2. Motor mount tight
___ 3. Bearings free
___ 4. Refrigerant lines properly supported
Refrigeration Cycle
___ 1. Check suction pressure
___ 2. Check head pressure
___ 3. Check superheat
___ 4. Evaporator coil clean
___ 5. Insulation intact
Electric Panel
___ 1. Check electrical connections
___ 2. Check operational sequences
Notes:
Signature _________________________________________________________
Make photocopies of this form for your records
32
Page 39
10.0 PARTS
Table 19 Refrigeration system parts, 1.5 and 2 ton units
1.5 Ton 2 Ton
ET017S ET018P ET023S ET023M ET024P ET024Y ET024A
Figure
No.
Run capacitor, scroll comp
7-7 Cap. 30μF, 370V 1A19537P1 1 N/A N/A N/A
7-7 Cap. 40μF, 370V 1A19538P1 1 1 N/A 1 N/A N/A
Compressors, scroll
7-6 Comp. 220/240-1 156204P1 1
7-6 Comp. 200/230-1 159146P1 1
7-6 Comp. 220/240-1 138493P2 1
7-6 Comp. 380/460-3 148324P2 1
7-6 Comp. 200/230-1 159145P1 1
7-6 Comp. 208/230-3 159148P1 1
7-6 Comp. 380/460-3 159148P2 1
Pressure switches
High pressure - 400 psi 159482P1 1 1 1 1 1 1 1
Fan cycle switch - 170 psi 159483P1 Optional feature - quantity 1 (as required)
Low pressure - 35 psi 159484P1 Optional feature - quantity 1 (as required)
Adj Pr Sw for Adj FCC P67-0110 Optional feature - quantity 1 (as required)
Filter drier 127185P1 1 1 1 1 1 1 1
7-10 Condenser coil- 1.5/3T 159118P1 1 1 1 1 1 1 1
9-1 Evaporator coil-1.5/2T 159200P1 1 1 1 1 1 1 1
9-1 Thermal expansion valve-1.5T 1C19507P3 1 1
9-1 Thermal expansion valve-2T 1C19507P1 1 1 1 1 1
Crankcase heaters
7-9 Strap style 240V recips 159202P1 1 1 1 1 1
7-9 Strap style 480V recips 159202P2 1 1
Retainer plug 159136P1 1 1 1 1 1 1 1
14-1 Soft start kit 1C19540P1 Optional feature - quantity 1 (as required)
Part Name/
Description Part #
220-240V
1Ph 50Hz
208-230V
1Ph 60Hz
220-240V
1Ph 50Hz
380-415V
3Ph 50Hz
208-230V
1Ph 60Hz
208-230V
3Ph 60Hz
3Ph 60Hz
Parts
460V
33
Page 40
Table 20 Refrigeration system parts, 3 ton units
3 Ton
ET035S ET035N ET035M ET036P ET036Y ET036A
Figure
No.
Compressors, scroll
7-6 Comp. 220/240-1 148221P2 1
7-6 Comp. 208/230-3 148325P1 1 1
7-6 Comp. 380/460-3 148325P2 1 1
7-6 Comp. 200/230-1 159149P1 1
Pressure switches
High pressure - 400 psi 159482P1 1 1 1 1 1 1
Fan cycle switch - 170 psi 159483P1 Optional feature—quantity 1 (as required)
Low pressure - 35 psi 159484P1 Optional feature—quantity 1 (as required)
Adj Pr Sw for Adj FCC P67-0110 Optional feature—quantity 1 (as required)
Filter drier 127185P1 1 1 1 1 1 1
7-10 Condenser coil - 1.5/3T 159118P1 1 1 1 1 1 1
9-1 Evaporator coil - 3T 159180P1 1 1 1 1 1 1
9-1 Thermal expansion valve - 3T 1C19507P2 1 1 1 1 1 1
Crankcase Heaters
7-9 Strap style 240V scrolls 132102P1 1 1 1 1
7-9 Strap style 480V scrolls 132102P2 1 1
Retainer plug 159136P1 1 1 1 1 1 1
14-1 Soft start kit 1C19540P1 Optional feature—quantity 1 (as required)
Part Name / Description Part #
220-240V 1Ph 50Hz
200-240V 3Ph 50Hz
380-415V 3Ph 50Hz
208-230V
1Ph 60Hz
208-230V 3Ph 60Hz
Parts
460V
3Ph 60Hz
34
Page 41
Table 21 Refrigeration system parts, 4-ton units
4 Ton
ET047N ET347N
Figure
No.
