Liebert Nfinity Maintenance Bypass Cabinet User Manual

Page 1
POWER AVAILABILITY
Maintenance Bypass Cabinet for Nfinity
USER MANUAL
Page 2
Page 3
i
TABLE OF CONTENTS
GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
System Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Standard Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FRONT VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
REAR VIEW (WITHOUT TRANSFORMER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
REAR VIEW (WITH TRANSFORMER). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
MODES OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
UPS Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Bypass Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
MAJOR COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Bypass Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
User Selectable Output Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
PREPARATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Required Setup Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
UNLOADING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Unloading the Maintenance Bypass Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Stationary Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
CABLE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Wiring Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Preparing Internal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Dual Source Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Removing the Cover Plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Power Cable Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
REPO Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Input Wiring (TB1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Maintenance Bypass Cabinet With Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Maintenance Bypass Cabinet Without Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
UPS to Maintenance Bypass With Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
UPS to Maintenance Bypass Without Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
OPERATING PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Start-Up and Initialization. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Shutting Down the UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Transferring System from UPS to Maintenance Bypass Operation. . . . . . . . . . . . . . . . . . . 18
Transfer of the System from Maintenance Bypass to UPS Operation. . . . . . . . . . . . . . . . . 18
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Proper Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Scheduled Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Replacing Fan Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Page 4
Page 5
1
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be closely followed during installation and maintenance of this Maintenance Bypass Cabinet.
This product is designed for commercial/ industrial use only. this product is not intended for use with life support and other designated “critical” devices. Maximum load must not exceed that shown on the UPS and the Maintenance Bypass Cabinet rating label.
The Nfinity Maintenance Bypass Cabinet is designed for use on properly grounded (earthed) 208/240 VAC 60 Hz supply, for installation by qualified personnel. This UPS equipment is intended to be installed by a qualified / certified electrician who must review and approve customer supplied wiring, circuit breakers, intended loads and verify correct input, output and grounded (earthed) connections to ensure compliance with technical standards and national and local electrical codes. Installation instructions and warning notices are located in the Installation section of this manual.
Operate the UPS equipment in an indoor environment only in an ambient temperature range of 32°F to 104°F (0°C to 40°C). Install it in a clean environment, free from conductive contaminants, moisture, flammable liquids, gases, or corrosive substances.
Never block or insert any object into the ventilation holes or other openings.
!
WARNING
LETHAL VOLTAGES MAY BE PRESENT WITHIN THIS UNIT EVEN WHEN IT IS APPARENTLY NOT OPERATING. OBSERVE ALL CAUTIONS AND WARNINGS IN THIS MANUAL. FAILURE TO DO SO MAY RESULT IN SERIOUS INJURY OR DEATH. NEVER WORK ALONE.
!
CAUTION
To reduce the risk of fire:
• The NMB1x and NMB4x models must be connected to a circuit provided with 100 amperes maximum branch circuit overcurrent protection in accordance with applicable national and local electrical codes.
• The NMB5x and NMB8x models must be connected to a circuit provided with 125 amperes maximum branch circuit overcurrent protection in accordance with applicable national and local electrical codes.
Page 6
2
GLOSSARY OF SYMBOLS
Risk of Electrical Shock
Indicates Warning or Caution Followed by Important Instructions
AC Input
AC Output
Requests the user to consult the manual
Equipment Grounding Conductor
ON
OFF
i
Page 7
3
GENERAL DESCRIPTION
Congratulations on your purchase of Liebert’s Nfinity™ Maintenance Bypass Cabinet with Configurable Output Distribution. As with every Liebert product, we stand behind our quality. If you have any questions concerning this Maintenance Bypass Cabinet, please feel free to contact your local dealer, Liebert representative, or call the appropriate Technical Support number listed on the back of this manual.
To ensure proper installation and operation of this unit, please read this manual thoroughly.
Installation must be done by a qualified/ certified electrician, but general operation may be performed without special training.
