Liebert MPX User Manual

Liebert® MPX™ Rack Power Distribution Unit
User Manual - Global Applications
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this manual to see if the issue can be resolved by following outlined procedures. For additional assistance, visit https://www.VertivCo.com/en-us/support/.
Important Safety Instructions 1
1 Introduction 3
1.1 MPX™ PRC: Power and Communication Bus 4
1.1.1 Mounting features 6
1.2 MPX™ PEM: Power Input 6
1.2.1 Connecting the MPX™ IPC for variable capacity models 8
1.3 MPX™ BRM: Power Output 9
1.4 RPC-1000™ and RPC2™ Communications Modules 11
1.4.1 RPC-1000 Communications Module 11
1.4.2 RPC2™ Communications Module 12
1.4.3 Accessing information on the RPC BDM 13
2 Installation and Assembly 15
2.1 Installing the MPX™PRC in a Rack 15
2.1.1 Preparing the Liebert MPX rack PDUfor mounting 15
2.1.2 Attaching brackets 16
2.2 System Assembly 18
2.2.1 Installing an MPX™ PEM onto the MPX™ PRC 18
2.2.2 Installing an MPX IPC to a variable capacity MPX PEM 22
2.2.3 Installing an MPX™BRMto an MPX™PRC 23
2.2.4 Installing a communications module 26
2.2.5 Installing optional temperature and humidity sensors 27
2.2.6 Installing an optional RPC™ BDM 27
3 System Functional Test 31
3.1 Assembly Checklist 31
3.2 Functionality Test 31
4 Operating and Configuring Rack PDUCards 33
4.1 Configuring Rack PDUCards 33
4.1.1 Configuring the RPC2 communications module 33
4.1.2 Configuring the RPC-1000™ communications web card 34
4.1.3 Indicators 35
4.2 Operating Rack PDUCards 36
4.2.1 Connecting to the rack PDUcards 36
4.3 Operation without Rack PDUCards 36
5 Maintenance 37
5.1 No User-Serviceable Parts 37
6 Troubleshooting 39
6.1 Liebert MPX Rack PDU 39
6.1.1 MPX™ PEM indicators and LEDs 39
6.1.2 MPX BRM indicators and LEDs 40
6.2 RPC-1000™ Communications Web Card Basic Troubleshooting 42
Vertiv | Liebert® MPX™ Rack Power DistributionUnit Installer/U ser Guide | i
6.2.1 Basic troubleshooting 42
6.2.2 Array configurations 43
6.2.3 Restarting or resetting 43
Appendices 45
Appendix A: Agency Approvals 45
Appendix B: Dimensional Drawings 47
Appendix C: Recycling, Compliance and Modifications Information 49
Vertiv | Liebert® MPX™ Rack Power DistributionUnit Installer/U ser Guide | ii
IMPORTANT SAFETY INSTRUCTIONS
The following components are covered in this safety section:
Liebert® MPX™ Power Rail Chassis (PRC)
Liebert® MPX™ Power Entry Module (PEM)
Liebert® MPX™ Branch Receptacle Module (BRM)
Liebert® MPX™ Input Power Cord (IPC)
Liebert® RPC-1000™ Communications Module
Liebert® RPC2™Communications Module
Saving These Instructions
WARNING! The MPX rack PDUcontains hazardous voltage that creates a risk of arc flash and electric shock resulting in equipment damage, injury or death. Follow the warnings and cautions in this document to avoid serious injury or death from electric shock.
Read this manual
This manual contains important safety instructions. Read all safety, installation and operating instructions before installing a Liebert® MPX™ rack PDU. Adhere to all cautions and warnings on the unit and in this manual. Upon installation, follow all operating and user instructions.
Installation location
Install the Liebert MPX rack PDUin a restricted-access location controlled and monitored by a responsible authority where access is only possible through the use of a tool, lock and key or other means of security.
Operate the Liebert MPX rack PDUonly in an indoor environment within an ambient temperature range of 32°F to 140°F (0°C to 60°C) with a relative humidity of 5% to 95%, non-condensing. Install it in a clean environment, free of conductive contaminants, moisture, flammable liquids, gases and corrosive substances.
Qualified personnel
Vertiv strongly recommends that the MPX PEM be installed only by an individual who has been properly trained and qualified to perform electrical work.
Only allow personnel who understand the precautions in this manual into the Liebert MPX rack PDU’s restricted access location.
Safety-critical applications
Do not use the Liebert MPX rack PDU for safety-critical situations. It is designed to deliver power to information technology and telecommunication equipment, and is not intended for use with life support or other critical devices. If you are uncertain about its application, consult your local dealer or your Vertiv representative.
