Liebert Nfinity 208 User Manual

English
4 to 16 kVA
208 V / 240 V 60Hz
User Manual
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS.
This manual contains important instructions that should be closely followed during installation and maintenance of this UPS unit and during the installation and replacement of power and battery modules.
This product is designed for Commercial / Industrial use only. This product is not intended for use with life support and other U.S. FDA designated “critical” devices. Maximum load must not exceed that shown on the UPS rating label. See Limited Warranty.
WARNING: Lethal voltages may be present within this unit even when it is apparently not operating. Observe all cautions and warnings in this manual. Failure to do so MAY result in serious injury or death. Never work alone.
Observe the following precautions when working with batteries:
§ CAUTION: DO NOT dispose of battery modules in a fire; the battery module may explode.
§ CAUTION: DO NOT open or mutilate batteries; released electrolyte is harmful to skin and eyes, and may be toxic.
§ CAUTION: A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries:
§ Remove watches, rings or other metal
objects.
§ Use tools with insulated handles.
§ CAUTION: Lead-acid batteries contain
hazardous toxic materials. Handle, transport, and recycle in accordance with local regulations.
This UPS is designed for use on a properly grounded (earthed), 208/240 VAC, 60Hz supply, and is to be installed by qualified personnel.
ELECTROMAGNETIC COMPATIBILITY - The Nfinity™ UPS complies with the limits for a Class A digital device, pursuant to Part 15 of FCC rules. These limits provide reasonable protection against harmful interference in a commercial environment. This device generates, uses, and radiates radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operating this device in a residential area is likely to cause harmful interference, which the user must correct at their own expense.
Operate the UPS in an indoor environment only in an ambient temperature range of 0°C to +40°C (32°F to +104°F). Install it in a clean environment, free from conductive contaminates, moisture, flammable liquids, gasses, or corrosive substances.
Turn the UPS off and isolate the UPS before cleaning. Use only a soft cloth, never liquid or aerosol cleaners. Keep the front and rear vents free of dust accumulation that could restrict airflow.
Never block or insert any object into the ventilation holes or other openings.
This UPS contains user replaceable modules. No attempts should be made to access the interior of any module. See troubleshooting section on module replacement.
1
Glossary of Symbols
2
3
Introduction
General Description
Modes of Operation
Major Components
General Description
Congratulations on your purchase of Liebert’s Nfinity™ Uninterruptible Power System. As with every Liebert product, we stand behind our quality. If you have any questions concerning this UPS, please feel free to contact your local sales representative, or call the appropriate Technical Support number listed in the back of this manual.
To ensure proper installation and operation of this unit, please read this manual thoroughly.
SYSTEM DESCRIPTION
The Liebert Nfinity Power System is a modular UPS intended for use with workstations, servers, network, telecom or other sensitive electronic equipment. It provides continuous, high-quality AC power to your equipment, protecting it from any power disturbance due to blackouts, brownouts, surges or noise interference. The Nfinity modular UPS was designed to provide maximum system availability to business critical equipment. Nfinity is also an easily adaptable UPS system. By simply installing additional power or battery modules you can expand your current system capacity or extend your back-up runtime. Nfinity has a comprehensive user interface that can be configured according to the user’s preference. It also informs the user of details on the status of the UPS, and keeps a log of events.
FEATURES:
§ Up to 16 kVA of modular back-up power
§ Continuous power conditioning
§ A user-friendly interface for custom
configuration
§ Continuous system monitoring
§ Warning alarms and event logs
STANDARD COMPONENTS:
§ Power Modules – for power conditioning
§ Battery Modules – for back-up power
§ System Control Modules – for system
monitoring and communications
§ LCD display for comprehensive user indications and programmable controls
§ Output transformer for isolation
COMMUNICATIONS
§ Dry contacts
§ RS-232
§ Optional communications via
Intellislot™ communication ports
4
5
Modes of Operation
The Nfinity UPS is designed to operate as a true on-line system in the following modes:
Normal Mode
The Power Module rectifiers derive power from a utility AC source and supplies regulated DC power to the inverter. The module’s inverter regenerates precise AC power to supply the connected equipment. The battery charger maintains a float-charge on the battery.
Back-Up Mode
When AC utility fails, the connected equipment is supplied power by the inverter, which obtains energy from the battery modules. The output power equipment will not be interrupted during the failure or restoration of the AC utility source.
Auto Restart Mode
After a power outage and complete battery discharge, once the AC utility is restored, the UPS will automatically restart and resume supplying power to the connected equipment. This feature is enabled at the factory, but can be disabled by the user. The user can also program two auto restart delay settings:
1. Battery capacity level (%)
2. Countdown timer
Recharge Mode
When AC utility is restored, the unit will then automatically recharge the battery modules until they are fully charged.
Bypass Mode
The bypass provides an alternate path for power to the connected equipment that operates in the following manner:
Automatic
In the event of an internal failure or should the inverter overload capacity be exceeded, the UPS performs an automatic transfer of the connected equipment from the inverter to the bypass source.
Manual
Should the UPS need to be taken out of service for limited maintenance or repair, manual activation of the bypass will cause an immediate transfer of the equipment from the inverter to the bypass source.
6
Major Components
The following is a general description of each component and its functions. Please review this section carefully, as it will give you a better understanding as to how Nfinity operates.
Unit Frame
Nfinity’s frame houses all of the other system components. Looking at the front of Nfinity™, one will see a series of plastic bezels. By grabbing these bezels from the side and pulling out, you will remove the bezel to reveal the Battery / Power Module bays. The bottom bezel covers the cooling fans and the Manual Bypass Switch.
