Liebert micro smart switch User Manual

DISCONTINUED
PRODUCT
DUAL INPUT POWER DISTRIBUTION
MICRO SMAR TSWITCH
USER MANUAL
200 VAC to 240 VAC
50/60 Hz
24 Amps
The Liebert Micro SmartSwitch (MSS) is a single Phase Dual Input rack mount­able Power Distribution Unit (PDU) with a built in Automatic Transfer Switch. When Input A falls below 168 VAC and Input B is valid, the output is automati­cally transferred to Input B. The output is transferred back to Input A when Input A is valid and rises above 178 VAC. This high speed transfer rate ensures that the transfer is transparent to the sensitive equipment.
The two sources are not required to be in phase. This is an effective solution that
uilds in redundancy and increases the AC power availability of connected
b equipment. If the dual input power is fed through two independent AC sources, then the system availability is increased and the dual input advantages are fully used.
The Micro SmartSwitch provides 12 receptacles power and may be rack mounted. There are four groups of three IEC-320 (10A) receptacles, where each group is backed up by a 10A magnetic circuit breaker. The MSS has two attached line cords that are terminated with NEMA L6-30 plugs with a 20A fuse for each. The total load for the MSS cannot exceed 24A of AC load at 200-240 VAC. Also the load for each of the four groups cannot exceed 10A or the internal breaker may trip or the fuse will blow. The load must be balanced among the four segments such that the total current draw per section does not exceed 10A and a total of 24A for all the four segments of the MSS. This product provides line-to-line surge protection of 500 Joules.
that distribute redundant AC
Glossary of Symbols
Risk of Electrical Shock
Indicates Caution - followed by important instructions
!
Bonded to Ground
AC Voltage
On
I
Off
O
No user servicable parts inside
DISCONTINUED
PRO DUC T
About This Device
This guide serves as an outline to assist Qualified personnel with the installation of the Liebert Micro SmartSwitch. The input voltage for this Micro SmartSwitch unit is 200VAC to 240VAC.
This Micro SmartSwitch includes the following features:
Mounts in 1U of rack space
Provides 12 receptacles on 4 circuit breakers
Protects against electrical line surges and spikes
This Micro SmartSwitch is UL and c-UL listed as Information Technology
uipment.
Eq
WARNING: There is a risk of personal injury from electrical shock
and hazardous energy levels. The installation of options and routine
!
maintenance and service of the product must be performed by individuals who are knowledgeable about the procedures, precautions, and hazards associated with AC power products (trained service technician).
To reduce the risk of electrical shock and or servicing the Micro SmartSwitch:
The Micro SmartSwitch must be disconnected from the product and
unplugged from the AC electrical outlet before servicing or repairing prod­uct.
Do not overload the output of the Micro SmartSwitch. The total connected
should not exceed rated input power.
load
Do not exceed the leakage current limit for the Micro SmartSwitch in your system. See the “Earth Leakage Current” section later in this document for limits.
Earth Leakage Current
To reduce the risk of electrical shock du grounded (earth) connection is essential before connecting Micro SmartSwitch to AC power. Observe the following limits when connecting the product to AC power distribution devices. For products that have attached AC power co ing power, the total combined leakage current should not exceed 5 percent of the rated input current for the device. For products that have detachable AC power current should not exceed 3.5mA.
Voltage Selection
On connected equipment that have voltage select switches, make sure that the switch is set for the type of voltage you use (208/240 VAC).
/or equipment damage when installing
e to high leakage current, a reliable
rds directly connected to the build-
cords, the total combined leakage
DISCONTINUED
PRO DUC T
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS.
This manual contains important instructions that should be closely followed dur­ing installation and maintenance of this product.
This product is designed for Commercial/Industrial use only. It is not intended for use with life support and other U. S. F imum load must not exceed that shown on the rating label. See Limited Warranty.
DA designated “critical” devices. Max-
WARNING: Lethal voltages may be present within this unit even when it is
apparently not operating. Observe all cautions and warnings in this manual. Failure to do so MAY result in serious injury.
This equipment or Micro SmartSwitch is designed for use on a properly grounded (earthed), 208/240 VAC, 50Hz or 60Hz supply.
ELECTROMAGNETIC COMPATIBILITY- The Micro SmartSwitch complies
the limits for a CLASS B digital device, pursuant to part 15 of FCC rules.
with These limits provide reasonable protection against harmful interference. If this device is not installed and used in accordance with the instruction manual, it may cause harmful interference to radio communications. Not operating this device in accordance with these instructions may cause harmful interference, which the user must correct at their own expense.