Vertiv | Liebert® MPX™ Rack Power DistributionUnit Installer/U ser Guide | 1
MPXPEMinstallation
WARNING! The connectors on the bottom of the MPXPEMare energized with hazardous voltage when it is connected to power.
WARNING! Connect input power only after the MPX PEM is properly installed on the MPX PRC and the MPX IPC is properly connected to the MPX PEM.
WARNING! The MPXPEM is not hot swappable. Never remove an MPXPEM from the power distribution unit while input power is connected. Disconnect power before unlocking the connector screws that attach the MPXPEM to the MPXPRC.
WARNING! Connect only one MPX PEM to an MPX PRC. Failure to comply can result in serious injury or equipment damage.
Module cover removal and foreign objects
With exception of the communications module cover on the MPX PEM module, never open or remove the cover of any Liebert® MPX™ rack PDU.
Never insert a foreign object into an MPX module, particularly into the MPXPRC, with the exception of the RPC-1000™ and RPC2™ communications modules. Each module has a small hole between the display and sensor RJ45 connectors to reset the card.
MPXmodule service
Do not attempt to service the Liebert MPX rack PDUs. The modules do not contain user-serviceable parts. If you need support or have questions about your Liebert MPX rack PDU, contact Vertiv™ Technical Support or your local Vertiv representative.
Vertiv | Liebert® MPX™ Rack Power DistributionUnit Installer/U ser Guide | 2
1 INTRODUCTION
The Liebert® MPX™ is an adaptive rack power distribution unit (PDU) built with modular and scalable components that can be installed and reconfigured on-site to meet varying input and output power connectivity needs. For optimal flexibility, ensure that the modules match the power requirements of the application. Failure to do so could result in damage to the Liebert MPX rack PDUand connected components. The Liebert MPX adaptive rack PDU family consists of the following components:
MPX™ Power Rail Chassis (PRC) - distributes intermodule power and communications and serves as the mounting base for all Liebert MPX rack PDUcomponents.
MPX™ Power Entry Module (PEM) - delivers power to the Liebert MPX rack PDUand includes provisions for remote and local communication options. Detachable and non-detachable cord models are available.
MPX™ Input Power Cord (IPC) - a detachable input power cord required for some models of MPX PEM. A variety of single- and three-phase plug types are available.
MPX™ Branch Receptacle Module (BRM) - distributes overload-protected output power to user loads. The hot swappable design allows for field reconfiguration with a choice of receptacle type, quantities and monitoring/control performance.
RPC-1000™ and RPC2™ communications modules - optional network interface cards that provide network connectivity, monitoring and control capabilities to rack PDUs from a single network connection and serve as a rack accessory integration point. The communications modules can be installed in the MPXPEMcommunications card slot.
NOTE: The RPC-1000 and RPC2 communications modules cannot be used together in an array configuration.
NOTE: Effective December 1, 2016, Vertiv ended distribution of the RPC-1000 communications module. If you purchased an RPC-1000 communications module and the extended warranty on or before December 1, 2016, the last effective day of the extended warranty is December 1, 2021, or before, respective to your purchase date. After this date, Vertiv no longer supports the RPC-1000 communications module.
The Liebert MPXrack PDUalso comes with an optional display module:
RPC Basic Display Module (RPC BDM) - optional display for local monitoring of Liebert MPX rack PDUs. It is equipped with a supplied Ethernet cable. However, if the mounting location is not within reach of the supplied cable, a longer field-supplied cable may be used.
Vertiv | Liebert® MPX™ Rack Power DistributionUnit Installer/U ser Guide | 3
Figure 1.1 Liebert® MPX™ Rack PDUAssembly Diagram
Table 1.1 MPX Assemblies
ITEM DESCRIPTION
1 MPX PRC
2 MPX PEM
3 Rack PDU Card communications module (RPC2)
4 MPX BRM (threeshown connected)
1.1 MPX™ PRC: Power and Communication Bus
The MPX™ PRC is the fundamental building block of the Liebert MPX rack PDU. Power and Communications buses are integrated into the length of the MPX PRC. The MPX™ BRM and MPXPEM lock onto the MPX PRC to facilitate power input and output, monitoring and management, depending on the type of module.
The MPX PRC is available in different lengths to accommodate a single MPXP PEM and up to seven MPX BRMs. The MPX PRC has five power bus channels that allow you to connect the MPX PEM and MPX BRM modules to up to three phases of line, neutral and protective earth. The communication bus allows the Liebert RPC, MPX PEM and MPX BRM modules to communicate with each other.