The User Interface Module is located above the Power / Battery Module bays for easy access. From here the user may find out various information about Nfinity’s condition. By moving the User Interface and setting it on top of the frame, you will see the System Control Module bays.
Nfinity’s frame with bezels removed
7
User Interface Module
The User Interface Module is the primary source of communication between the UPS and the user. From the interface, the user can:
§ View the status of the UPS
§ Custom configure the system
§ Review the event log to assist with
troubleshooting
§ Enable / disable the output power
§ Silence the audible alarm
For a more detailed explanation on how to operate the User Interface module, see the Controls and Indicators section of this manual.
System Control Module
User Interface Module
System Control Module
The System Control Module is the communicative backbone of the UPS. It gathers input from all modules and processes the data to control the operation of the system – including monitoring the condition of each module. An optional second System Control Module can be installed to provide full system functionality (operation and communication), in the unlikely event a Control Module should fail.
Under normal operation, the Status LED (green) will blink and the Fault LED (amber) will be off. For any condition other than this, check the Troubleshooting section of this manual.
8
Power Module
Under Normal Operation, the Status LED (green) will blink and the Fault LED (amber) will be off. For any
The Power Module maintains the condition of power in the Nfinity UPS. Each module is an independent 4-kVA unit, consisting of a power factor corrected rectifier, battery charger, and inverter, with associated monitoring and control­circuitry. The modules are paralleled to provide greater capacity and/or redundancy. Modules may be added or replaced on-line with no interruption or danger to the connected equipment.
Battery Module
The Battery Modules provide back-up power in the event of input utility failure. Each module contains a quantity of ten individual 12-volt valve regulated (VRLA) battery blocks with associated monitoring and controls to isolate the battery module in the event of a battery failure. The modules are paralleled to provide greater back­up time and/or redundancy. Modules may be added or replaced on-line with no interruption or danger to the connected equipment.
Power Module Battery Module
condition other than this, check the Troubleshooting section of this manual.
9
10
Installation
Preparation
Unloading
Cable Installation
Communications
Preparation
These installation instructions provide all the information needed for positioning the UPS (including environmental requirements) and for connecting the input and output power cables.
Inspection
Upon receiving the UPS, examine the packaging for any signs of mishandling or damage. If any damage is noted, call your local Liebert representative and/or notify your carrier.
Environment
Note: Operating in temperatures above 77° F
(25° C) will reduce battery life. The UPS environment must be free of conductive contaminants and excessive moisture (water condensation, flammable vapors, chemical fumes, or corrosive gasses and liquids).
Required Setup Equipment
The tools below are required in order to properly setup your UPS:
§ Pallet jack
Site Preparation
When deciding where to locate your UPS, consider the weight and size of the unit. Make sure that the structural integrity of the floor can withstand the weight of a fully loaded unit. Refer to the table below for size and fully populated weight considerations:
Model Max Weight H x W x D
8 bay 871 40” x 20” x 28”
12 bay 1186 53” x 20” x 28”
Check to make sure that your UPS will be located in a well-ventilated area with at least 12 inches behind it. The UPS is force cooled with the aid of internal cooling fans. Cooling air enters from the front of the UPS and is exhausted through ventilation grills in the back. It should also have at least 36 inches in front, in order to change modules when necessary.
§ 1/2” (13mm) ratchet or wrench
§ Torque Wrench (in / lb)
§ Flathead Screwdriver
§ #2 Phillips Screwdriver
The unit frame is bolted to the shipping pallet to ensure safety. It is recommended that a pallet jack be used to transport the unit to its operating location (prior to unbolting the unit).
11
Unloading
Unloading the UPS
CAUTION: This UPS is very heavy (see weight
on previous page). At least two people should be present to unload it off of the pallet.
1. Once the UPS is near the desired operating location, remove the cardboard cover.
2. Use a ratchet (1/2” or 13mm) or open-ended wrench to remove the four mounting bolts from the pallet brackets. Remove mounting brackets from the pallet and UPS. Keep brackets for future transportation of UPS, or for additional stability once in place.
3. Remove the metal ramp from the bottom of the UPS, rotating it. Fit ramp in pallet slot as shown above.
4. Using two people, slowly move the UPS down the ramp until the UPS is on level ground.
12
5. Once the UPS in its desired location, adjust the leveling feet to secure its position.
Stationary Mounting
Additional stability can be added by bolting the mounting brackets (used in shipping) to the floor.
For greater stability, use a higher-grade bolt. Refer to the dimensions below when drilling holes for stationary mounting.
13
Cable Installation
Wiring Preparation
WARNING: Please read this section thoroughly
before attempting to install wiring to this unit. Be sure that the unit is not connected to any AC utility power source before installing any wiring to this unit. This UPS should be installed by a qualified / certified electrician.
Removing the Cover Plates
On the back of the UPS, cover plates are over the input and output terminals, as shown on right. Remove these using a Phillips screwdriver. Keep screws and plates to one side.
Configuring the Bypass Voltage (TB2)
The UPS voltage is factory set to 208V. Should the user have a utility supply of 240V, the bypass voltage jumper will have to be changed to ensure correct output voltage.
Power Cable Installation
Refer to the charts below when selecting cables:
Power Cable and Protection Ratings
120V 208V 240V
Max Input Current Input Protection
Max Output Current
Input / Output Terminal Details
90°C rated copper wire is recommended
Notes:
If the start-up is on bypass the UPS has a 3­cycle inrush current that is 6 times the rated output current. This must be taken into account when selecting the overload protection device at the AC input supply distribution point. To avoid random tripping on start up, it is recommended that the AC input supply be protected with a circuit breaker capable of withstanding this initial inrush.