Run capacitor, scroll comp
7-7 Cap. 40μF, 370V 1A19538P1 N/A N/A 1 N/A N/A
Compressors, scroll
7-6 Comp. 208/230-3 159153P1 1 1
7-6 Comp. 380/460-3 159153P2 1 1
7-6 Comp. 200/230-1 159152P1 1
Pressure switches
High pressure - 400 psi 159482P1 1 1 1 1 1
Fan cycle switch - 170 psi 159483P1 Optional feature - quantity 1 (as required)
Low Pressure - 35 psi 159484P1 Optional feature - quantity 1 (as required)
Adj Pr Sw for Adj FCC P67-0110 Optional feature - quantity 1 (as required)
Filter drier 128177P1 1 1 1 1 1
7-10 Condenser coil - 4/5T 159235P1 1 1 1 1 1
9-1 Evaporator coil - 4/5T 159237P1 1 1 1 1 1
9-1 Thermal expansion valve - 4T 159264P1 1 1 1 1 1
Crankcase heaters
7-9 Strap style 240V scrolls 132102P1 1 1 1
7-9 Strap style 480V scrolls 132102P2 1 1
14-1 Soft start kit 1C19540P1 Optional feature - quantity 1 (as required)
Part Name/
Description Part #
200-230V 3Ph 50Hz
ET047M ET347M
380-415V 3Ph 50Hz
ET048P ET348P
208-230V 1Ph 60Hz
ET048Y ET348Y
208-230V 3Ph 60Hz
Parts
ET048A ET348A
460V
3Ph 60Hz
35
Page 42
Table 22 Refrigeration system parts, 5-ton units
5 Ton
ET059N ET359N
Figure
No.
Run capacitor, scroll comp
7-7 Cap. 60μF, 370V E13-2430 N/A N/A 1 N/A N/A
Compressors, scroll
7-6 Comp. 200/240-3 132101P2 1 1
7-6 Comp. 380/460-3 132101P3 1 1
7-6 Comp. 200/230-1 132101P1 1
Pressure switches
High pressure - 400 psi 159482P1 1 1 1 1 1
Fan cycle switch - 170 psi 159483P1 Optional feature - quantity 1 (as required)
Low Pressure - 35 psi 159484P1 Optional feature - quantity 1 (as required)
Adj Pr Sw for Adj FCC P67-0110 Optional feature - quantity 1 (as required)
Filter drier 128177P1 1 1 1 1 1
7-10 Condenser coil - 4/5T 159235P1 1 1 1 1 1
9-1 Evaporator coil - 4/5T 159237P1 1 1 1 1 1
9-1 Thermal expansion valve - 5T 159264P2 1 1 1 1 1
Crankcase heaters
7-9 Strap style 240V scrolls 132102P1 1 1 1
7-9 Strap style 480V scrolls 132102P2 1 1
14-1 Soft start kit 1C19540P1 Optional feature - quantity 1 (as required)
Part Name/
Description Part #
200-230V 3Ph 50Hz
ET059M ET359M
380-415V 3Ph 50Hz
ET060P ET360P
208-230V
1Ph 60Hz
ET060Y ET360Y
208-230V
3Ph 60
Parts
ET060A ET360Y
460V
3Ph 60Hz
36
Page 43
Table 23 Electric panel, 1.5- and 2-ton units
1.5 Ton 2 Ton
ET017S ET018P ET023S ET023M ET024P ET024Y ET024A
Figure
No.
