This manual contains important instructions that should be closely followed during installation and
maintenance of this UPS unit and during the installation and replacement of Power and Battery
Modules.
This product is designed for Commercial/Industrial use only. This product is not intended for use
with life support and other U.S. FDA-designated “critical” devices. Maximum load must not exceed
that shown on the UPS rating label.
WARNING
!
Lethal voltages may be present within this unit even when it is apparently not operating.
Observe all cautions and warnings in this manual. Failure to do so MAY result in serious
injury or death. Never work alone.
Observe the following precautions when working with batteries:
CAUTION
!
DO NOT dispose of Battery Modules in a fire because the modules may explode.
DO NOT open or mutilate batteries; released electrolyte is harmful to skin and eyes and may
be toxic.
A battery can present a risk of electrical shock and high short-circuit current. The following
precautions should be observed when working on batteries:
• Remove watches, rings and other metal objects.
• Use tools with insulated handles.
Lead-acid batteries contain hazardous toxic materials. Handle, transport and recycle in
accordance with local regulations.
This UPS is designed for use on a properly grounded (earthed), 208/240 VAC, 60 Hz supply and is to
be installed by qualified personnel.
Electromagnetic Compatibility—The Nfinity™ UPS complies with the limits for a Class A digital
device, pursuant to Part 15 of FCC rules. These limits provide reasonable protection against harmful
interference in a commercial environment. This device generates, uses and radiates radio frequency
energy and, if not installed and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operating this device in a residential area is likely to cause
harmful interference which users must correct at their own expense.
Operate the UPS in an indoor environment only in an ambient temperature range of 32°F to +104°F
(0°C to +40°C). Install it in a clean environment, free from conductive contaminates, moisture, flammable liquids, gases and corrosive substances.
Turn the UPS off and isolate the UPS before cleaning. Use only a soft cloth, never liquid or aerosol
cleaners. Keep the front and rear vents free of dust accumulation that could restrict airflow.
Never block or insert any object into the ventilation holes or other openings.
This UPS contains user replaceable modules. No attempts should be made to access the interior of
any module. See 4.3 - Module Replacement.
1
GLOSSARYOF SYMBOLS
Risk of electrical shock
Indicates caution followed by important instructions
AC input
AC output
i
Requests the user to consult the manual
Indicates the unit contains a valve-regulated lead acid
battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
OFF
ON
Standby
No telecommunication connection
Locked position
Unlocked position
Contact closure signals
Serial communications
2
1.0INTRODUCTION
1.1General Description
Congratulations on your purchase of Liebert’s Nfinity™ Uninterruptible Power System. As with
every other Liebert product, we stand behind our quality. If you have any questions concerning this
UPS, please feel free to contact your local dealer or Liebert representative or call the appropriate
Technical Support number listed on the back of this manual.
To ensure proper installation and operation of this unit, please read this manual thoroughly.
For details on product warranty and registration, see 6.1 - Product Warranty Registration.
1.1.1System Description
The Liebert Nfinity Power System is a modular UPS available in 8 & 12 bay frames. It is intended for
use with workstations, servers, network, telecom and other sensitive electronic equipment. It provides continuous, high-quality AC power to your equipment, protecting it from any power disturbance
due to blackouts, brownouts, surges or noise interference.
The Nfinity modular UPS was designed to provide maximum system availability to business-critical
equipment. Nfinity is also an easily adaptable UPS system. By simply installing additional Power or
Battery Modules, you can expand your current system capacity or extend your backup runtime.
Nfinity has a comprehensive user interface that enables configuration according to the user’s preference. It also informs the user of details on the status of the UPS and keeps a log of events.
Introduction
Features
• Up to 16 kVA of modular backup power
• Continuous power conditioning
• A user-friendly interface for custom configuration
• Continuous system monitoring
• Warning alarms and event logs
• Internal automatic & manual bypass
Standard Components
• Power Modules - for power conditioning
• Battery Modules - for backup power
• System Control Modules - for system monitoring and communications
• LCD Display - for comprehensive user indications and programmable controls
• Output Transformer - for isolation
• REPO Switch Connection
Communications
• Dry contacts
• RS-232
• Optional communications via Intellislot™ communication ports
3
Figure 1Front and back views (12 bay model shown)
Introduction
Power
Module
Bays
Battery
Module
Bays
User Interface
!
