Liebert Nfinity Extended Battery Cabinet User Manual

Page 1
POWER PROTECTION
Extended Battery Cabinet for Nfinity
USER MANUAL
Page 2
Page 3
i
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
OPERATING ENVIRONMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
GLOSSARY OF SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
SYSTEM DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
FEATURES:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
PREPARATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
ENVIRONMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
REQUIRED SETUP EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
UNLOADING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
UNLOADING THE EXTENDED BATTERY CABINET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
STATIONARY MOUNTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
GROUNDING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
DC POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
CONFIGURATION SETTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
MODULE REPLACEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
R
EMOVING MODULES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
REPLACING MODULES. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
BATTERY RUN TIMES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
I
NTERNAL AND EXTENDED BATTERY CABINETS (MINUTES) . . . . . . . . . . . . . . . . . . . . . 11
Page 4
Page 5
1
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be closely followed during installation of this Extended Battery Cabinet.
This product is designed for commercial/industrial use only. This product is not intended for use with life-support and other designated “critical” devices.
Observe the following precautions when working with batteries:
This UPS equipment is designed for use on a properly grounded electrical system. This equipment is intended to be installed by a qualified, certified electrician who must review and approve customer-supplied wiring, circuit breakers and earth connections to ensure compliance with technical standards and local electrical codes. Installation instructions and warning notices only for use by qualified personnel are located in the
INSTALLATION section of this manual.
Electromagnetic Compatibility
This UPS equipment complies with the requirements of the EMC directive 89/336/EEC, the published technical standards and Class A digital device pursuant to Part 15 of FCC rules. These limits provide reasonable protection against harmful electromagnetic interference in a commercial environment.
This device generates, uses and radiates radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference with radio communications. Operating this device in a residential area is likely to cause harmful electromagnetic interference that the user must correct at his own expense.
Operating Environment
Operate the Extended Battery Cabinet in an indoor environment only in an ambient temperature range of 32°F to 104°F (0°C to 40°C). For optimum battery life, operate the unit in an ambient temperature range of 59°F to 77°F (15°C to 25°C). Install the Extended Battery Cabinet in a clean environment, free from conductive contaminants, moisture, flammable liquids, gases and corrosive equipment in an indoor environment.
Turn the UPS off and isolate the system before cleaning. Use only a soft cloth, never liquid or aerosol cleaners. Keep the front and rear vents free of dust accumulation that could restrict air flow.
Never block or insert any object into the ventilation holes or other openings.
This Extended Battery Cabinet contains user replaceable modules. No attempts should be made to access the interior of any module. See MODULE REPLACEMENT on page 9 for details on this procedure.
!
WARNING Lethal voltages may be present
within this unit even when it is apparently not operating. Observe all cautions and warnings in this manual. Failure to do so may result in serious injury or death. Never work alone.
!
CAUTION DO NOT dispose of battery
modules in a fire; the battery module may explode.
DO NOT open or mutilate batteries; released electrolyte is harmful to skin and eyes and may be toxic.
A battery can present a risk of electrical shock and high short­circuit current. The following precautions should be observed when working on batteries.
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
!
CAUTION Lead-acid batteries contain
hazardous toxic materials. Handle, transport and recycle in accordance with local regulations.
Page 6
2
GLOSSARY OF SYMBOLS
Risk of electrical shock
Indicates caution followed by important instructions
AC input
AC output
Requests the user to consult the manual
Indicates the unit contains a valve-regulated lead acid battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
OFF
ON
Standby
No telecommunication connection
Locked position
Unlocked position
Contact closure signals
Serial communications
i
Page 7
3
GENERAL DESCRIPTION
System Description
The Extended Battery Cabinet is a modular cabinet intended for use with the Nfinity™ modular UPS system. The cabinet will hold a maximum of 12 battery modules with the same level of monitoring and control as the battery modules fitted in the UPS.
Features:
• Up to four Extended Battery Cabinets can be used with a single Nfinity UPS
• Up to 12 battery modules per cabinet
• A user-friendly interface, on the UPS, for cus­tom configuration
• Continuous system monitoring
• Warning alarms and event logs.