SYSTEM DESCRIPTION
The Liebert Nfinity Maintenance Bypass Cabinet is intended for use with the Nfinity UPS. Typical applications include supporting workstations, servers, network, telecom or other sensitive electronic equipment.
The Nfinity Maintenance Bypass Cabinet was designed to provide maximum system availability to business critical equipment. The Nfinity Maintenance Bypass Cabinet allows for transfer of connected loads to an alternate power path allowing full isolation of the UPS. The UPS can then be turned “OFF” and removed from service with no interruption of power to connected loads.
Features
• Supports up to 20 kVA loads
• High speed transfer switch
• Compact design
• Highly configurable
• Multiple power path indicators
Standard Components
• Casters and leveling feet
• Easily accessible terminal blocks
• Supports Lockout/Tagout Program
• Support/mounting brackets for additional stability
• Provisions for hardwire output
• Dual-source compatible for increased availability
Options
• Output transformer for isolation
• Field installable output distribution
Page 8
4
FRONT VIEW
Bypass availability
indicator (amber)
Cooling fans (transformer models only)
UPS input power
present (amber)
UPS output availability indicator (green)
Bypass switch (SW1)
UPS input switch (SW2)
Support bracket
Output breaker (CB1)
Page 9
5
REAR VIEW (WITHOUT TRANSFORMER)
Configurable output
distribution (optional)
Hardwire output
(standard)
Maintenance
bypass input (TB1)
UPS output (TB4)
Maintenance bypass input (TB2)
UPS input (TB3)
Support bracket
Hardwire output terminal block (TB5)
Page 10
6
REAR VIEW (WITH TRANSFORMER)
Hardwire output terminal block (TB6)
Configurable output
distribution (optional)
Hardwire output
(standard)
Maintenance bypass
input (TB1) (TB2)
UPS output (TB5)
UPS input (TB3)
Tap selector (TB4)
Support bracket
Page 11
7
MODES OF OPERATION
The Nfinity Maintenance Bypass Cabinet is designed to operate in the following modes:
UPS MODE
While the Nfinity Maintenance Bypass Cabinet is in the UPS Mode, the UPS is supplying the connected load with continuous high quality AC power. In this mode of operation, the load is protected by the UPS. The Bypass Switch rotated toward the green lamp indicates this mode.
BYPASS MODE
When the Nfinity Maintenance Bypass Cabinet is in the Bypass mode it provides an alternate path for power to the connected equipment. Should the UPS need to be taken out of service for limited maintenance or repair, manual activation of the bypass will cause an immediate transfer of the equipment from the UPS inverter to the bypass source. The amber lamp illuminated in the Maintenance Bypass Switch compartment indicates bypass is available. In this mode of operation the load is NOT protected by the UPS. The Bypass Switch rotated toward the amber lamp indicates this mode. See OPERATING PROCEDURES on page 18 for instructions on use.
UPS ouput available (green)
Bypass mode
Bypass
available
(amber)
UPS Input source (amber)
ON = AC power supplied to UPS input OFF = AC power removed from UPS input
Page 12
8
MAJOR COMPONENTS
The following is a general description of each component and its functions. Please review this section carefully, as it will give you a better understanding as to how the Nfinity Maintenance Bypass Cabinet operates.
BYPASS SWITCH
The Bypass Switch allows easy and rapid transfer of connected loads between the UPS and Bypass source.