This UPS is fitted with EMI suppression filters. Earth leakage current is less than 40mA. Transient and steady state earth leakage currents may occur when starting the equipment. This should be taken into account when selecting ground current detection devices, as the earth leakage currents of both the UPS and load will be carried.
Input and output cables must be run in separate conduits.
A branch rated overcurrent protection device (circuit breaker or fused disconnect switch) must be installed for the AC output.
67A /
phase
79 A
69 A
100 A 90 A
77 A
67 A
2 AWG max (35 mm²) 6 AWG min (16 mm²) Torque Rating: 22-26 in/lb
(2.5-3 nm)
14
Input Wiring (TB1)
UPS contains an isolation transformer that generates a neutral conductor for the connected equipment. The UPS is a separately derived source
o ground bonding jumper. A grounding electrode conductor (GEC) must be installed in accordance with national and local wiring code /
To connect the input wiring, follow these steps:
1. Locate the input wiring access, remove the knockout and pull the three input wires through it, allowing some slack for installation.
2. Secure the conduit to the rear panel of the UPS.
3. Input Power cables connect to screw terminals on the Input Terminal Block located to the right of the Bypass Voltage Terminal. Connect the wires to the block connections as shown below. Using a torque wrench, turn the screws clockwise until tightened to the proper torque value. Insert the ground wire through the grounding lug and tighten it to the proper torque value.
Output Wiring (TB3)
Output wiring may be configured one of two different ways (240 / 120 or 208 / 120). Refer to the chart and diagram below when configuring the output wiring.
Note the Neutral / Ground jumper on the terminal above.
Voltage 120 208 240
Terminals
Only use the connections listed above. Other connections will produce non-standard voltages.
The Nfinity
1, 4 3, 4
2, 3
1, 3
Grounding Conductor Installation
An insulated grounding conductor must be identical in size, insulation material, and thickness as the grounded and ungrounded branch-circuit supply conductors. This cable must be green with or without one or more yellow stripes, and is to be installed as part of the branch circuit that supplies the unit or system. The grounding conductor is to be grounded to earth at the service equipment or, if supplied by a separately derived system, at the supply transformer or motor-generator set.
and contains a neutral t
regulations.
15
Connecting to External Panel Boards
UPS Output Panel Board
UPS Output Panel Board
If connected equipment will operate at 240 / 120 VAC, use a standard single-phase panel board.
If connected equipment will ONLY operate at 208 / 120 VAC, use a three-phase panel board.
Ensure that all 120V equipment is connected L1 – N, L3 – N. Ensure that all 208V equipment is connected L1 – L2.
Input
Input
REPO Switch
Nfinity is equipped with a Remote Emergency Power Off (REPO) Switch.
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS input feeder breaker to remove all sources of power to the UPS and connected equipment to comply with national and local wiring codes / regulations.
Remove jumper before wiring.
1 = 24V DC, 35 mA 2 = sense 3 = sense 4 = ground
If the installation does not require connection to a REPO system, the jumper must be removed.
Caution: To maintain safety (SELV) barriers and electromagnetic compatibility signal cables should be segregated and run separately from power cables.
16
Communication
COM Ports
Nfinity is able to communicate through multiple communication ports simultaneously.
Pin Assignment
COM 1 – Relay Contacts
Relay contacts are available through a DB-9F communications connector. Contact closure provides the following:
Pin Assignment
1 Low Battery (normally open)
UPS shutdown in battery mode
4
(5-12 V DC for 1.5 sec) 5 Common 7 Low Battery (common) 8 On Battery (common) 9 On Battery (normally open)
The contacts are rated 48V DC, 1 Amp maximum and are compatible with the SiteNet MultiLink software.
COM 2 – Serial
Nfinity is able to communicate via Liebert proprietary protocol. The pin-out configuration of the DB-9 connector is:
Pin Assignment
2 Transmit Data 3 Receive Data 5 Common
Intellislot™ Ports
The following communication cards may be used with Nfinity:
Intellislot™ SNMP cards – allows the Nfinity communicate intelligently with your Ethernet network. The SNMP card must be installed in port 1; any additional cards can be added in consecutive ports.
Intellislot™ MultiPort4 cards– allows up to four client computer systems to simultaneously monitor the status of Nfinity.
Intellislot™ Relay Contacts cards – provides contact closures for remote monitoring of alarm conditions; On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS signals. It will integrate with AS400 computers (additional cable required) and other monitoring systems.
17
Operating Instructions
Controls and Indicators
Operating Procedures
Main Menu
18
Controls and Indicators
A Warning has occured. Consult event log.
Display Controls
The Front Display Panel informs the user of the status of the UPS, and lets him configure the UPS to his own needs or preferences through the user interface.
It consists of a series of Status LED’s, a 4 line by 20 character LCD display window, and buttons for navigation (as displayed above).
Buttons
Refer to the legend below in order to properly navigate the Nfinity User Interface.
LEDs
Refer to the legend below to indicate occurrence when an LED is lit.
!
Fault / Warning Solid­ Flashing-
AC Input
On Bypass
Inverter On
On Battery
AC Output
A UPS fault condition has occured.