FRONT VIEW
REAR VIEW
Page 8
4
PREPARATION
These installation instructions provide all the information needed for positioning the Extended Battery Cabinet (including environmental requirements) and for connecting the input and output power cables.
Inspection
Upon receiving the Extended Battery Cabinet, examine the packaging for any signs of mishandling or damage. If any damage is noted, call your local Liebert representative and/or notify your carrier.
Environment
Required Setup Equipment
The tools below are required in order to properly set up your Extended Battery Cabinet.
• Pallet jack
• 13 mm or 1/2" wrench
• Flathead screwdriver
• #2 Phillips screwdriver
Site Preparation
When deciding where to locate your Extended Battery Cabinet, consider the weight and size of the unit. Make sure that the structural integrity of the floor can withstand the weight. Refer to the table below for size and fully populated weight considerations:
Check to make sure that your Extended Battery Cabinet will be located in a well-ventilated area with at least 300 mm (12”) behind it. It should have at least one meter (39 in.) in front to change modules when necessary.
The unit frame is bolted to the shipping pallet to ensure safety. It is recommended that a pallet jack be used to transport the unit to its operating location (prior to unbolting the unit).
NOTE
Operating in temperatures above 77°F (25°C) will reduce battery life. The environment must be free of conductive contaminants and excessive moisture (water condensation), flammable vapors, chemical fumes, or corrosive gases and liquids.
Max Weight
lbs (kg)
H x W x D
in (mm)
942
(427)
52" x 20" x 28"
(1320 x 508 x 711)
1 meter (39 in.)
300 mm (12 in)
Page 9
5
UNLOADING
Unloading the Extended Battery Cabinet
1. Once the Extended Battery Cabinet is near the desired operating location, remove the card­board cover.
2. Use a 13 mm (1/2") wrench to remove the four mounting bolts from each of the pallet brack­ets. Remove mounting brackets from the pallet and cabinet. Keep brackets and bolts for future transportation of cabinet or for additional sta­bility once in place.
3. Remove the metal ramp from the bottom of the battery cabinet, rotating it. Fit ramp in pallet slot as shown above.
4. Using two people, slowly move the cabinet down the ramp until the Extended Battery Cabinet is on a level surface.
!
CAUTION This battery cabinet is heavy (see
weight on previous page). At least two people should be present to unload it from the pallet.
Page 10
6
5. Once the Extended Battery Cabinet is in the desired location, adjust the leveling feet to secure its position.
Stationary Mounting
Additional stability can be added by bolting the mounting brackets (used in shipping) to the floor.
Optional Stationary Mounting
For greater stability, use a higher-grade bolt. Refer to the dimensions below when drilling holes for stationary mounting.
1/2"
(13 mm)
4.75”
(120 mm)
center line
28”
(711 mm)
4.75”
(120 mm)
5/16" diameter (7.94 mm) 6 places
Page 11
7
INSTALLATION
Grounding
The Extended Battery Cabinet must be installed with a dedicated grounding electrode conductor (GEC) to the site grounding system in accordance with national and local wiring codes and regulations as shown below.
Communications
To enable communication between the Extended Battery Cabinet and the Nfinity, it is necessary to install an Intellislot Battery Card (IBC) in the Intellislot port of the UPS. See below. A second, included IBC is installed in the Extended Battery Cabinet. The provided serial cable is to be connected between the two cards.
DC Power
DC connection with the UPS unit must be via the factory-supplied battery cables, or if longer connection cable is required, via the optional Extended Battery Cable kits. See below.
After connections are made and verified, the output circuit breaker must be closed to connect the batteries inside the Extended Battery Cabinet to the Nfinity UPS. To do this, move the handle of the circuit breaker under the lower-most bezel to the ON position (see illustration below for circuit breaker location).
L1 L2
GEC Connection
Communications
NOTE
Failure to turn on the circuit breaker may cause damage to the batteries in the Extended Battery Cabinet. Failure to follow this procedure may limit your warranty.