User Selectable Output Distribution
Several receptacle and hardwire options are available as user selectable output distribution. These are factory configured when ordered and also allow for field upgrades. Common receptacle and hardwire options include:
15 Amp Options
5-15R2 L5-15R2 6-15R2-208 6-15R2-240 L6-15R2-208 L6-15R2-240 15A,120V, 1 pole breaker w/ 1/2" & 3/4"
knockouts 15A,208V, 2 pole breaker w/ 1/2" & 3/4"
knockouts 15A,240V, 2 pole breaker w/ 1/2" & 3/4"
knockouts
20 Amp Options
5-20R2 (T-slot) L5-20R L6-20R-208 L6-20R-240 L14-20R-240 20A,120V, 1 pole breaker w/ 1/2" & 3/4"
knockouts 20A,208V, 2 pole breaker w/ 1/2" & 3/4"
knockouts 20A,240V, 2 pole breaker w/ 1/2" & 3/4"
knockouts
30 Amp Options
L5-30R L6-30R-208 L6-30R-240 L14-30R-240 30A,120V, 1 pole breaker w/ 1/2" & 3/4"
knockouts 30A,208V, 2 pole breaker w/ 1/2" & 3/4"
knockouts 30A,240V, 2 pole breaker w/ 1/2" & 3/4"
knockouts
Other Options
Single Position Blanking Plate Hardwire Option
Optional Transformer
Models offering a transformer are designed to accept the same input voltage as the UPS and provide 240 / 208 / 120 / 120 output. Models with transformers are provided with redundant cooling fans and user serviceable fan filters. The fans only operate when in Bypass mode.
Page 13
9
PREPARATION
These installation instructions provide all the information needed for positioning the Nfinity Maintenance Bypass Cabinet (including environmental requirements) and for connecting the input and output power cables.
INSPECTION
Upon receiving the Nfinity Maintenance Bypass Cabinet, examine the packaging for any signs of mishandling or damage. If any damage is noted, contact your local dealer or Liebert representative and notify your carrier.
ENVIRONMENT
The Maintenance Bypass Cabinet environment must be free of conductive contaminants and excessive moisture (water condensation), flammable vapors, chemical fumes, or corrosive gases and liquids.
REQUIRED SETUP EQUIPMENT
The tools below are required in order to properly setup your maintenance bypass cabinet:
• pallet jack
• 1/2" (13 mm) wrench
• torque wrench
• flat-head screwdriver
• #2 Phillips screwdriver
• 3/16" (5 mm) Allen wrench
SITE PREPARATION
When deciding where to locate your Maintenance Bypass Cabinet, consider the weight and size of the unit. Make sure that the structural integrity of the floor can withstand the weight. Refer to the
table below for dimensional considerations:
Check to make sure that your Maintenance Bypass Cabinet will be located in a well-ventilated area with at least 12 inches in front of and behind it. Transformer based models are forced air cooled with the aid of two internal cooling fans.
The unit frame is bolted to the shipping pallet to ensure safety. It is recommended that a pallet jack be used to transport the unit to its operating location (prior to unbolting the unit).
Dimensions
Model w/Transformer w/oTransformer
W x D x H In (mm)
9.5 x 26.5 x 30.4
(241.3 x 673.1 x 772.16)
Weight 287 lbs (130 kg) 85 lbs (38 kg)
12" (304mm)
12" (304mm)
Page 14
10
UNLOADING
UNLOADING THE MAINTENANCE B
YPASS CABINET
1. Once the Maintenance Bypass Cabinet is near the desired operating location, remove the cardboard cover.
2. Use a 1/2" (13mm) wrench to remove the eight mounting bolts (four per bracket) from the pallet brackets. Remove mounting brackets from the pallet and Maintenance Bypass Cabinet. Keep brackets and bolts for future transportation of the Maintenance Bypass Cabinet or for securing the cabinet to the floor.
3. Remove the metal ramp from the bottom of the pallet, rotating it 180°. Fit ramp onto opposite side of pallet (in slot) as shown below.
4. Using two people, slowly roll the Maintenance Bypass Cabinet down the ramp until the Maintenance Bypass Cabinet is on a level surface.
!
CAUTION
This Maintenance Bypass Cabinet is heavy (see weight in Dimensions table on page 9). At least two people should assist to unload it from the pallet.
Page 15
11
5. Once the Maintenance Bypass Cabinet is in the desired location, adjust the leveling feet to secure its position.
STATIONARY MOUNTING
Additional stability can be added by bolting the mounting brackets (used in shipping) to the floor.
For greater stability, use a higher-grade bolt. Refer to the dimensions below when drilling holes for stationary mounting.