- AC utility is available
- The Bypass is supplying the power
- The Inverter is supplying the power
- Battery is supplying power to the inverter
- Power is available to supply the load
19
Status LED Modes
LED Off
LED Flashing
LED On
UPS is Off or Initializing
UPS On, Utility Good and Output Off
UPS On, Utility Good and Output On
(Normal Operation)
UPS On, Utility Bad and Output On
(On Battery Operation)
UPS On, Utility Bad, and Output Off
Unit in Bypass Operation
(Manual or Automatic)
Unit in Manual Bypass Operation with Utility out of Bypass Operation Range
Shutdown Due to end of Discharge
20
Navigating the Menu
In order to review or change any settings on the UPS, it must be navigated using the buttons seen on the previous page. Because some menus contain more than four rows of information, you may see an arrow on the display pointing up or down (as shown below) – indicating to scroll using the $ or # buttons.
If you are scrolling through any of the main menus, items will scroll one line at a time with the menu heading on the top line:
Pressing # reveals:
Note the arrows on the screen indicating that the user scroll up or down to reveal more information.
21
Operating Procedures
Start-up and Initialization
Follow these steps in order to start up the UPS.
1. Close Input Circuit Breaker (CB1) and close the Enable Switch (SW2). Ensure the manual bypass switch is in UPS position. You should see the following on the LCD display window:
2. Press & button.
Manual Transfer to Bypass
In the event of a UPS overload or failure, the UPS will transfer to bypass via its automatic bypass switch. It is possible for the user to manually transfer the UPS to bypass by operating the manual bypass switch located behind the lowest front cover to the bypass position. To transfer the UPS from bypass to normal mode, simply operate the manual bypass switch back to the UPS position.
It should be noted that the load is not protected from utility interruptions when in bypass mode.
3. Press % to access the main menu.
Shutting down the UPS
Use the following procedure to power down the UPS.
1. Press & to disable power from the connected equipment.
2. Verify request to disable the output by pressing %.
3. Turn off the Enable Switch (SW2). Open the Input Circuit Breaker (CB1).
22
Main Menu
After initialization, the % button will take you to the main menu. From here you may check on the status of the UPS, review the event and alarm log, configure your UPS, and even receive instructions on replacing modules. The main menu is divided into five sub-menus as shown below:
Use the $ # buttons to select the desired menu item and press % to access the appropriate sub-menu.
23
UPS Status Screen
From the main menu the user may select UPS Status and press %. Once at the UPS Status Screen, the user may access any information on the present condition of the UPS. Note the chart below when reviewing the UPS. Any underlined text indicates measured parameters.
24
UPS Configuration Screen
Main Menu
Review Settings
Follow this procedure to review your UPS configuration settings. Any underlined text indicates factory default values.
Follow the menus below by pressing # or $ to review the settings:
>
UPS Configuration
>
Review Settings
Voltage Settings
Voltage Settings Input 208/120 LLG
Battery Settings
Battery Settings Test intervl weeks on at :
Wed0600
Low Batt Warn : min
Alarm Settings
Alarm Settings
Power: Max Load: kVA
N+1
2
2
xx.x
Service Contact
Service Contact Liebert Corp.
1-800-543-2378
25
Change Configuration Settings
Main Menu
Change Settings Menu
Starting from the Main Menu, locate and press UPS Configuration. From the UPS Configuration screen, select the Change Settings option. Here one may configure Nfinity from a large variety of selections. Items indicated by an asterisk (*) or underlined are the selected settings.
>
UPS Configuration
>
Set Password: Set a Password to prevent unauthorized users from changing the configuration of the Nfinity. It can be up to 7 characters in length. Once set, the password will be required to change the configuration.
Auto Battery Test: Configure when and how often the Nfinity’s automatic battery test will run. This test is designed to ensure Battery system integrity and warn of early problems.
Change Settings
Input Voltage: Select the required input voltage
setting. This voltage must match the bypass voltage jumper setting.
Input Voltage 208/120 LLNG
*
208/120 LLNG
Low Battery Warning: Notifies user as to how much runtime is available. Can be set from 1 to 30 minutes.
26
Auto Restart: Automatically restarts once both
delay parameters (battery capacity percentage and countdown timer) are met.
Set Date/Time: Allows user to enable DST (Daylight Savings Time), change the Day, Date and Time setting on Nfinity. When enabled, the time will automatically adjust to Daylight Savings.
User Settings: From here one can enter the UPS ID or adjust the contrast of the user interface LCD.
Max Load Alarm Set: Allows an alarm to set when Nfinity’s load reaches a specific level.
UPS Shutdown Delay: Delays UPS shutdown for specified amount of time after receiving shutdown command via communications (serial or SNMP).
27
Redundant Alarm Set: Sets Alarm to notify
user when redundancy is no longer available.
UPS Test: Allows user to test the Batteries, LED’s, LCD, or Alarm.
Service Contact: Set a contact for the user to reach if problems occur.
Remote Shutdown: Enables / Disables the Remote Communications Shutdown. If you are using SiteNet™ software, this parameter should be enabled in order for the UPS output to be turned off once the operating system has been shutdown.
External Battery: Sets total amp-hour for external batteries to provide a more accurate runtime remaining value on the LCD display and through communications.
Enter in the following when using the External Battery Cabinets with Chargers. (P/N: PB10SLF105WC120)
# Cabinets AH Value
1 0105 2 0210 3 0315 4 0420 5 0525 6 0630
28
Event Log
One may open the Event Log from the main menu. By accessing the Event Log, the user may scroll through the Nfinity’s past 255 occurrences in chronological order by pressing
the $ # buttons.