Control
Switch (SW2)
ESC
REPO
Connection
Intellislot™
Communications Ports
DB-9
Communication
Ports
Output Power
Terminal
Manual
Bypass
Switch
(SW1)
Intake
Cooling Fans
FRONT VIEW
with bezels
removed
BACK VIEW
with access
plates removed
Refer to the table below for size and fully populated weight considerations.
Table 1Nfinity weight and dimensions
ModelMax Weight - lb (kg)W x D x H - in. (mm)
8 bay855 (388)20 x 28 x 40 (508 x 711 x 1016)
12 bay1176 (534)20 x 28 x 53 (508 x 711 x 1346)
208/240 Jumper
Input Power
Terminal
Input Earth
Terminal
Input Circuit
Breaker (CB1)
External Battery
Connection
4
1.2Modes of Operation
Introduction
EMI
FILTER
Normal Mode
USER
INTERFACE
POWER
MODULE(S)
BATTERY
MODULE(S)
COMMUNICATIONS
CONTROL
INTERFACE
MANUAL
BYPASS
OUTPUT &
BYPASS
CONTACTOR
SYSTEM
CONTROL
MODULE(S)
OUTPUTINPUT
OUTPUT
TRANSFORMER
POWER
CONTROL
The Power Module rectifiers derive power from a utility AC source and supply regulated DC power to
the inverter. The module’s inverter regenerates precise AC power to supply the connected equipment.
The battery charger is in the Power Module and maintains a float-charge on the batteries.
Backup Mode
When AC utility fails, the connected equipment is supplied power by the inverter, which obtains
energy from the Battery Modules. The output power equipment will not be interrupted during the
failure or restoration of the AC utility source.
Auto Restart Mode
After a power outage and complete battery discharge, and once AC utility is restored, the UPS will
automatically restart and resume supplying power to connected equipment. This feature is enabled at
the factory, but can be disabled by the user. The user can also program two auto restart delay settings:
1. Battery capacity level (%)
2. Countdown timer
Bypass Mode
The bypass provides an alternate path for power to the connected equipment and operates in the following manner:
•Automatic
In the event of an internal fault or should the inverter overload capacity be exceeded, the UPS
performs an automatic transfer of the connected equipment from the inverter to the bypass
source.
• Manual
Should the UPS need to be taken out of service for limited maintenance or repair, manual activation of the bypass will cause an immediate transfer of the equipment from the inverter to the
bypass source.
5
Introduction
1.3Major Components
The following is a general description of each component and its functions. Please review this section
carefully, as it will give you a better understanding as
to how the Nfinity operates.
1.3.1Unit Frame
The front of the Nfinity consists of a series of plastic
bezels. By grasping these bezels from the left and
right sides and pulling straight out, you can remove
the bezel to reveal the Battery / Power Module bays.
The bottom bezel covers the internal cooling fans and
the manual bypass switch.
The User Interface Module is located above the
Power / Battery Module bays for easy access. By moving the User Interface and setting it on top of the
frame, you will see the system control module bays.
NOTE
In the figure at right, the Power Module and
Battery Module are extended for illustration
purposes only. Extending more than one
module at a time could cause the unit to be
top-heavy and/or tip.
Nfinity’s frame
with bezels removed
1.3.2User Interface Module
The User Interface Module is the primary source of
communication between the UPS and the user. From
the interface, the user can:
• View the status of the UPS
• Custom configure the system
• Review the event log to assist with
troubleshooting
• Enable/disable the output power
• Silence the audible alarm
• Manually transfer the unit to bypass
For a more detailed explanation on how to operate the
User Interface Module, see 3.1 - Controls and Indi-cators.
1.3.3System Control Module
The System Control Module is the communications
backbone of the UPS. It gathers input from all modules and processes the data to control the operation of
the system — including monitoring the condition of
each module. An optional redundant System Control
Module can be installed to provide full system functionality (operation and communication).