10-3 Transformer 208/230V 159463P1 1 1 1 1 1
10-3 Transformer 360/460V 159463P2 1 1
Circuit breakers
10-1 No heat 138457P7 138457P3 138457P3 147957P8 138457P3 147957P7 147957P8
10-1 5 kW heat 138457P5 138457P5 138457P5 147957P8 138457P5 147957P7 147957P8
10-1 10 kW heat 138457P2 138457P2 138457P2 147957P1 138457P2 147957P10 147957P1
10-1 15 kW heat N/A N/A N/A N/A N/A N/A N/A
10-1A Heater breaker N/A N/A N/A N/A N/A N/A N/A
Circuit breakers - scrolls
10-1 No heat 138457P3 138457P3 138457P5 147957P8 138457P5 147957P7 147957P8
10-1 5 kW heat 138457P5 138457P5 138457P5 147957P8 138457P5 147957P7 147957P8
10-1 10 kW heat 138457P2 138457P2 138457P2 147957P1 138457P2 147957P10 147957P1
10-1 15 kW heat N/A N/A N/A N/A N/
10-1A Heater breaker N/A N/A N/A N/A N/A N/A N/A
Contactor, compressor
10-4 2 pole E-013A 1 1 1 1
10-4 3 pole 124501P1 1 1 1
Contactor, heater, 5 kW
10-9 2 pole E-013A 1 1 1 1
10-9 3 pole 124501P1 1 1 1
Contactor, heater, 10 kW
10-9 2 pole E-011C 1 1 1 1
10-9 3 pole 124501P1 1 1
10-9 3 pole E-0110 1
10-6 Contactor evaporator fan E-0130 1 1 1 1 1
10-6 Contactor evaporator fan E-013A 1 1
10-7 Contactor, condenser fan E-013A 1 1
10-8 Time delay relay, anticycle 148089P1 1 1 1 1 1 1 1
10-16 Heater interlock relay E03-0170 1 1
10-10 Terminal strip, 10 position 159468P1 1 1 1 1 1 1 1
Wall thermostat, 1 stage 138968P1 1 1 1 1 1 1 1
Thermostat base 138940P1 1 1 1 1 1 1 1
Optional features
10-13 Time delay relay, LP bypass 138491P1 Optional feature - quantity 1 (as required)
10-12 Economizer relay E03-0170 Optional feature - quantity 1 (as required)
10-11 Lockout relay E-0130 Optional feature - quantity 1 (as required)
Common alarm assembly
13-1 Air flow switch B02-0190 Optional feature - quantity 1 (as required)
13-2 T/D relay E-3530 Optional feature - quantity 1 (as required)
13-3 Relay R1 E03-0170 Optional feature - quantity 1 (as required)
13-4 Relay R2 E03-0170 Optional feature - quantity 1 (as required)
13-5 Thermostat E-0230 Optional feature - quantity 1 (as required)
Part Name / Description Part #
220-240V
1Ph 50Hz
208-230V
1Ph 60Hz
220-240V
1Ph 50Hz
380-415V
3Ph 50Hz
208-230V
1Ph 60Hz
208-230V
3Ph 60Hz
AN/AN/A
3Ph 60Hz
460V
Parts
37
Page 44
Table 24 Electric panel parts, 3-ton units
3 Ton
ET035S ET035N ET035M ET036P ET036Y ET036A
Figure
No.
10-3 Transformer 208/230V 159463P1 1 1 1 1
10-3 Transformer 360/460V 159463P2 1 1
Circuit breakers
10-1 No heat 138457P1 147957P5 147957P8 138457P8 147957P5 147957P8
10-1 5 kW heat 138457P1 147957P5 147957P8 138457P8 147957P5 147957P8
10-1 10 kW heat 138457P2 147957P10 147957P1 138457P2 147957P10 147957P1
10-1 15 kW heat 138457P2 147957P3 147957P2 138457P2 147957P3 147957P11
10-1A Heater breaker 138457P5 N/A N/A 138457P5 N/A N/A
Circuit breakers - scrolls
10-1 No heat 138457P9 147957P9 147957P8 138457P1 147957P5 147957P8
10-1 5 kW heat 138457P9 147957P9 147957P8 138457P1 147957P5 147957P8
10-1 10 kW heat 138457P2 147957P10 147957P1 138457P2 147957P10 147957P1
10-1 15 kW heat 138457P2 147957P3 147957P2 138457P2 147957P3 147957P11
10-1A Heater breaker 138457P5 N/A N/A 138457P5 N/A N/A
Contactor, compressor
10-4 2 pole E-011B 1 1
10-4 3 pole 124501P1 1 1
10-4 3 pole E-0110 1 1
Contactor, heater, 5 kW
10-9 2 pole E-013A 1 1
10-9 3 pole 124501P1 1 1 1 1
Contactor, heater, 10 kW
10-9 2 pole E-011C 1 1
10-9 3 pole 124501P1 1 1
9 3 pole E-0110 1 1
10-
Contactor, heater, 15 kW
10-15 2 pole E-013A 1 1
10-9 2 pole E-011C 1 1
10-9 3 pole E-0110 1 1
10-9 3 pole E-009F 1 1
10-6 Contactor evaporator fan E-0130 1 1 1 1
10-6 Contactor evaporator fan E-013A 1 1
10-7 Contactor, condenser fan E-013A 1 1
10-8 Time delay relay, anticycle 148089P1 1 1 1 1 1 1
10-16 Heater interlock relay E03-0170 1 1
10-10 Terminal strip, 10 position 159468P1 1 1 1 1 1 1
Wall thermostat, 1 stage 138968P1 1 1 1 1 1 1
Thermostat base 138940P1 1 1 1 1 1 1
Optional features
10-13 Time delay relay, LP bypass 138491P1 Optional feature - quantity 1 (as required)
10-12 Economizer relay E03-0170 Optional feature - quantity 1 (as required)
10-11 Lockout relay E-0130 Optional feature - quantity 1 (as required)
Common alarm assembly
13-1 Air flow switch B02-0190 Optional feature - quantity 1 (as required)
13-2 T/D relay E-3530 Optional feature - quantity 1 (as required)
13-3 Relay R1 E03-0170 Optional feature - quantity 1 (as required)
13-4 Relay R2 E03-0170 Optional feature - quantity 1 (as required)
13-5 Thermostat E-0230 Optional feature - quantity 1 (as required)
Part Name / Description Part #
220-240V 1Ph 50Hz
200-240V 3Ph 50Hz
380-415V 3Ph 50Hz
208-230V
1Ph 60Hz
208-230V
3Ph 60Hz 3
460V
3Ph 60Hz
Parts
38
Page 45
Parts
Table 25 Electric panel parts, 4-ton unit
4 Ton
ET047N ET347N
Figure
No.