The typical event log screen will display the event number and reference code on the first line. The purpose of this code is to assist factory trained service personnel in troubleshooting. Please make a note of the code number when contacting technical support. The second line contains the event description. The third line will have either more detail about the event, a serial number indicating as to which module the event occurred, or be left blank. The last line will show the date and time the event occurred.
Press " to go back to the main menu. In the event of an event / alarm, the User
Interface LCD will display the last message regardless of the default screen. A list of possible event / alarm messages is displayed at right. If you encounter one of these or other messages and are unsure of the corrective action to take, please contact a qualified Liebert representative at the number listed in the back of this manual.
For more information regarding events, consult the troubleshooting section.
Alarm Log
When an alarm sounds, the User Interface LCD will display a general explanation as to what the alarm is indicating. These alarms will also be displayed in the Alarm Log, which will display the last 32 alarm messages. To view these
messages in chronological order, press the $ # buttons.
The first line of a typical alarm log screen will display the reason for the alarm occurrence. The second line will give a more specific detail of the occurrence (i.e.; module serial number).
Press " to go back to the main menu. Below is a list of possible events / alarms.
Occurrence Event Alarm
Battery EOD Battery Mod Removed Battery Module Added Battery Module Fail Battery Test Fail Battery Test Pass Display Panel Added Display Panel Removed Firmware Error General UPS Fail Main Control Fail with redundant control Max Load Alarm Power Mod Added Power Mod Failure Power Mod Removed Red. Power Alarm Transformer Fan Fail UPS Auto Restart UPS CANBus Fail UPS Low Battery UPS on Battery UPS on Bypass (auto) UPS on Bypass (manual) UPS Shutdown UPS Shutdown Imminent Wrong Voltage
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
4 4
4
29
Module Replacement
For more details on module replacement, consult the troubleshooting section of this user manual.
The user interface also supplies instructions for removing and replacing modules. From the main menu, access the module replacement screen and select the type of module. Refer to the screens below for reference:
30
Troubleshooting
Module LED Indication
Alarm Messages
Module Replacement
31
Alarm Messages
In the event of an alarm, the User Interface LCD will display the last message regardless of the default screen. A list of possible alarm messages is displayed below. If you encounter one of these or other alarm messages and are unsure of the corrective action to take, please contact a qualified Liebert representative at the number listed in the back of this manual.
Alarm Message
Battery Module Failure Battery Module is no longer working
Power Module Failure A Power Module is no longer working
General UPS Failure The UPS is operating on bypass. Contact a Liebert Global Services at
Battery Test Failed Unit has detected a battery module problem. Verify the battery status via the display
Redundant Power Alarm The UPS is no longer redundant. Replace faulty module to regain
Maximum Load Alarm Maximum load has been exceeded. Insert additional modules to increase
System Control Module Failure Firmware version error Firmware is incompatible. Download latest firmware version from
On Battery Load is currently being supplied from UPS. Wait for input AC to return. Low Battery Battery power is low. Allow batteries time to recharge. UPS on Bypass (auto) UPS switched to auto bypass. Alarm screen should indicate reason
UPS on Bypass (manual) User switched UPS to manual bypass. When ready, switch back to UPS. Transformer fan failure The transformer cooling fans are no longer
UPS CanBus Failure The internal communications are not
UPS Shutdown Imminent The UPS is about ready to shut down Check for faulty modules, output
Wrong Voltage The input voltage configuration and bypass
Cause Action
Refer to Module LED indication section
properly.
properly.
System Control Module no longer working properly.
working properly.
working properly.
jumper settings DO NOT MATCH.
for corrective action. Replace the faulty Power Module by following the procedure in this manual.
1-800- 543-2378.
and perform self-battery test.
redundancy.
load capacity or reduce current load. Replace faulty module.
www.liebert.com.
for auto bypass.
Contact a Liebert Global Services at 1-800- 543-2378. Contact a Liebert Global Services at 1-800- 543-2378.
overloads, or Contact a Liebert Global Services at 1-800- 543-2378. Check to make sure the bypass voltage matches the input voltage and ensure the input voltage configuration matches the bypass jumper setting.
32
Module LED Indication
On every Battery, Power or Control Module are two LEDs to help inform the user of the module status. Refer to the chart below for Power and Battery Modules:
Status LED
(Green)
OFF
OFF ON Module is initializing (max 10 seconds*). FLASHING OFF Normal Operation FLASHING FLASHING Module is in start-up qualification mode, or module warning. ** FLASHING ON Module failed, is off-line and module control is functioning.
OFF FLASHING
ON OFF ON ON ON FLASHING
* If this persists for more than 10 seconds, check to verify the lever is in the down position or the module is faulty. ** If both Green and Amber LEDs are flashing for more than 30 seconds, then re-insert module.
Fault LED
( Amber)
OFF
Module Status
Module not inserted into frame. System is OFF.
Abnormal operation, re-insert module. If this persists, call Liebert Global Services at 1-800- 543-2378.
33
Module Replacement
Occasionally a control, battery or power module will need to be removed or replaced. Follow the instructions below when such an event occurs. To order additional modules, contact your Liebert representative or call 1-800-LIEBERT.
Removing Modules
1. Remove bezel cover of appropriate module. When replacing a Power or Battery Module, verify the faulty module by confirming the amber LED is lit.
2. If removing a Control or Power Module with no redundant modules, switch UPS to manual bypass.
3. Pull out and lift the lever if replacing a Control or Power Module, then turn fastener counter-clockwise until it is loosened.