User Interface Module
System Control Module
Fasteners
Under normal operation, the Status LED (green) will
blink and the Fault LED (yellow) will be off. For any
condition other than this, check 4.0 - Troubleshoot-ing.
6
Fault LED
Status LED
Lever
1.3.4Power Module
Each power module is an independent 4 kVA, 2.8kW unit, consisting of a power factor corrected rectifier, battery charger and inverter, with associated monitoring and control circuitry. The modules are
paralleled to provide greater capacity and/or redundancy. Modules may be added or replaced on-line
with no interruption or danger to the connected equipment.
1.3.5Battery Module
Each battery module contains 10 individual 12-volt, 9 amp hour, valve-regulated (VRLA) battery
blocks with associated monitoring and controls to isolate the Battery Module in the event of a battery
failure. The modules are paralleled to provide greater capacity, backup time and/or redundancy. Modules may be added or replaced on-line with no interruption or danger to the connected equipment,
provided that the UPS is not operating on battery.
Introduction
Power ModuleBattery Module
Shipping screws
Fastener
Green Status LED
Yellow Fault LED
Cooling Fan
Lever
FRONTFRONT
Under normal operation, the Green Status LED will blink continuously and the Yellow Fault LED
will be off. For any condition other than this, check 4.0 - Troubleshooting.
NOTE
Nfinity is shipped with each battery module secured to the frame by two shipping screws. These
screws should be removed prior to start-up.
7
2.0INSTALLATION
2.1Inspection
Upon receiving the UPS, examine the packaging for any signs of mishandling or damage. If any damage is noted, call your local dealer or Liebert representative and/or notify your carrier.
2.1.1Environment
NOTE
Operating in temperatures above 77°F (25°C) will reduce battery life. The UPS environment
must be free of conductive contaminants and excessive moisture (water and condensation),
flammable vapors, chemical fumes, corrosive gases and liquids.
2.1.2Required Setup Equipment
The tools below are required to properly set up your UPS:
• Pallet jack
• 1/2" (13mm) ratchet or wrench
• Torque wrench (in-lb)
• Flathead screwdriver
• #2 Phillips screwdriver
Installation
2.1.3Site Preparation
When deciding where to locate your UPS,
consider the weight and size of the unit. Make
sure that the structural integrity of the floor
can withstand the weight of a fully loaded unit.
Check to make sure that your UPS will be
located in a well-ventilated area with at least
12 inches (305mm) behind it. The UPS is
air-cooled utilizing internal fans. Air is drawn
into the front of the UPS and is exhausted
through ventilation grilles in the back. It should
also have at least 36 inches (915mm) in front in
order to change modules when necessary.
The unit frame is bolted to the shipping pallet to ensure safety. It is recommended that a pallet jack
be used to transport the unit to its operating location (prior to unbolting the unit).
12"
(305mm)
36"
(915 mm)
8
2.2Unloading
2.2.1Unloading the UPS
Installation
CAUTION
!
This UPS is very heavy (see weight in
Table 1). At least two people should
assist in unloading it from the pallet.
2. Remove the metal ramp from the bottom of
the UPS.
Pull ramp out from
under front of unit,
then turn ramp over
3. Fit the ramp flange in the slot in the rear
of the pallet (back of unit) as shown below.
1. Use a ratchet or wrench, 1/2" (13mm), to
remove the four mounting bolts from the
front and rear pallet brackets. Remove the
mounting brackets from the pallet and
UPS. Keep the brackets for future
transportation of the UPS or for additional
stability of the UPS once in place.
Fit ramp in
rear of pallet
4. Using two people, slowly move the UPS
down the ramp until the UPS is on a level
surface.
9
5. Once the UPS is in the desired location, adjust the leveling feet to secure its position.
2.2.2Stationary Mounting
Additional stability can be added by bolting the mounting brackets (used in shipping) to the floor, as
shown below left.
Installation
1/2" (13mm)
Shipping Brackets Used
for Stationary Mounting
28"
(711mm)
Optional Stationary
Mounting Dimensions
4.75"
(120mm)
4.75"
(120mm)
Center Line
5/16" (7.94mm)
diameter - in six
places
For greater stability, use a higher-grade bolt. Refer to the dimensions above right when drilling holes
for stationary mounting.
10
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.