Liebert Magnetic Synthesizer Datawave User Manual

Page 1
AC
Power Systems
For Business-Critical Continuity
Liebert Datawave®Magnetic Synthesizer
High Level Power Conditioning That Delivers The Highest Quality Power
Page 2
Weekly malfunctioning of a critical
system due to power problems
would be unthinkable. But experi-
ence shows that this can be a reality
— an average site will experience
approximately 60 disruptive power
disturbances each year. The Liebert
Datawave magnetic synthesizer
provides the answer by meeting
the power quality needs of today’s
sensitive electronic systems.
Available in capacities from 15
to 200 kVA, it conditions and
distributes power, while offering
convenient system control and
monitoring — all in a single self-
contained unit. Designed for
lity as your needs change,
i
b
a
d
an
xp
e
the system is parallelable, allowing
you to add capacity or redundancy.
Reliability
Dependable components — Power conditioning is accomplished using only magnetic components and capacitors — there are no moving parts to wear out or power semiconductors to fail. This rugged technology and simple design results in high reliability, minimal maintenance and many years of dependable operation.
Overload and unbalanced loads — The Liebert Datawave is designed to support load imbalance, commonly caused by adding equipment to the load or by turning loads on and off. It also handles the high inrush and start-up currents demanded by electronic systems.
Deep sag protection — The unit’s broad input voltage regulation range protects computer systems and other sensitive electronics from deep sags, which other technologies would consider outages.
Transient voltage protection — The Liebert Datawave’s output voltage waveform is independent of input waveform, assuring protection from high energy spikes and ringing transients that can disrupt or damage your electronic systems.
Single-phase protection — Shorting, opening or unbalance of an input phase typically causes motors and transformers to overheat or go off-line. The Liebert Datawave’s unique design allows it to maintain 3-phase output voltage, even with the loss of one input phase, up to 60% load.
Harmonics isolation — Today’s electronic systems are non-linear loads, which can cause reflected distortion — a problem for conventional power systems. The Liebert Datawave’s controlled input current distortion prevents the load’s current distortion
wer system, while its controlled output voltage distortion
g the po
tin
ec
ff
om a
fr prevents the power system voltage distortion from affecting the load. High neutral current can also be handled without the need for oversizing.
Flexibility
Broad size range — The Liebert Datawave is available in several kVA ratings and input voltage options, allowing flexible system design.
Model CA Liebert Datawave — The basic Datawave power conditioning unit, the
odel is equipped with a main output breaker. It can be used with an existing
A m
C
on panel board. It is capable of remote distribution, multiple distribution
ti
u
ib
tr
is
d and paralleling.
Model SC Liebert Datawave — A complete system in a single package, with full conditioning, monitoring and distribution capabilities. The SC model has integral output circuit distribution with flexible output cables.
Secure distribution and circuit identification for SC units — Each breaker has an adjacent identification tag for rapid circuit ID. Each output cable is labeled at each e
n
d with circuit number, length, type of receptacle and circuit identification.
Low Total Cost of Ownership
ient
c
ffi
y e
rg
e
En
while high operating efficiency reduces utility costs and heat output.
— N
y unit
l
ar
e
put power factor means lower input current,
y in
2
Page 3
Integral Power
Output Waveform
(Note: Resultant Synthesized Waveform Has Less Than 4% THD)
Synthesized Waveform "Building Blocks"
Time
Voltage
Monitoring Panel
Provides comprehensive metering and
arms for system power parameters.
al
onitoring features include:
M
True RMS measurements.
Autoscan of all parameters.
Adjustable alarm thresholds.
Programmable custom alarms.
Battery-backed alarm memory.
Summary alarm contact.
Isolated RS-232 ASCII port.
Remote Monitoring Interface
The Liebert Datawave can be interfaced
ebert SiteScan centralized moni-
with Li
oring systems, allowing single point
t supervision and control of power conditions as well as alarm management. SiteScan systems provide historical data on power conditions for future require­ment planning and troubleshooting.
Service Business of Emerson Network Power
One call to 1-800-LIEBERT puts you in touch with a qualified service represen­tative 24-hours-a-day. Service engineers are factory trained and equipped with the specialized tools and knowledge to respond to any service problem quickly.