4. Start to pull out module. About 2/3 out it will stop. Slide module away from the center of the UPS. Continue to pull until module is removed. (Seen at right) Caution: Battery Modules are heavy (66 lbs, 30 kg). Make sure to use two people when removing a Battery Module.
5. Dispose of module in an environmentally responsible way that complies with local codes / regulations or return to Liebert for proper disposal.
Note: Battery Modules may contain shipping screws. These screws may be removed and discarded.
34
WARNING
POTENTIAL TIP HAZARD
Install all modules starting from bottom to top bays. For module removal, start from top to bottom bays. Do Not remove more than one module at a time. Failure to do so may cause unit to tip over and cause serious injury.
Replacing Modules
1. Lift module to appropriate bay, resting end of module on bay shelf. Use caution not to rest the module on the lower bezel cover.
2. Push module into bay. Once half way in, slide module sideways toward the center of the UPS. Continue pushing module fully inserted.
Replacing the User Interface
1. Lift off user interface and set it on top of the UPS frame.
2. The attached cable will be connected to an Intellislot card, found in a port between the control modules.
3. Press and turn fastener clockwise until locked. If replacing a Control or Power Module, press lever down.
4. Wait about 15 seconds as the module performs a start-up test and synchronizes with the other modules. Both the amber and green LEDs should be flashing. A green flashing LED will then confirm the module is properly connected.
5. If UPS was placed in bypass manually, transfer back to UPS operation.
6. Replace bezels.
3. Disconnect the cable from the Intellislot card.
4. Plug the new user interface cable into the Intellislot card.
5. Set replacement User Interface into proper position.
35
Scheduled Maintenance
Maintenance
Proper Care
Replacing Fan Filters
36
Maintenance
Proper Care
Keeping your Liebert Nfinity UPS operating properly is imperative to optimal performance and life of the unit. It is recommended that a certified technician perform preventive and corrective maintenance. Liebert Global Services (LGS) is dedicated to ensuring the highest level of performance and unmatched support for your Nfinity UPS. Contact an LGS representative at 1-800-LIEBERT for services to guarantee maximum reliability and system availability.
Scheduled Maintenance
It is recommended the following maintenance is performed at least monthly:
§ Clean unit
§ Clean / replace filters
§ Verify proper airflow
It is recommended the following maintenance is performed annually:
§ Verify all power modules are operating properly.
§ Verify all battery modules are operating properly.
§ Verify redundancy (if applicable).
Replacing Fan Filters
Nfinity’s intake fans contain filters that will need to be replaced / cleaned periodically, depending on the surrounding environment. Check by removing the bottom bezel and noting the condition of the two filters. If filters are dirty, replace them by removing the plastic cover over the filter frame and inserting a new filter in its place. Use caution when replacing filters when fans are running.
The fan filters are washable and can be reused. To wash filters, place them under a running faucet (with the dirt side down) to remove dirt and dust. Blot dry with a towel and allow air­drying before reusing.
37
Warranty
Reference
Specifications
Battery Run Times
Technical Support
38
Specifications
General & Environmental Units 4 8 12 16
kVA 4 8 12 16 Unit Rating
kW 2.8 5.6 8.4 11.2 Conducted and Radiated EMC Levels FCC Part 15, Class A Compliant Safety Standards UL 1778; c-UL Compliant Immunity Standards IEEE C62.41, Category B
Mechanical Units 8 Bay 12 Bay
Dimensions:
Environmental Units
Operating Temperature (max) F (C) 32° - 104° (0° - 40°) Relative Humidity 0-95% non-condensing Maximum operating altitude Ft. (M) 10,000 (3000) Nominal heat dissipation BTU/Hr 1062 2124 3186 4248 Acoustic noise level dBA <62 @ 1 meter
Input Data Units
Nominal input voltage VAC 170 to 276 Power factor Cos Ø >.98 Input frequency (nominal) Hz 60 Input frequency range Hz 40-70
Battery Module Units
Number of lead acid batteries 10 Number of battery cells 60 Battery capacity A/hr 9
Autonomy time (full load)
Maximum charge current (full load) A 3 Nominal Voltage VDC 120 Recharge Time Hrs 3-5 (to 90% capacity)
Output Data Units
Output voltage VAC 208/120 or 240/120 Voltage regulation % ±3 Voltage stability (100% step load) % ±7 Recovery time msec 96
Voltage distortion: Output frequency Hz 60
Efficiency at 100% load % 89 Output overload capability %
Width 20 (508.0) 20 (508.0) Depth 28 (711.2) 28 (711.2) Height
In (mm)
mins
40 (1016.0) 53 (1346.2)
6
(With an equal number of Battery & Power Modules,
in a non-redundant configuration)
%
<3 THD, linear load
<7 THD, non-linear load
110-125% for 10 min 126-150% for 10 sec
>151 – 200% for 2 cycles
39
Battery Run Times
8 Bay Frame
Internal and External (minutes)
Load Load