10-3 Transformer 208/230V 159463P1 1 1 1
10-3 Transformer 360/460V 159463P2 1 1
Circuit breakers - scrolls
10-1 No heat 147957P10 147957P1 138457P4 147957P10 147957P1
10-1 5 kW heat 147957P10 147957P1 138457P4 147957P10 147957P1
10-1 10 kW heat 147957P10 147957P11 138457P2 147957P10 147957P1
10-1 15 kW heat 147957P6 147957P2 138457P2 147957P6 147957P2
10-1A Heater breaker N/A N/A 138457P5 N/A N/A
Contactor, compressor
10-4 2 pole E-011C 1
10-4 3 pole 124501P1 1 1
10-4 3 pole E-0110 1 1
Contactor, heater, 5 kW
10-9 2 pole E-013A 1 1
10-9 3 pole 124501P1 1 1 1
Contactor, heater, 10 kW
10-9 2 pole E-011C 1 1
10-9 3 pole 124501P1 1 1
10-9 3 pole E-0110 1
Contactor, heater, 15 kW
10-15 2 pole E-013A 1
10-9 2 pole E-011C 1
10-9
10-9 3 pole E-009F 1 1
10-6 Contactor evaporator fan E-0130 1 1 1
10-6 Contactor evaporator fan E-013A 1 1
10-7 Contactor, condenser fan E-013A 1 1
10-8 Time delay relay, anticycle 148089P1 1 1111
10-16 Heater interlock relay E03-0170 1 1
10-10 Terminal strip, 10 position 159468P1 1 1111
10-13 Time delay relay, LP bypass 138491P1 Optional feature - quantity 1 (as required)
10-12 Economizer relay E03-0170 Optional feature - quantity 1 (as required)
10-11 Lockout relay E-0130 Optional feature - quantity 1 (as required)
13-1 Air flow switch B02-0190 Optional feature - quantity 1 (as required)
13-2 T/D relay E-3530 Optional feature - quantity 1 (as required)
13-3 Relay R1 E03-0170 Optional feature - quantity 1 (as required)
13-4 Relay R2 E03-0170 Optional feature - quantity 1 (as required)
13-5 Thermostat E-0230 Optional feature - quantity 1 (as required)
3 pole E-0110 1 1
Wall thermostat, 1 stage 138968P1 1 1111
Thermostat base 138940P1 1 1111
Optional features
Common alarm assembly
Part Name / Description Part #
200-230V 3Ph 50Hz
ET047M ET347M
380-415V
3Ph 50Hz
ET048P ET348P
208-230V 1Ph 60Hz
ET048Y ET348Y
208-230V 3Ph 60Hz
ET048A ET348A
460V
3Ph 60Hz
39
Page 46
Table 26 Electric panel parts, 5-ton unit
5 Ton
ET059N ET359N
Figure
No.