4-3/4"
(120 mm)
center line
28"
(711 mm)
5/16" diameter 6 places
4-3/4"
(120 mm)
Page 16
12
CABLE INSTALLATION
WIRING PREPARATION
Be sure that the unit is not connected to any AC mains power source or UPS before installing any wiring to this unit. This Maintenance Bypass Cabinet should be installed by a qualified / certified electrician.
Preparing Internal Wiring
The Maintenance Bypass Cabinet is factory­configured for single-source installations. If your installation requires dual-source capabilities, the Maintenance Bypass Cabinet’s wiring must be modified.
Dual Source Configuration
Modifying the wiring consists of removing the jumpers between TB1 and TB2 as described below:
1. Remove cover plates.
2. Identify TB1 and TB2.
3. Using a 3/16" Allen wrench, loosen terminal mounting jumpers between TB1 and TB2.
4. Remove jumpers and retighten terminals to 22-26 in-lb (2.5 to 3.0 Nm).
5. Connect primary source to TB2 and secondary source to TB1.
!
WARNING
PLEASE READ THIS SECTION THOROUGHLY BEFORE ATTEMPTING TO INSTALL WIRING TO THIS UNIT.
TRANSFORMER MODELS
TB1 TB2 TB3
Cables to be removed
NON-TRANSFORMER MODELS
TB1 TB2
Cables to be removed
Page 17
13
REMOVING THE COVER PLATES
On the back of the Maintenance Bypass Cabinet, cover plates are over the input and output terminals. Remove these using a phillips screwdriver. Keep screws and plates to one side.
POWER CABLE INSTALLATION
Refer to the chart below when selecting cables:
NOTES: If an output transformer is fitted, the Nfinity Maintenance Bypass has a five-cycle inrush current that is 10 times the rated output current. This must be taken into account when selecting the overload protection device at the AC input supply distribution point. To avoid random tripping on start up, it is recommended that the AC input supply be protected with a circuit breaker capable of withstanding this initial inrush.
Transient and steady state earth leakage currents may occur when starting the equipment. This should be taken into account when selecting ground current detection devices, as these will carry the earth leakage currents of both the UPS equipment and the load.
REPO CONNECTION
Refer to the Nfinity user manual for connection details.
Power Cable and Protection Ratings
Models NMB1x & NMB4x
Max Input Current
100 A
Input Protection
100 A
Max Output Current
100 A
Input/ Output Terminal Details
Max: 2/0 (70 mm
2
)
Min: 6 AWG (16 mm
2
)
Models NMB5x & NMB8x
Max Input Current
125 A
Input Protection
125 A
Max Output Current
125 A
Input/ Output Terminal Details
Max: 2/0 (70 mm
2
)
Min: 6 AWG (16 mm
2
)
Page 18
14
INPUT WIRING (TB1)
Connect the input wiring as stated in the following steps:
1. Locate the input wiring access, remove the knockout and pull the three/four input wires through it, allowing some slack for installation.
2. Secure the conduit to the rear panel of the Maintenance Bypass Cabinet.
3. Input power cables connect to hex terminals on the input terminal block.
4. Insert the ground (earth) wire through the earth lug and tighten it to the proper torque value (22-26 in-lb). Then connect the wires to the block connections as shown below. Using a torque wrench, turn the screws clockwise until tightened to the proper torque value (22-26 in-lb).
NOTE
Input wiring must be installed using conduit.
208 input voltage jumper—if only the connections for 208 VAC are made between the UPS and theNfinity Maintenance Bypass, the 208 input voltage jumper must be installed for proper operation. To install this jumper, place the jumper wire provided in the accessory kit between Pin 1 and Pin 2 on TB4.