DC Power
Output Circuit Breaker
Page 12
8
Configuration Setting
For the UPS system to be aware of the presence of the Extended Battery Cabinet(s), the system has to be configured with the necessary information. To enter the information, follow the steps below:
After initialization, pressing the button will take you to the main menu.
Scroll down to UPS Configuration, and select it by pressing the button.
Scroll down to Change Settings; press
Scroll down to Intellislot Battery Ca.; select it by pressing
Enter the quantity of Extended Battery Cabi­nets installed.
Press
return arrow and then press to
save your changes and exit.
The system is now configured.
Main Menu
UPS Status
> UPS Configuration
Display Date/Time Event Log Alarm Log Transfer to Bypass Module Replacement Tools
UPS Configuration
UPS Configuration
Review Settings
> Change Settings
Service Mode
Change Settings
Input Voltage Frequency Sync Range Frequency Slew Rate Set Password Auto Battery Test Low Battery Warning Auto Restart User Settings Set Date/Time Max Load Alarm Set UPS Shutdown Delay Redund Alarm Set Service Contact Remote Shutdown External Battery Bypass Alarm Mode
> Intelli-Batt Ca.
Air Filter Reminder Factory Defaults
ESC
Page 13
9
MODULE REPLACEMENT
Follow the instructions below when replacing a battery module and when adding modules to the system.
Removing Modules
1. Remove bezel cover of appropriate module. When replacing a battery module, verify the faulty module by confirming the amber LED is lit.
2. Turn fastener counterclockwise until it is loosened.
3. Start to pull out module. About 2/3 out it will stop. Slide module away from the center of the unit.
4. Dispose of the removed module in an environmentally responsible way that complies with local codes and regulations or return the module to Liebert for proper disposal.
!
CAUTION Battery modules are heavy: 30 kg
(66 lbs). Make sure to use two people when removing a battery module. Continue to pull until module is removed (seen at right).
NOTE
Battery modules may contain shipping screws. These screws may be removed and discarded.
Status LED Fault LED
WARNING
POTENTIAL TIP HAZARD
Install all modules starting with bottom bays and moving to top. For module removal, start with top bays and proceed to bottom. Do not remove more than one module at a time—doing so may cause unit to tip over and cause serious injury.
Page 14
10
Replacing Modules
1. Lift the module to the appropriate bay, resting the end of the module on the bay shelf. Use caution not to rest the module on the lower bezel cover.
2. Push the module into bay. Once it is half way in, slide the module sideways toward the center of the unit. Continue pushing module until fully inserted.
3. Press and turn fastener clockwise until locked.
4. Wait about 15 seconds as the module performs a start-up test and synchronizes with the other modules. Both the amber and green LEDs should be flashing. A green flashing LED will then confirm that the module is properly connected.
5. Replace the bezels.
Page 15
11
BATTERY RUN TIMES
Internal and Extended Battery Cabinets (minutes)
Load VA Load Watts
Quantity of
Battery Modules
Quantity of
Extended Battery Cabinets
123456789101 2 3 4
20,000 14,000 - - - - 7 9 - - - - 25 51 75 99
19,500 13,650 - - - - 7 9 - - - - 25 56 80 104
19,000 13,300 - - - - 7 9 - - - - 26 57 81 105
18,500 12,950 - - - - 8 11 - - - - 27 58 82 106
18,000 12,600 - - - - 8 12 - - - - 28 61 97 133
17,500 12,250 - - - - 8 12 - - - - 28 63 99 135
17,000 11,900 - - - - 8 12 - - - - 29 64 100 136
16,500 11,550 - - - - 9 13 - - - - 30 66 102 138