10-3 Transformer 208/230V 159463P1 1 1 1
10-3 Transformer 360/460V 159463P2 1 1
Circuit breakers - scrolls
10-1 No heat 147957P3 147957P11 138457P2 147957P3 147957P11
10-1 5 kW heat 147957P3 147957P11 138457P2 147957P3 147957P11
10-1 10 kW heat 147957P3 147957P11 138457P2 147957P3 147957P11
10-1 15 kW heat 147957P3 147957P2 138457P2 147957P3 147957P2
10-1A Heater breaker N/A N/A 138457P5 N/A N/A
Contactor, compressor
10-4 2 pole E-011C 1
10-4 3 pole 124501P1 1 1
10-4 3 pole E-0110 1 1
Contactor, heater, 5 kW
10-9 2 pole E-013A 1
10-9 3 pole 124501P1 1 1 1 1
Contactor, heater, 10 kW
10-9 2 pole E-011C 1
10-9 3 pole 124501P1 1 1
10-9 3 pole E-0110 1 1
Contactor, heater, 15 kW
10-15 2 pole E-013A 1
2 pole E-011C 1
10-9
10-9 3 pole E-0110 1 1
10-9 3 pole E-009F 1 1
10-6 Contactor evaporator fan E-0130 1 1 1
10-6 Contactor evaporator fan E-013A 1 1
10-7 Contactor, condenser fan E-013A 1 1
10-8 Time delay relay, anticycle 148089P1 1 1 1 1 1
10-16 Heater interlock relay E-0130 1 1
10-10 Terminal strip, 10 position 159468P1 1 1 1 1 1
Wall thermostat, 1 stage 138968P1 1 1 1 1 1
Thermostat base 138940P1 1 1 1 1 1
Optional features
10-13 Time delay relay, LP bypass 138491P1 Optional feature - quantity 1 (as required)
10-12 Economizer relay E03-0170 Optional feature - quantity 1 (as required)
10-11 Lockout relay E-0130 Optional feature - quantity 1 (as required)
Common alarm assembly
13-1 Air flow switch B02-0190 Optional feature - quantity 1 (as required)
13-2 T/D relay E-3530 Optional feature - quantity 1 (as required)
13-3 Relay R1 E03-0170 Optional feature - quantity 1 (as required)
13-4 Relay R2 E03-0170 Optional feature - quantity 1 (as required)
13-5 Thermostat E-0230 Optional feature - quantity 1 (as required)
Part Name / Description Part #
200-230V 3Ph 50Hz
ET059M ET359M
380-415V 3Ph 50Hz
ET060P ET360P
208-230V
1Ph 60Hz
ET060Y ET360Y
208-230V
3Ph 60Hz
ET060A ET360Y
460V
3Ph 60Hz
Parts
40
Page 47
Table 27 Motor parts, heater, Economizer, 1.5- and 2-ton units
1.5 Ton 2 Ton
ET017S ET018P ET023S ET023M ET024P ET024Y ET024A
Figure
No.
Condenser fan motors
Standard
7-1 Motor 1/8 Hp, 208/230V (std) 159206P1 1 1 1 1 1
7-1 Motor 1/8 Hp, 380/460V (std) 159206P2 1 1
7-2 Fan prop, 2 blade, 20", 28-deg 159189P2 1 1 1 1 1 1 1
High ambient option
7-1 1/5 Hp, 208/230V (high amb) 159205P1 1 1 1 1 1
7-1 1/5 Hp, 380/460V (high amb) 159205P2 1 1
7-2 Fan prop, 4 blade, 20", 22-deg 159112P1 1 1 1 1 1 1 1
7-8 Capacitor, run 5μF, 370V B-1220 1 1 1 1 1 1 1
7-4 Motor mount 159175P1 1 1 1 1 1 1 1
Evaporator fan motors
8-11 Motor 1/4 Hp dual 206/230V 159207P1 1 1 1 1 1
8-11 Motor 1/4 Hp dual 380/460V 159207P2 1 1
8-2 Blower, CW 159201P2 1 1 1 1 1 1 1
8-1 Blower, CCW 159201P1 1 1 1 1 1 1 1
8-3 Capacitor, run 5μF, 370V B-1220 1 1 1 1 1 1 1
8-8 Motor mount 159174P1 1 1 1 1 1 1 1
8-9 Mount bolt 100061 1 1 1 1 1 1 1
8-10 Mount nut S-3380 1 1 1 1 1 1 1
8-4 Grommot washer 127843P1 4 4 4 4 4 4 4
8-5 Screw 147993P1 4 4 4 4 4 4 4
-6 Grommot tube 127843P2 4 4 4 4 4 4 4
8
8-7 Spacing sleeve 127843P3 4 4 4 4 4 4 4
Heaters - optional
11-1 Heater element, 5kW, 240V 159170P1 1 1 1 1 1 1
11-1 Heater element, 5kW, 277V 159170P2 1
11-1 Heater element, 10kW, 240V 159170P3 1 1 1 1 1 1
11-1 Heater element, 10kW, 277V 159170P4 1
11-1 Heater element, 15kW, 240V 159170P5 1 1 1 1 1 1
11-1 Heater element, 15kW, 277V 159170P6 1
11-1 Fuse link, safety 147896P1 3 3 3 3 3 3 3
11-1 Therm switch, safety (5kW) R-013A 1 1 1 1 1 1 1
11-1 Thermswitch, safety (10, 15kW) R-013B 1 1 1 1 1 1 1
11-1 Jumper wire 146807G1 4 4 4 2 4 3 2
Economizer - optional
12-1 Actuator motor, spring return 159115P1 Optional feature - quantity 1 (as required)
12-2 Min position potentiometer 159471P1 Optional feature - quantity 1 (as required)
12-3 Enthalpy control 138401P1 Optional feature - quantity 1 (as required)
12-4 Mixed air sensor 159204P1 Optional feature - quantity 1 (as required)
12-5 Push rod 159137P1 Optional feature - quantity 1 (as required)
12-6 Linkage, ball type 129645P1 Optional feature - quantity 1 (as required)
12-7 Filter, 2" x 16" x 32.5" 138447P2 1 1 1 1 1 1 1
Part Name/
Description Part #
220-240V
1Ph 50Hz
208-230V
1Ph 60Hz
220-240V
1Ph 50Hz
380-415V
3Ph 50Hz
208-230V
1Ph 60Hz
208-230V
3Ph 60Hz
3Ph 60Hz
Parts
460V
41
Page 48
Table 28 Motor parts, heater, Economizer, 3-ton units
3 Ton
ET035S ET035N ET035M ET036P ET036Y ET036A
Figure
No.