Vertiv | Liebert® MPX™ Rack Power DistributionUnit Installer/U ser Guide | 4
The MPX PRC has a module connector T-slot for securely attaching the MPX PEM and MPX BRM modules via two latching screws. Spacer covers are available to reserve unused sections of the MPX PRC’s surface for future expansion.
WARNING! Connecting multiple MPX PEMs to one MPX PRC can cause equipment damage, injury or death. Connect only one MPX PEM to an MPX PRC. Connecting more than one MPX PEM could cause cross-conduction. Cross-conduction can cause upstream overcurrent protective devices (OCPD) to trip or the resulting short circuit current to exceed the OCPD Ampere Interrupting Capacity (A.I.C.) ratings.
Items 1 and 2 in the following figure show the top and side view of the MPX PRCto illustrate how to properly seat the component on the MPX rack PDU.
Figure 1.2 MPX PRC Components
Table 1.2 MPX PRC Components
ITEM DESCRIPTION
1 MPXPRCtop view
2 MPXPRCside view
3 MPXPRCend cap
4 Communication bus
5 Module connector slot
6 Power bus
7 Rail connector T-slots to accommodate spring nuts for mounting
Vertiv | Liebert® MPX™ Rack Power DistributionUnit Installer/User Guide | 5
1.1.1 Mounting features
The back of the MPX™ PRC features T-slots running the length of the unit. These can be used for mounting the assembled units in racks.
1.2 MPX™ PEM: Power Input
WARNING! The MPX rack PDUcontains hazardous voltage that creates a risk of arc flash and electric shock resulting in equipment damage, injury or death. The power conductors on the bottom of the MPX PEM are energized with hazardous voltage whenever the MPX PEM is connected to power.
WARNING! This unit must be properly and securely installed on the MPX PRC before power is applied. If the MPX PEM is not installed on the MPX PRC, live conductors will be exposed.
WARNING! Vertiv strongly recommends that the MPX PEM be installed only by an individual who has been properly trained and qualified to perform electrical work.
WARNING! Connecting two MPX PEMs to one MPX PRC can cause equipment damage, injury or death. Only connect one MPX PEM to an MPX PRC. Connecting more than one MPX PEM can cause cross-conduction. A cross-conduction willresult in an upstream OCPD trip, and may result in a short circuit current that exceeds the OCPD A.I.C. ratings.
The MPX PEM securely fastens to the MPX PRC to deliver polyphase power from the power supply cord to the power bus. You can install the Liebert® RPC2™ communications module in the MPX PEM to monitor and configure the communication bus.
The North American MPX PEM models are available with variable-capacity or fixed-capacity. The European models are available with fixed-capacity only. The power supply cords for both configurations are available in a variety of single- and three-phase NEMA, Schuko and IEC plug styles and ratings.
You must connect a detachable MPX™IPCto the power inlet on the variable-capacity models. (See
Connecting the MPX™ IPC for variable capacity models on page 8.) The power input ratings are
determined by the plug type. An MPX IPC can be exchanged for an MPX IPC with a different plug type and rating (single phase, three-phase or ampacity) to adapt it for a different power service configuration.
NOTE: For fixed capacity, the North American models support up to 60 A (48 A) per phase and the European models support up to 63 A per phase. For variable capacity, the North American models support up to 30 A (24 A) per phase and the European models support up to 32 A per phase.
All models, except the elementary model, provide power metering of the polyphase inputs, including individual line voltages and currents, total kilowatts (kW) and total kilowatt hours (kW-h). Additionally, individual line current alarm and operation status are supported. Elementary models of the MPX PEM are available only in Europe and are not equipped with power metering capability.
Other important features include:
Input phase LEDs to indicate the operational status of each phase of input power.
Vertiv | Liebert® MPX™ Rack Power DistributionUnit Installer/User Guide | 6
Audible alarms that indicate an overcurrent condition. You can test or silence the audible alarm by pressing the A la r m Silen ce/T e s t button. The audible alarm can be tested by momentarily pressing the button when an alarm condition is not pending or active.
The Silence/Test button is also used during troubleshooting to confirm the communications module is communicating with each MPX™BRM (see Restarting or resetting on page 43).
You can reestablish communication with all the modules and reset the MPX™PEM by pressing and holding the alarm silence button for more than 5 seconds when no active alarm condition is present. During an MPXPEM reset, the unit's input phase LEDs become dark. The MPXPEM reset function takes approximately 30 seconds. When complete, each MPXBRM displays a numeric value within its Branch Numeric Indicator display window. The MPXPEM reset function does not interrupt critical power to the MPXPEM or any of the MPXBRM modules.