VA Watts 1 2 3 4 5 6 7 1 2 3 4 5 6 16,000 11,200 - - - 6 - - - 24 60 100 120 180 240 15,500 10,850 - - - 6 - - - 26 63 107 140 195 255 15,000 10,500 - - - 6 - - - 27 67 114 160 210 270 14,500 10,150 - - - 6 - - - 28 70 120 180 225 285 14,000 9,800 - - - 7 - - - 30 73 127 190 240 300 13,500 9,450 - - - 7 - - - 31 77 135 200 252 320 13,000 9,100 - - - 8 - - - 32 80 142 210 264 340 12,500 8,750 - - - 8 - - - 34 85 150 220 276 360 12,000 8,400 - - 6 9 12 - - 36 90 157 230 288 375 11,500 8,050 - - 6 9 13 - - 38 95 165 240 300 390 11,000 7,700 - - 6 10 14 - - 40 100 173 255 320 405 10,500 7,350 - - 7 10 15 - - 42 110 180 270 340 420 10,000 7,000 - - 7 11 18 - - 45 120 195 285 360 450
9,500 6,650 - - 8 13 18 - - 50 130 210 300 390 480 9,000 6,300 - - 9 14 19 - - 53 140 225 320 420 510 8,500 5,950 - - 9 15 20 - - 57 150 240 340 450 540 8,000 5,600 - 6 10 18 21 26 - 60 160 260 360 480 570 7,500 5,250 - 6 11 18 23 28 - 65 170 280 390 510 600 7,000 4,900 - 7 13 19 25 29 - 70 180 300 420 540 660 6,500 4,550 - 8 14 21 27 30 - 80 200 330 480 600 720 6,000 4,200 - 9 18 24 29 36 - 90 220 360 510 660 810 5,500 3,850 - 10 19 26 30 39 - 100 240 420 540 720 900 5,000 3,500 - 12 20 29 36 43 - 120 270 450 600 810 1,000 4,500 3,150 - 14 24 30 40 46 - 140 300 480 720 900 1,100 4,000 2,800 6 18 26 36 43 49 52 160 360 540 810 1,080 1,200 3,500 2,450 7 19 29 41 48 52 56 180 420 600 900 1,260 1,440 3,000 2,100 9 24 36 46 51 56 62 210 480 720 1,050 1,440 1,620 2,500 1,750 12 29 43 51 56 63 68 240 600 900 1,200 1,620 1,800 2,000 1,400 18 36 50 57 64 68 72 360 720 1,200 1,440 1,800 2,880 1,500 1,050 24 46 56 65 69 73 74 480 900 1,440 2,400 3,000 3,600 1,000 700 36 56 68 73 74 75 78 720 1,440 2,400 3,600 4,320 4,320
900 630 39 59 69 73 75 78 78 900 1,800 3,000 4,320 4,320 4,320 800 560 43 63 72 74 76 78 79 1,080 2,100 3,600 4,320 4,320 4,320 700 490 48 68 73 75 78 79 79 1,260 2,400 4,320 4,320 4,320 4,320 600 420 51 69 74 77 79 79 80 1,440 3,000 4,320 4,320 4,320 4,320 500 350 56 72 75 78 79 80 80 1,440 3,600 4,320 4,320 4,320 4,320
Note: Back-up times are in minutes and are based upon resistive loading at an ambient of 25°C, for non-redundant (standard) configurations. Back-up times for external battery cabinets with chargers include internal battery modules that are equal to the number of power modules in the UPS frame.
Quantity of
Battery Modules
External Battery Cabinets with charger
Quantity of
40
Battery Run Times
12 Bay Frame
Internal and External (minutes)
Load Load
VA Watts 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 16,000 11,200 - - - 6 8 10 13 18 - - - 24 60 100 120 180 240 15,500 10,850 - - - 6 8 11 14 18 - - - 26 63 107 140 195 255 15,000 10,500 - - - 6 9 11 15 18 - - - 27 67 114 160 210 270 14,500 10,150 - - - 6 9 12 15 19 - - - 28 70 120 180 225 285 14,000 9,800 - - - 7 9 13 18 19 - - - 30 73 127 190 240 300 13,500 9,450 - - - 7 10 14 18 20 - - - 31 77 135 200 252 320 13,000 9,100 - - - 8 11 14 18 21 - - - 32 80 142 210 264 340 12,500 8,750 - - - 8 11 15 19 22 - - - 34 85 150 220 276 360 12,000 8,400 - - 6 9 12 18 20 23 26 - - 36 90 157 230 288 375 11,500 8,050 - - 6 9 13 18 20 24 27 - - 38 95 165 240 300 390 11,000 7,700 - - 6 10 14 19 21 25 29 - - 40 100 173 255 320 405 10,500 7,350 - - 7 10 15 19 23 27 29 - - 42 110 180 270 340 420 10,000 7,000 - - 7 11 18 20 25 28 30 - - 45 120 195 285 360 450
9,500 6,650 - - 8 13 18 21 26 29 31 - - 50 130 210 300 390 480 9,000 6,300 - - 9 14 19 24 27 30 36 - - 53 140 225 320 420 510 8,500 5,950 - - 9 15 20 25 29 31 38 - - 57 150 240 340 450 540 8,000 5,600 - 6 10 18 21 26 30 36 39 43 - 60 160 260 360 480 570 7,500 5,250 - 6 11 18 23 28 30 38 42 45 - 65 170 280 390 510 600 7,000 4,900 - 7 13 19 25 29 36 41 44 48 - 70 180 300 420 540 660 6,500 4,550 - 8 14 21 27 30 38 43 47 50 - 80 200 330 480 600 720 6,000 4,200 - 9 18 24 29 36 42 46 49 51 - 90 220 360 510 660 810 5,500 3,850 - 10 19 26 30 39 44 49 51 54 - 100 240 420 540 720 900 5,000 3,500 - 12 20 29 36 43 48 51 54 56 - 120 270 450 600 810 1,000 4,500 3,150 - 14 24 30 40 46 50 54 57 59 - 140 300 480 720 900 1,100 4,000 2,800 6 18 26 36 43 49 52 56 59 63 66 160 360 540 810 1,080 1,200 3,500 2,450 7 19 29 41 48 52 56 60 64 68 69 180 420 600 900 1,260 1,440 3,000 2,100 9 24 36 46 51 56 62 65 68 69 72 210 480 720 1,050 1,440 1,620 2,500 1,750 12 29 43 51 56 63 68 69 72 73 73 240 600 900 1,200 1,620 1,800 2,000 1,400 18 36 50 57 64 68 72 73 74 74 75 360 720 1,200 1,440 1,800 2,880 1,500 1,050 24 46 56 65 69 73 74 75 76 78 78 480 900 1,440 2,400 3,000 3,600 1,000 700 36 56 68 73 74 75 78 78 79 79 80 720 1,440 2,400 3,600 4,320 4,320
900 630 39 59 69 73 75 78 78 79 79 80 80 900 1,800 3,000 4,320 4,320 4,320 800 560 43 63 72 74 76 78 79 79 80 80 80 1,080 2,100 3,600 4,320 4,320 4,320 700 490 48 68 73 75 78 79 79 80 80 81 81 1,260 2,400 4,320 4,320 4,320 4,320 600 420 51 69 74 77 79 79 80 80 81 81 82 1,440 3,000 4,320 4,320 4,320 4,320 500 350 56 72 75 78 79 80 80 81 82 82 82 1,440 3,600 4,320 4,320 4,320 4,320
Note: Back-up times are in minutes and are based upon resistive loading at an ambient of 25°C, for non-redundant (standard) configurations. Back-up times for external battery cabinets with chargers include internal battery modules that are equal to the number of power modules in the UPS frame.