16,000 11,200 - - - 7 8 12 17 - - - 32 68 104 140
15,500 10,850 - - - 7 9 13 17 - - - 33 70 106 142
15,000 10,500 - - - 7 11 14 18 - - - 34 72 108 144
14,500 10,150 - - - 8 12 15 19 - - - 36 74 110 146
14,000 9,800 - - - 8 13 16 20 - - - 37 82 130 178
13,500 9,450 - - - 8 13 16 20 - - - 38 85 133 181
13,000 9,100 - - - 9 13 17 21 - - - 39 86 134 182
12,500 8,750 - - - 10 14 18 22 - - - 42 90 138 186
12,000 8,400 - - 7 12 16 20 24 28 - - 44 93 141 189
11,500 8,050 - - 7 12 17 21 25 29 - - 46 97 145 193
11,000 7,700 - - 7 12 17 21 26 30 - - 48 101 149 197
10,500 7,350 - - 8 14 18 23 28 32 - - 51 111 171 231
10,000 7,000 - - 9 15 19 24 29 34 - - 54 113 173 233
9,500 6,650 - - 10 15 21 26 30 36 - - 57 119 179 239
9,000 6,300 - - 11 16 22 28 33 38 - - 60 131 203 275
8,500 5,950 - - 12 17 23 29 35 40 - - 64 139 211 283
8,000 5,600 - 7 13 19 25 31 37 43 49 - 68 142 214 286
7,500 5,250 - 8 14 21 28 34 40 47 53 - 73 149 221 293
7,000 4,900 - 8 16 23 30 36 43 50 57 - 78 161 245 329
6,500 4,550 - 9 17 24 32 40 47 55 62 - 84 174 258 342
6,000 4,200 - 11 19 24 36 43 51 60 68 - 92 190 286 382
5,500 3,850 - 12 21 23 39 47 56 66 74 - 101 203 299 395
5,000 3,500 - 14 23 28 42 52 61 72 80 - 110 223 331 439
4,500 3,150 - 15 25 37 47 57 67 78 88 - 119 245 365 485
4,000 2,800 7 19 31 43 55 66 79 91 104 115 140 285 429 573
3,500 2,450 9 23 37 51 65 79 93 107 123 136 165 333 489 645
3,000 2,100 11 28 44 60 76 93 109 126 143 159 192 387 567 747
2,500 1,750 14 33 52 71 89 109 128 147 167 185 224 448 652 856
2,000 1,400 18 42 65 88 112 136 160 183 207 230 276 554 818 1,082
1,500 1,050 26 57 87 119 151 182 213 243 276 306 367 734 1,094 1,454
1,000 700 45 94 144 195 246 294 344 393 444 493 570 1145 1,685 2,225
900 630 50 105 160 216 273 327 382 436 492 547 627 1261 1,849 2,437
800 560 55 116 177 238 300 359 420 480 540 601 684 1378 2,014 2,650
700 490 61 128 195 263 331 396 463 529 594 661 752 1515 2,223 2,931
600 420 72 149 227 304 382 457 535 610 685 762 887 1776 2,628 3,480
500 350 82 171 258 346 433 518 606 691 777 862 1022 2036 3,032 4,028
NOTE: Backup times are in minutes and are based on resistive loading at an ambient temperature of 77°F (25°C). Extended battery cabinets are fully loaded with 12 battery modules. Extended battery cabinets assume that the UPS frame is fitted with all available battery modules.
Page 16
12
Page 17
Page 18
The Company Behind the Products
With over a million installations around the globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics:
Environmental systems—close-control air conditioning from 1 to 60 tons
Power conditioning and UPS with power ranges from 300 VA to more than 1000 kVA
Integrated systems that provide both environmental and power protection in a single, flexible package
Monitoring and control—from systems of any size or location, on-site or remote
Service and support through more than 100 service centers around the world and a 24/7 Customer Response Center
While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2002 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-23966 (3/02) Rev. 2
Technical Support
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Single-Phase UPS
800-543-2378
Outside the United States
614-841-6598
3-Phase UPS
800-543-2378
Environmental Control
800-543-2778
Italy
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
+39 049 9719 111
FAX: +39 049 5841 257
Asia
23F, Allied Kajima Bldg.
138 Gloucester Road
Wanchai
Hong Kong
+852 2 572 2201
FAX: +852 2 831 0114
Web Site
www.liebert.com
POWER PROTECTION
Extended Battery Cabinet for Nfinity
USER MANUAL
Loading...