Item 1 and 2 in the following figure shows the variable-capacityMPXPEMand the fixed-capacity MPXPEM. The variable-capacity MPXPEMhas quick-connect couplings for a power input cable, while the fixed-capacity model is equipped with a hard-wired power input cable.
Figure 1.3 MPX PEM Features
Table 1.3 MPX PEM Features
ITEM DESCRIPTION
1 Variable-capacity MPXPEM
2 Fixed-capacity MPXPEM
3 RPC2 communications module
4 Latch screws
Vertiv | Liebert® MPX™ Rack Power DistributionUnit Installer/User Guide | 7
ITEM DESCRIPTION
5 Input phase power indicators
6 Alarm Silence/Test button
7 Quick-connect couplings for power input cable (variable-capacity models)
8 Hard-wired power input cable (fixed-capacity models)
Network port used for:
9
10
11 Display port used to plug in the optional RPC BDM
12 Port for optional Liebert® SN sensor accessories
13 Command Line Interface (CLI) Serialconsole port
• Plugging in the Local Area Network (LAN) via an Ethernet cable (not included)
• Creating a rack PDU array by interconneting additional rack PDUs
Link port used for:
• Local configuration throughinterconnection to a computer
• Creating a rack PDU array by interconnecting additionalrack PDUs
1.2.1 Connecting the MPX™ IPC for variable capacity models
The MPX IPC is a detachable input power cord that permits changing the input power configuration of variable capacity models of the MPX™ PEM. These changes must be made during planned outages. For detailed installation steps, see the Liebert® MPX™ PEM Quick Installation Guide (SL-20821 Rev6/590­1624-501A).
The MPX IPC is offered only for North American (UL-listed) models. A variety of single- and three-phase NEMA and IEC plug types are also available. The MPX IPC is not compatible with the fixed-capacity MPXPEM.
WARNING! Do not connect the MPX IPC to input power until the MPX PEM is attached to the MPX PRC and the MPX IPC is attached to the MPX PEM. If the MPX PEM is not connected to the MPX PRC, conductors with live hazardous voltage are exposed when power is connected.
Exposed conductors with hazardous voltage can create a risk of arc flash and electric shock which can result in equipment damage, injury or death.
Vertiv | Liebert® MPX™ Rack Power DistributionUnit Installer/User Guide | 8
Figure 1.4 MPX IPC Clamp
Table 1.4 MPX IPC Clamp
ITEM DESCRIPTION
1 MPXIPC retention clamp to prevent accidental disconnection (included with MPXIPC assembly)
2 Quick connect power coupling
3 Integrated snap locks
1.3 MPX™ BRM: Power Output
The MPX BRM provides output power distribution to user load equipment. MPX BRMs are available with a variety of combinations of output receptacles such as NEMA, IEC, Schuko and other regional types that are overcurrent-protected by 100% rated hydraulic-magnetic circuit breakers.
MPX BRMs are hot-swappable to allow installation without powering down the Liebert MPX rack PDU. All MPX BRMs include an alphanumeric LED that uniquely identifies the individual module. Each MPXBRM's unique identification is assigned by the RPC2 communications module.
North American and European MPXBRMunits are available in the following models:
Elementary - provides power distribution only; power metering and alarming are not supported.
Branch Monitoring - provides power distribution and branch power metering, including voltage, current, Watt and VA power, energy and power factor.
Receptacle Management - provides the same features as the branch monitoring models, plus power metering, including crest factor, on/off control, current alarming and operational status of individual receptacles. The receptacles can be turned on or off remotely and programmed for automatic power-on sequencing.
MPXBRMfeatures include:
An alphanumeric LED to identify the module.
The alphanumeric LED display on the branch monitoring and receptacle management models shows operational status of the branch current condition.
Vertiv | Liebert® MPX™ Rack Power DistributionUnit Installer/User Guide | 9
A magnetic hydraulic circuit breaker. If necessary, the circuit breaker can be manually opened by inserting a flat-blade screwdriver into the integrated reset slot. Open circuit breaker detection causes the alphanumeric LED to flash on the Branch Monitoring and Receptacle Management models.
Color-coded labeling to clearly identify the output-phasing configuration (L1-L2, L2-L3, L3-L1, L1-N, L2-N or L3-N) of the MPX™BRM receptacles. Voltage phasing is determined by the power blade configuration on the bottom of each MPX BRM. The voltage phasing, for example, "L12", flashes three times on the alphanumeric LED display when the module is first attached.
IEC C13 receptacle types support attachment of optional retaining clips to provide strain relief for the load's power supply cord.
The Branch Monitoring models provide current alarming and operational status of the branch. The unit displays an “o” for an overcurrent condition and a “u” for an undercurrent condition. The Receptacle Management models include additional LEDs for each receptacle to alert you of the operational status of the receptacle (on or off).