Condenser fan motors
Standard
7-1 Motor 1/8 Hp, 208/230V (std) 159206P1 1 1 1 1
7-1 Motor 1/8 Hp, 380/460V (std) 159206P2 1 1
7-2 Fan prop, 4 blade, 20", 26-deg 159112P2 1 1 1 1 1 1
High ambient option
7-1 1/5 Hp, 208/230V (high amb) 159205P1 1 1 1 1
7-1 1/5 Hp, 380/460V (high amb) 159205P2 1 1
7-2 Fan prop, 4 blade, 20", 22-deg 159112P1 1 1 1 1 1 1
7-8 Capacitor, run 5μF, 370V B-1220 1 1 1 1 1 1
7-4 Motor mount 159175P1 1 1 1 1 1 1
Evaporator fan motors
8-11 Motor 1/4 Hp dual 206/230V 159207P1 1 1 1 1
8-11 Motor 1/4 Hp dual 380/460V 159207P2 1 1
8-2 Blower, CW 159201P2 1 1 1 1 1 1
8-1 Blower, CCW 159201P1 1 1 1 1 1 1
8-3 Capacitor, run 5μF, 370V B-1220 1 1 1 1 1 1
8-8 Motor mount 159174P1 1 1 1 1 1 1
8-9 Mount bolt 100061 1 1 1 1 1 1
8-10 Mount nut S-3380 1 1 1 1 1 1
8-4 Grommot washer 127843P1 4 4 4 4 4 4
8-5 Screw 147993P1 4 4 4 4 4 4
Grommot tube 127843P2 4 4 4 4 4 4
8-6
8-7 Spacing sleeve 127843P3 4 4 4 4 4 4
Heaters - optional
11-1 Heater element, 5kW, 240V 159170P1 1 1 1 1 1
11-1 Heater element, 5kW, 277V 159170P2 1
11-1 Heater element, 10kW, 240V 159170P3 1 1 1 1 1
11-1 Heater element, 10kW, 277V 159170P4 1
11-1 Heater element, 15kW, 240V 159170P5 1 1 1 1 1
11-1 Heater element, 15kW, 277V 159170P6 1
11-1 Fuse link, safety 147896P1 3 3 3 3 3 3
11-1 Therm switch, safety (5kW) R-013A 1 1 1 1 1 1
11-1 Therm switch, safety (10,15kW) R-013B 1 1 1 1 1 1
11-1 Jumper wire 146807G1 4 3 2 4 3 2
Economizer - optional
12-1 Actuator motor, spring return 159115P1 Optional feature - quantity 1 (as required)
12-2 Min position potentiometer 159471P1 Optional feature - quantity 1 (as required)
12-3 Enthalpy control 138401P1 Optional feature - quantity 1 (as required)
12-4 Mixed air sensor 159204P1 Optional feature - quantity 1 (as required)
12-5 Push rod 159137P1 Optional feature - quantity 1 (as required)
12-6 Linkage, ball type 129645P1 Optional feature - quantity 1 (as required)
12-7 Filter, 2" x 16" x 32.5" 138447P2 1 1 1 1 1 1
Part Name/
Description Part #
220-240V 1Ph 50Hz
200-240V 3Ph 50Hz
380-415V 3Ph 50Hz
208-230V
1Ph 60Hz
208-230V
3Ph 60Hz 3
Parts
460V
3Ph 60Hz
42
Page 49
Table 29 Motor parts, heater, Economizer, 4-ton units
4 Ton
ET047N ET347N
Figure
No.