Input
Conduit
RIGHT HAND OPTION
( LOOKING FROM FRONT OF UNIT )
REAR VIEW
LEFT HAND OPTION
( LOOKING FROM FRONT OF UNIT )
REAR VIEW
Page 19
15
Maintenance Bypass Cabinet With Transformer
Maintenance Bypass Cabinet Without Transformer
SW2
UPS Input
Switch
Transformer
TB4
208/240V
Tap Selector
UPS Input UPS Output
Output
SW1
Bypass
Switch
CB1
Output
Breaker
TB5
TB2
TB3
TB6
Input 1
Input 2
TB1
Single input jumper (remove for dual input feeds)
Input 2
SW2
UPS Input
Switch
UPS Input UPS Output
Output
SW1
Bypass
Switch
CB1
Output
Breaker
TB4
TB2
TB3
TB5
Input 1
TB1
Single input jumper (remove for dual input feeds)
Page 20
16
UPS to Maintenance Bypass With Transformer
G
TB1
TB2
G
TB3 TB4
123
TB5
TB6
L1
L2
L1
L2
L1 L2 G 1 2 3 4
1
2
3
4
120
208
240
120
L1 L2 G 1 2 3 1 2 3 4 5
GEC
TB3TB2TB1
Flexible conduit
208 240
NFINITY UPS
NFINITY MAINTENANCE BYPASS CABINET
WITH TRANSFORMER
Input 2
Input 1
See Nfinity user manual for details on connecting GEC.
G
G
G
NOTES
1. If feeding the Maintenance Bypass Cabinet from a single source, the input connection may be made to either TB1 or TB2.
2. If feeding the Maintenance Bypass Cabinet from a dual source, the UPS input supply connection must
be made to TB1 and the bypass input supply connection
must
be made to TB2. The link between TB1 and TB2 must be removed.
Remove these two wires for dual source
Ensure that both tap selectors are set to the correct input voltage
Page 21
17
UPS to Maintenance Bypass Without Transformer
G
TB1
TB2
G
TB3 TB4
TB5
L1
L2
L1
L2
L1 L2 G 1 2 3 4
1
2
3
4
120
208
240
120
L1 L2 G 1 2 3 1 2 3 4 5
GEC
TB3TB2TB1
Flexible conduit
NFINITY UPS
NFINITY MAINTENANCE BYPASS CABINET
WITHOUT TRANSFORMER
Input 2
Input 1
N
N
See Nfinity user manual for details on connecting GEC.
G
G
G
NOTES
1. If feeding the Maintenance Bypass Cabinet from a single source, the input connection may be made to either TB1 or TB2.
2. If feeding the Maintenance Bypass Cabinet from a dual source, the UPS input supply connection must
be made to TB1 and the bypass input supply connection
must
be made to TB2. The link between TB1 and TB2 must be removed.
Remove these three wires for dual source
Ensure that the tap selector is set to the correct input voltage
Page 22
18
OPERATING PROCEDURES
START-UP AND INITIALIZATION
Follow these steps in order to start up the Nfinity UPS while connected to the Nfinity Maintenance Bypass.
1. Set Maintenance Bypass switch (SW1) to UPS position on Maintenance Bypass Cabinet.
2. Close UPS source switch (SW2).
3. Close output circuit breaker (CB1).
4. Close input circuit breaker (CB1).
5. On UPS, close control enable switch (SW2).
6. After UPS has initialized, turn UPS output on by pushing the standby button.
SHUTTING DOWN THE UPS
Use the following procedure to power down the system.
1. Turn UPS output off by pushing the Standby button.
2. Open the control enable switch (SW2) on the UPS.
3. Open the input circuit breaker (CB1) on the UPS.
4. Open the UPS source switch (SW2) on the Maintenance Bypass Cabinet.
5. Open the output circuit breaker (CB1) on the Maintenance Bypass Cabinet.
TRANSFERRING SYSTEM FROM UPS
TO MAINTENANCE BYPASS
O
PERATION
1. Verify that the amber bypass lamp is illuminated
2. Turn the bypass switch (SW1) to the bypass position on the Maintenance Bypass Cabinet. The connected equipment is now powered from the bypass source and is not protected.