Operate the Micro SmartSwitch in an i temperature range of 0°C to 50°C (32°F to +122°F). Install it in a clean environ­ment, free from conductive contaminates, moisture, flammable liquids, gasses, or corrosive substances.
Turn the Micro SmartSwitch off and isolate it from other equipment before
g. Use a soft cloth, never liquid or aerosol cleaners.
cleanin
Keep the vents free from dust accumulat
Never block or insert any object into the ventilation holes or other openings.
ndoor environment only in an ambient
ion that could restrict airflow.
DISCONTINUED
PRO DUC T
Installation
Place rear rail [R] over the studs in the front rail [F]. Tighten nuts finger tight. The mounting tab [T] will be facing out, so the holes align with the rack sides. Adjust length of rail assembly to fit inside rack. Tighten either the wing nuts or hex nuts.
Insert cage nut (one on each side) in rack. Set hooks at rear of rail over holes in
ack. Use screw [2] (one on each side) to attach rails to rear of rack through cage
r nut. Use screw [2] (two on each side) to attach rails to front of rack.
R
F
T
OUT SI DE
2
FRONT
Use screws [1] (two on each side) to attach brackets to side of unit. Slide unit into rails and secure by using screws [2] (one on each side) to attach the unit.
1
2
1
DISCONTINUED
PRO DUC T
Ground Bonding Screw
A ground bond­ing screw is pro­vided on the rear of the unit. This feature is pro­vided as an attachment point for conductors the rack may contain for the purpose of func­tional grounding or bonding of ungrounded metal parts. Ground cables are not included. Note: T proper grounding.
Connecting Devices
Make sure that the devices nected do not exceed the unit capabilities. This Dual Input Micro Switch features 3 output recepta­cles per circuit breaker, for a total of 12 receptacles. This model is rated at 10A per breaker. Each block of 3
eceptacles has a maximum output rating of 10A. If the total connected load
r exceeds 10A, the circuit breaker will trip and interrupt power to all loads attached to that block of receptacles. The maximum output of this Micro SmartSwitch is 24A. If the total load con­nected to all load segments exceed 24A, the circuit breaker at the wall could trip and interrupt power to all loads.
he Ground Bonding wire must be a minimum of 10 AWG to maintain
con-
Smart-
DISCONTINUED
PRO DUC T
About the Circuit Breakers
Input power can be verified by the illumination of the two LEDs on the front of the unit, marked ~A and ~B. Output power can be verified by the illumination of the circuit breaker, when in the On position If connected device is not powered, verify the respective circuit breaker is On and illuminated. If power is still not restored, see “Contacts” section later in this document.
DISCONTINUED
PRO DUC T
Configurations
The Micro SmartSwitch can be configured to fit several power distribution requirements.
Configuration 1
This application shows use of the Micro SmartSwitch in conjunction with single-
rd devices .
line co Note: Each segment can accommodate a maximum current draw of 10A, so the individual load connected to it must not exceed 10A or the circuit breaker will trip.
C Input A
~A: A
L6-30P
~B: AC Input B
1,2,3,4: Load segments on the
Micro SmartSwitch
~ A
Dual Input
~ B
1
P
2
D
3
U
4
L6-30P
Load: Any s
other equipment connected to the Micro SmartSwitch
Configuration 2
This configuration shows the use of the Micro SmartSwitch with 3-line cord
evices. The figure below shows how three Micro SmartSwitchs can be used to
d connect with up to four 3-line cord devices.
Note:
individual load connected to it must not exceed 10A or the circuit breaker will trip.
erver, storage, or
200-240 VAC
Each segment can accommodate a maximum current draw of 10A, so the
Load
Load
Load
Load
C Input A
~A: A
~B: AC Input B
Load: Any server, storage, or
other equipment connected to the Micro SmartSwitch
L6-30P
~ A
Dual Input
~ B
L6-30P
1
P
2
D
3
U
4
200-240 VAC
Load
Load
Load
Load
DISCONTINUED
PRO DUC T
Configuration 3
This configuration shows the use of a Micro SmartSwitch with 2-line cord devices. In this configuration, a server is connected to each of the four segments of the Micro SmartSwitch.
Each segment can
Note:
accommodate a maximum cur­rent draw of 10A, so the individ­ual load connected to it must not exceed 10A or the circuit breaker will trip.