Condenser fan motors
Standard
7-1 Motor 1/3 Hp, 200/240V (std) 159266P1 1 1 1
7-1 Motor 1/3 Hp, 380/460V (std) 159266P2 1 1
7-2 Fan prop, 4 blade, 24", 28-deg 159241P2 1 1 1 1 1
High ambient option
7-1 1/2 Hp, 200/240V (high amb) 159265P1 1 1 1
7-1 1/2 Hp, 380/460V (high amb) 159265P2 1 1
7-2 Fan prop, 4 blade, 24", 24-deg 159241P1 1 1 1 1 1
7-8 Capacitor, run 10μF, 370V B03-0030 1 1 1 1 1
7-4 Motor mount 159175P1 1 1 1 1 1
Evaporator fan motors
8-11 Motor 1/2 Hp dual 200/230V 159267P1 1 1 1
8-11 Motor 1/2 Hp dual 380/460V 159267P2 1 1
8-2 Blower, CW 159254P2 1 1 1 1 1
8-1 Blower, CW 159254P1 1 1 1 1 1
8-3 Capacitor, run 10μF, 370V B03-0030 1 1 1 1 1
8-8 Motor mount 159263P1 1 1 1 1 1
8-9 Mount bolt 100061 1 1 1 1 1
8-10 Mount nut S-3380 1 1 1 1 1
8-4 Grommot washer 127843P1 6 6 6 6 6
8-5 Screw 147993P1 6 6 6 6 6
8-6 Grommot tube 127843P2 6 6 6 6 6
8-7 Spacing sleeve 127843P3 6 6 6 6 6
Heaters - optional
11-1 Heater element, 5kW, 240V 159170P1 1 1 1 1
11-1 Heater element, 5kW, 277V 159170P2 1
11-1 Heater element, 10kW, 240V 159170P3 1 1 1 1
11-1 Heater element, 10kW, 277V 159170P4 1
11-1 Heater element, 15kW, 240V 159170P5 1 1 1 1
11-1 Heater element, 15kW, 277V 159170P6 1
11-1 Fuse link, safety 147896P1 3 3 3 3 3
11-1 Therm switch, safety (5kW) R-013A 1 1 1 1 1
11-1 Therm switch, safety (10,15kW) R-013B 1 1 1 1 1
11-1 Jumper wire 146807G1 3 2 4 3 2
Economizer - optional
12-1 Actuator motor, spring return 159115P1 Optional feature - quantity 1 (as required)
12-2 Min position potentiometer 159471P1 Optional feature - quantity 1 (as required)
12-3 Enthalpy control 138401P1 Optional feature - quantity 1 (as required)
12-4 Mixed air sensor 159204P1 Optional feature - quantity 1 (as required)
12-5 Push rod 159137P1 Optional feature - quantity 1 (as required)
12-6 Linkage, ball type 129645P1 Optional feature - quantity 1 (as required)
12-7 Filter, 2" x 21" x 36.25" 138447P3 1 1 1 1 1
Part Name/
Description Part #
200-230V 3Ph 50Hz
ET047M ET347M
380-415V
3Ph 50Hz
ET048P ET348P
208-230V 1Ph 60Hz
ET048Y ET348Y
208-230V 3Ph 60Hz
Parts
ET048A ET348A
460V
3Ph 60Hz
43
Page 50
Table 30 Motor parts, heater, Economizer, 5-ton units
5 Ton
ET059N ET359N
Figure
No.