Figure 1.5 MPX BRM
Table 1.5 MPX BRM
ITEM DESCRIPTION
1 Latch screws
2 LEDbranch numeric indicator
3 Color-codedreceptacle phase label
4 Receptacle on/off indicators (Receptacle Management units only)
Vertiv | Liebert® MPX™ Rack Power DistributionUnit Installer/User Guide | 10
ITEM DESCRIPTION
5 Receptacles
6 Branch-rated circuit breaker (100% rated)
1.4 RPC-1000™ and RPC2™ Communications Modules
NOTE: Effective December 1, 2016, Vertiv ended distribution of the RPC-1000 communications module. If you purchased an RPC-1000 communications module and the extended warranty on or before December 1, 2016, the last effective day of the extended warranty is December 1, 2021, or before, respective to your purchase date. After this date, Vertiv no longer supports the RPC-1000 communications module.
The Liebert MPX rack PDU can be centrally managed, locally and remotely, via either the RPC-1000 or RPC2 communications modules. Refer to the following documents for more information:
Liebert® RPC™ Web Card User Manual (SL-20825)
Liebert® RPC2™ Communications Module Installer/User Guide (590-1380-501A)
You can control the Liebert® MPX™rack PDUand attached devices through the communication module's web interface. For systems connected to an Ethernet network, the web interface uses Simple Network Management Protocol (SNMP). The communications module also serves as the connection point for multiple support capabilities and devices including:
RPC Basic Display Module (RPC BDM)
Various optional environmental sensors
“Sibling” connections to other Liebert MPX or Liebert MPH rack PDUsystems
For North American MPXmodels, the RPC-1000 or RPC2 communications modules are field-installed in the MPX PEM slot. European MPXmodels are equipped with factory-installed communications modules on monitored MPX PEMs.
1.4.1 RPC-1000 Communications Module
The RPC-1000 communications module is equipped with two RJ45 jacks for connecting to external devices and requires no custom cables. See the following figure and table for port descriptions.
Vertiv | Liebert® MPX™ Rack Power DistributionUnit Installer/User Guide | 11
Figure 1.6 RPC-1000™ Communications Module
Table 1.6 RPC-1000 Communications Web Card Port Descriptions
ITEM PORT DESCRIPTION
Used for:
1 Network
2 Display Used to connect the optional RPC BDM.
3 Sensor Used to connect optional Liebert® SN sensor accessories.
4 Link
5 Not applicable RPC-1000 Communications web card
• 10/100 Mbps LAN connection via an Ethernet cable (not included).
• Creating an optional rack PDUarray by interconnecting additional Vertiv rack PDUs.
Used for:
• Local configuration throughinterconnection to a computer.
• Creating an optional rack PDUarray by interconnecting additional Vertiv rack PDUs.
1.4.2 RPC2™ Communications Module
The RPC2 communications module has three RJ45 jacks for connecting to external devices and requires no custom cables. See the following table for port descriptions.
Vertiv | Liebert® MPX™ Rack Power DistributionUnit Installer/User Guide | 12
Figure 1.7 RPC2™ Communications Module
Table 1.7 RPC2 Communications Module Port Descriptions
ITEM PORT DESCRIPTION
1 Serial Used for the RS232 serialconsole using the CLI
2 USBMicro-AB Used for the USB memory stick
3 Sensor Used to connect optional Liebert® SN sensor accessories
4 Display Used to connect the RPC BDM
Used for:
5 Link
6 Network
7 Reset button access hole Used to reboot or reset the module to its factory default settings
• Local configuration throughinterconnection to a computer
• Creating an optional rack PDUarray by interconnecting additional Vertiv rack PDUs
Used for:
• 10/100/1000 Mbps LAN via an Ethernet cable (not included)
• Creating an optional rack PDUarray by interconnecting additional Vertiv rack PDUs
1.4.3 Accessing information on the RPC BDM
The RPC BDM is an optional local display that shows monitored data from all connected Liebert® MPX™ and Liebert MPH rack PDUsystems. You can access display information from a navigation switch on the RPC BDM. The switch is located beneath the Vertiv logo on the RPCBDM. It is connected by a cable to the communications module which allows you to locate the display for a local reading.
The RPCBDMcomes with a connector cable and mounting provisions. You can connect up to four rack PDUs in a rack PDUarray to a single display.
For detailed BDM operation instructions, see the Liebert® RPC2™ Communications Module Installer/User Guide.
Vertiv | Liebert® MPX™ Rack Power DistributionUnit Installer/User Guide | 13
Loading...
+ 38 hidden pages