C Input A
~A: A
L6-30P
~ A
Dual Input
~ B
L6-30P
1
P
2
D
3
U
4
Load
Load
Load
Load
200-240 VAC
~B: AC Input B
,3,4: Load segments on the
1,2
Micro SmartSwitch
Load: An other equipment connected to the Micro SmartSwitch
y server, storage, or
L6-30P
~ A
Dual Input
~ B
L6-30P
1
P
2
D
3
U
4
Load
Load
200-240 VAC
Configuration 4
If your facility does not have a centralized Uninterruptible Power System, then
e following configuration will provide maximum redundancy in a rack environ-
th ment. The diagram below shows how to use three Micro SmartSwitchs, each con­nected to a UPS and a server.
Each segment can accommodate a maximum current draw of 10A, so the
Note:
individual load connected to it must not exceed 10A or the circuit breaker will trip.
DUAL INPUT
C Input A
~A: A
~B: AC Input B
Load: Any server, storage, or
other equipment connected to the Micro SmartSwitch
~ A ~ B
~ A ~ B
~ A ~ B
L6-30P
P D
UPS
Load
U
P D
UPS
Load U
P D
UPS
Load U
200-240 VAC
DISCONTINUED
PRO DUC T
Liebert Micro SmartSwitch Specifications
Liebert Model Name Micro SmartSwitch
Part Number MSS30A-240
Unit Dimensions (H x W x D) in 1.72 x 17.00 x 15.25 in
(mm) (43.7mm x 432mm x 387mm)
Unit Weight: lbs.(kg) 20.0 lbs.(9.7kg)
Shipping Weight: lbs.(kg) 32.0 lbs.(14.55kg)
LED Indictors Input A (Primary) / Input B (Secondary)
Nominal Input Voltage Range 200 – 240VAC
On-Line Voltage Range 180 – 262VAC
Input Plug (2) Attached x L6-30 Plugs
Input Frequency 50/60Hz
Input Surge Rating 500J
Output Connectors (12) x IEC-320-C13
Output Circuit Breaker Protection Rating (4) x 10A
Output Power (VA) Rating 4320
Maximum Output Current 24A
Transfer Time <18ms
Environmental
Operating Temperature 0°C to 50°C (32°F to 122°F)
Storage Temperature -30°C to 60°C (-22°F to 140°F)
Relative Humidity 10 % to 80 %, non-condensing
Operating Altitude 0 to 10,000 feet above sea level
Safety and Agency
Safety Markings UL, c-UL
Safety Certifications UL1950
EMC Markings FCC
Emissions FCC Class A,
Immunity ANSI C62.41 Cat B (formerly IEEE 587)
DISCONTINUED
PRO DUC T
DISCONTINUED
PRO DUC T
Micro Smart Switch
DUAL INPUT POWER DISTRIBUTION
USER MANUAL
The Company Behind the Products
With over a mil lion installations around t he globe, Liebert is the wor ld leader in computer protect ion systems. Since its founding in 1965, Liebert has developed a co mplete range of support and protection systems for sensitive electronics:
• Environmental system s—close-control air
conditioning from 1 to 60 tons
• Power conditioning and UPS with power
ranges from 30 0 VA to more than 1000 kVA
• Integrated s ystems that provide both
environmen tal and power protection in a single, flexible package
• Monitoring and control—from systems of any
size or location, on-site or remote
• Service and support through more than 100
service cente rs around the world and a 24/7 Customer Res ponse Center
While every pr ecaution has been taken to en sure the accuracy an d completeness of this lit erature, Liebert Corpora tion assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
© 2001 Liebert Co rporation All rights reserved throughout the world. Specification s subject to change without no tice.
® Liebert and the Liebert logo are registered trademarks of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners.
SL-20350 (10/01)
Technical Support
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
1-800-222-5877
Outside the United States
24 hours a day, 7 days a week
35028 Piove Di Sacco (PD)
+614-888-0246
1-800-222-5877
3-Phase UPS
1-800-543-2778
Environmental Control
1-800-543-2778
Via Leonardo Da Vin ci 8
Zona Industrial e Tognana
+39 049 9719 111
FAX: +39 049 5841 257
23F, Allie d Kajima Bldg.
138 Glouces ter Road
+852 2 572 2201
FAX: +852 2 831 0114
www.liebert.com
Italy
Asia
Wanchai
Hong Kong
Web Si te
PRO DUC T
DISCONTINUED
Loading...