Quantity of
Battery Modules
External Battery Cabinets with charger
Quantity of
41
Warranty
Liebert Corporation extends the following LIMITED WARRANTY to the purchaser and to its customer (collectively referred to as the "Purchaser"): the enclosed Uninterruptible Power System (UPS) and components are free from defects in materials and workmanship under normal use, service, and maintenance FOR A PERIOD OF TWO YEARS FROM THE DATE OF ORIGINAL PURCHASE from Liebert or the Liebert dealer or retailer. THE FOREGOING WARRANTY IS THE ONLY WARRANTY GIVEN AND NO OTHER WARRANTY IS PROVIDED, EXPRESS OR IMPLIED, INCLUDING WITHOUT LIMITATION, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Certain aspects of disclaimers are not applicable to consumer products acquired by individuals and used for personal, family, or household purposes (as distinguished from industrial or other purposes). Local laws may not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you. This warranty gives you specific legal rights, and you may have other rights, which vary according to local law. Certain repairs or services are the responsibility of the Purchaser and the Purchaser is expected to pay for them. This warranty does not extend either to products with removed or altered serial numbers or to any losses or damages due to act of God or source external to the product, misuse, accident, abuse, neglect, negligence, unauthorised modification, alteration, or repair, use beyond rated capacity, or improper installation, maintenance, application or use, including, without limitation, use in a manner contrary to the accompanying instructions or applicable codes. WARNING: Warranty is void if the battery is allowed to discharge below the minimum battery cut-off point. The battery must be recharged every four (4) to six (6) months when not in use. If the UPS fails to conform to the above warranty within the two-year warranty period, Liebert will repair or replace the UPS, at Liebert's option. Repairs or replacements are warranted for the remainder of the original warranty period. Purchaser, to make a warranty claim, should call to obtain a Returned Goods Authorisation number and shipping instructions. Return transportation costs to Liebert are the responsibility of the Purchaser.
Due to the diversity of applications and considerations to be applied in each case, Liebert does not recommend or knowingly sells its products for
such use. The responsibility for risk assessment and management in applications where the malfunction or failure of the UPS could be reasonably expected to give rise to a risk of human life shall be the sole responsibility of the purchaser. Liebert accepts no liability for consequential harm in such applications.
LIMITED WARRANTY
"LIFE SUPPORT" APPLICATIONS
42
While every precaution has been taken to ensure accuracy and completeness of this literature, Liebert Corporation assumes no
for
damages resulting from use of this information
© 2000 Liebert Corporation. All rights reserved throughout the world. Specifications subject to
® Liebert and the Liebert logo are registered
demarks of Liebert Corporation. All names
referred to are trademarks or registered
(7/00) Rev. 2
Nfinity™ Power System
208 V / 240 V 60 Hz
4 to 16 kVA
Technical Service and Support
Worldwide FAX tech support +614-222-5877 option #4
Worldwide Support. +614-841-6755 or 1-800-222-5877
The Company Behind The Products With over a million installations around the
globe, Liebert is the world leader in computer protection systems. Since it’s founding in 1965, Liebert has developed a complete range of support and protection systems for sensitive electronics:
Environmental systems: close-control air conditioning from 1.5 to 60 tons.
Power conditioning and UPS with power ranges from 250 VA to more than 1000 kVA.
Integrated systems that provide both environmental and power protection in a single, flexible package.
Monitoring and control — on-site or remote — from systems of any size or location
Service and support, through more than 100 service centers around the world, and a 24­hour Customer Response Center.
U.S.A.
U.K. +44 (0) 1628 403200
France +33 (0) 1 43 60 01 77
Germany +49 89 99 19 220
Netherlands +31 (0) 475 503333
E-mail upstech@liebert.com
Web site http://www.liebert.com
Italy +39 02 98250 324
1-800-LIEBERT
responsibility, and disclaims all liability or for any errors or omissions.
change without notice.
tra trademarks of their respective owners.
SL-23950
43
Loading...