Condenser fan motors
Standard
7-1 Motor 1/3 Hp, 200/240V (std) 159266P1 1 1 1
7-1 Motor 1/3 Hp, 380/460V (std) 159266P2 1 1
7-2 Fan prop, 4 blade, 24", 28-deg 159241P2 1 1 1 1 1
High ambient option
7-1 1/2 Hp, 200/240V (high amb) 159265P1 1 1 1
7-1 1/2 Hp, 380/460V (high amb) 159265P2 1 1
7-2 Fan prop, 4 blade, 24", 24-deg 159241P1 1 1 1 1 1
7-8 Capacitor, run 10μF, 370V B03-0030 1 1 1 1 1
7-4 Motor mount 159175P1 1 1 1 1 1
Evaporator fan motors
8-11 Motor 1/2 Hp dual 200/230V 159267P1 1 1 1
8-11 Motor 1/2 Hp dual 380/460V 159267P2 1 1
8-2 Blower, CW 159254P2 1 1 1 1 1
8-1 Blower, CW 159254P1 1 1 1 1 1
8-3 Capacitor, run 10μF, 370V B03-0030 1 1 1 1 1
8-8 Motor mount 159263P1 1 1 1 1 1
8-9 Mount bolt 100061 1 1 1 1 1
8-10 Mount nut S-3380 1 1 1 1 1
8-4 Grommot washer 127843P1 6 6 6 6 6
8-5 Screw 147993P1 6 6 6 6 6
8-6 Grommot tube 127843P2 6 6 6 6 6
8-7 Spacing sleeve 127843P3 6 6 6 6 6
Heaters - optional
11-1 Heater element, 5kW, 240V 159170P1 1 1 1 1
11-1 Heater element, 5kW, 277V 159170P2 1
11-1 Heater element, 10kW, 240V 159170P3 1 1 1 1
11-1 Heater element, 10kW, 277V 159170P4 1
11-1 Heater element, 15kW, 240V 159170P5 1 1 1 1
11-1 Heater element, 15kW, 277V 159170P6 1
11-1 Fuse link, safety 147896P1 3 3 3 3 3
11-1 Therm switch, safety (5kW) R-013A 1 1 1 1 1
11-1 Therm switch, safety (10,15kW) R-013B 1 1 1 1 1
11-1 Jumper wire 146807G1 3 2 4 3 2
Economizer - optional
12-1 Actuator motor, spring return 159115P1 Optional feature - quantity 1 (as required)
12-2 Min position potentiometer 159471P1 Optional feature - quantity 1 (as required)
12-3 Enthalpy control 138401P1 Optional feature - quantity 1 (as required)
12-4 Mixed air sensor 159204P1 Optional feature - quantity 1 (as required)
12-5 Push rod 159137P1 Optional feature - quantity 1 (as required)
12-6 Linkage, ball type 129645P1 Optional feature - quantity 1 (as required)
12-7 Filter, 2" x 21" x 36.25" 138447P3 1 1 1 1 1
Part Name/
Description Part #
200-230V
3Ph 50Hz
ET059M ET359M
380-415V 3Ph 50Hz
ET060P ET360P
208-230V
1Ph 60Hz
ET060Y ET360Y
208-230V
3Ph 60
Parts
ET060A ET360Y
460V
3Ph 60Hz
44
Page 51
Figure 7 Condenser /piping assembly
8
Parts
Soft start device
10
7
2
4
1
9
6
45
Page 52
Figure 8 Evaporator blower
3
Parts
12
Figure 9 Evaporator coil and expansion valve
1
4
2
7
6
5
8910
11
1
2
TEV systems
46
Page 53
Figure 10 Electric panels
11
3
31
Parts
16
13
8
12
7
6
15
4
380/460V, 3 phase
10
11
3
3
31
11
31
13
8
12
6
10
13
8
12
6
Evaporator “MF”
15
9
1
4
4
1A
200/240V, 3 phase
1
200/240V, 1 phase
10
1
47
Page 54
Figure 11 Heater assembly
5kW &10kW
208/230V, 1 phase
(Parallel)
Connection
15kW
208/230V, 1 phase
(Parallel)
Connection
5kW, 10kW & 15kW
208/230V, 3 phase
(Delta)
Connection
Parts
5kW, 10kW & 15kW
380/460V, 3 phase
(Wye)
Connection
159171G1 & G2,
G13 & G14
159171G3 & G15 159171G4, G5 &G6
G16, G17 & G18
159171G7, G8, G10, G11& G12
G19, G20, G21, G22, G23& G24
1
48
Page 55
Figure 12 Economizer assembly
4
1
3
Parts
7
5
6
2
Figure 13 Common alarm assembly
5
4
2
3
1
49
Page 56
Figure 14 Soft start device
Parts
To compressor capacitor
1
50
Page 57
Notes
Parts
51
Page 58
Parts
52
Page 59
Page 60
Ensuring The High Availability Of Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical continuity, ensures network resiliency and adaptability through a family of technologies—including Liebert power and cooling technologies—that protect and support business-critical systems. Liebert solutions employ an adaptive architecture that responds to changes in criticality, density and capacity. Enterprises benefit from greater IT system availability, operational flexibility and reduced capital equipment and operating costs.
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions. © 2007 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice. ® Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-19530_REV02_05-09
Technical Support / Service
Web Site
www.liebert.com
Monitoring
800-222-5877
Liebert.monitoring@emerson.com
Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877
upstech@emersonnetworkpower.com
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
powertech@emersonnetworkpower.com
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
7/F Dah Sing Financial Centre
108 Gloucester Road
Wanc hai
Hong Kong
852 2572 2201
Fax: 852 2519 9210
Emerson Network Power. The global leader in enabling Business-Critical Continuity.
AC Power Connectivity DC Power
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2007 Emerson Electric Co.
Embedded Computing Embedded Power Power Switching & Controls Monitoring
Outside Plant
Precision Cooling
EmersonNetworkPower.com
Racks & Integrated Cabinets Services Surge Protection
Loading...