TRANSFER OF THE SYSTEM FROM M
AINTENANCE BYPASS TO UPS
O
PERATION
1. Close the UPS source switch (SW2) on the Maintenance Bypass Cabinet.
2. Close the input circuit breaker (CB1) on the UPS.
3. Close the control enable switch (SW2) on the UPS.
4. Turn the UPS output on by pushing the standby button on the UPS. Verify the Green UPS lamp is illuminated.
5. Turn the bypass switch to the bypass position on the Maintenance Bypass Cabinet.
Page 23
19
MAINTENANCE
PROPER CARE
Keeping your Liebert Nfinity Maintenance Bypass Cabinet operating properly is imperative to optimal performance and life of the unit. It is recommended that a certified technician perform preventive and corrective maintenance. Liebert Global Services (LGS) is dedicated to ensuring the highest level of performance and unmatched support for your Nfinity Maintenance Bypass Cabinet. Contact an LGS representative for services to guarantee maximum reliability and system availability.
SCHEDULED MAINTENANCE
It is recommended that the following maintenance be performed at least monthly:
• Check, clean and replace filters.
• Verify that airflow is not obstructed.
It is recommended that the following maintenance be performed annually:
• Verify all power connections.
• Verify that all output distribution modules are operating properly.
REPLACING FAN FILTERS
Transformer Models Only
The Maintenance Bypass Cabinet intake fans contain filters that will need to be replaced or cleaned periodically, depending on the surrounding environment. Check by noting the condition of the two filters. If filters are dirty, replace or wash them. The filters may be taken out of the UPS for replacement or cleaning by removing the plastic cover over the filter frame. Use caution when replacing filters when fans are running.
The fan filters are washable and can be reused. To wash these filters, place them under a running faucet (with the dirt side down) to remove dirt and dust. Blot dry with a towel and allow air-drying before reusing.
Fan Filters
Page 24
20
SPECIFICATIONS
General & Environmental Rating
Unit Rating
kVA
Models NMB1x and NMB4x = 18
Models NMB5x and NMB8x = 20
Amps
Models NMB1x and NMB4x = 100 max
Models NMB5x and NMB8x = 125 max
Compliant Safety Standards UL 1778, c-UL
Mechanical
Dimensions
Width
In (mm)
9.5 (241)
Depth 26.5 (700)
Height 30.4 (775)
Weight lb (kg)
287 (130)
transformer model
85 (39)
transformerless model
Environmental
Operating Temperature (max) F (C) 32º - 104º (0º - 40º)
Relative Humidity % 0-95% non-condensing
Maximum Operating Altitude Ft (M) 10,000 (3000)
Input Data
Nominal Input Voltage VAC 208 or 240
Input Frequency (nominal) Hz 60
Input Frequency Range Hz 55-65
Output Data 208/240 240 208
Output Voltage VAC 120/120/208/240 120/120/240* 120/120/208*
Transfer Time msec <4 msec typical
Output Frequency Hz 60
* Transformerless model requires neutral input
Page 25
Page 26
The Company Behind the Products
With over a million installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics:
Environmental systems—close-control air conditioning from 1 to 60 tons
Power conditioning and UPS with power ranges from 300 VA to more than 1000 kVA
Integrated systems that provide both environmental and power protection in a single, flexible package
Monitoring and control—from systems of any size or location, on-site or remote
Service and support through more than 100 service centers around the world and a 24/7 Customer Response Center
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2002 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-23960 (7/02) Rev. 2
Technical Support /Service
Web Site
www.liebert.com
Monitoring
800-222-5877
monitoring@liebert.com
Outside the US: 614-841-6755
Single-Phase UPS
800-222-5877
upstech@liebert.com
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
powertech@liebert.com
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Italy
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
+39 049 9719 111
Fax: +39 049 5841 257
Asia
23F, Allied Kajima Bldg.
138 Gloucester Road
Wanchai
Hong Kong
+852 2 572 2201
Fax: +852 2 831 0114
POWER AVAILABILITY
Maintenance Bypass Cabinet for Nfinity
USER MANUAL
Loading...