Simplified Diagram, Magnetic Power Synthesizer
aveform
W
sis
the
Syn
And Inductive
gy Storage
r
Ene
3 Phase
In
put
Energy Transfer
And Line Isolation
3 Phase O
utput
Capacitive
rgy Storage
Ene
Synthesized
Waveform,
“Building Blocks”
3
Page 4
Emerson Network Power.com
Emerson Network Power.
The global leader in enabling
Business-Critical Continuity
.
AC Power Systems
Connectivity DC Power Systems Embedded Computing Embedded Power Integrated Cabinet Solutions Outside Plant Power Switching & Control Precision Cooling Services Site Monitoring Surge Protection
Liebert Corporation
1050 Dearborn Drive P.O. Box 29186 Columbus, Ohio 43229 800 877 9222 Phone (U.S. & Canada Onl
y)
614 888 0246
Phone (Outside U.S.)
614 841 6022
FAX
Via Leonardo Da Vinci 8 Zona Industriale Tognana
35028
Piove Di Sacco (PD)
Ital
y
39 049 971
9 111 Phone
39 049 584
1 257 FAX
Eme
rson Network Power Asia Pacific 7/F., Dah Sing Financial Centre 108 G
loucester Rd, Wanchai
Hong
Kong 852 25722201 Phone 852 2802
9250 FAX
liebert.com
24 x 7 Tech Support
800 222 5877 Phone
614 841 6755 (outside U.S.)
Liebert Datawave®Magnetic Synthesizer
Specifications
60Hz
Output Input Breaker Board (in) Weight @ Full Load
kVA kW Voltage1(Amps) Poles2(Wx D xH) (lbs) PF=1
15 15 208 60 42 36x 34x64 1,200 6,350
20 20 208 80 42 36x 34x64 1,500 8,450
30 30 208 125 42 36 x34x 64 1,600 10,125
50
75 75 208 300 84 44x32 x68 2,750 19,270
100 100 208 400 120 66x 36x76 3,900 25,700
125 125 208 500 120 66 x36x76 4,300 32,100
150 150 208 600 120 104
200 200 208 800 120 104
50Hz
Output Input Breaker Board (cm) Weight @ Full Load
kVA kW Voltage4(Amps) Poles2(Wx D xH) (kg) PF=1
15 15 380 40 42 92x 87x 163 590 1.85
20 20 380 50 42 92x 87x 163 730 2.47
30 30 380 70 42 92x 87x 163 775 2.97
50 50 380 110 84 112x 81x173 1,200 3.76
75 75 380 175 84 112x 81x173 1,375 5.65
100 100 380 225 120 168x92x 193 2,000 7.53
125
150 150 380 350 120 264
200 200 380 450 120 264
1
Other input voltages available. Standard output voltages are 208/120, 480/277, and 600/346 volts. For voltages not show, consult factory.
2
Panelboards furnished on "SC" models. Main output breakers furnished on "CA" models.
3
ase in shipping and handling, unit shipped in two modules of 52 inches (132 cm) each.
or e
F
4
Other input voltages available. Standard output voltages are 208/120, 380/220, 400/230 and 415/240 volts. For voltages not shown, consult factory.
Three Input Heat Output Phase Circuit Panel Dimensions (BTU/Hr)
480 30 600 25
480 40 600 30
480 50 600 50
50 208 200 84 44x 32x68 2,400 12,850
480 90 600 70
480
125
600 110
480
175
600 150
480 225 600 175
480 250 600 225
480 350 600 300
Three Input Heat Output
Phase Circuit Panel Dimensions (kW/Hr)
400 40 415 30
400 50 415 40
70 60
175
225
380 300 120 168 x92x193 2,230 9.41
450
125
400 415
400 110 415 100
400 415 150
400 415 200
400 250 415 250
400 350 415 300
400 415 400
3
x36 x76 5,800 38,500
3
x36x76 6,500 51,400
3
x92x193 2,950 11.29
3
x92x 193 3,340 15.05
General Specifications
oltage Regulation:For input voltages of ±40%,
V
output voltage is within +5% for any load condition up to full load.
Overload Capacity: Supports 200% load until circuit breaker trips, 5 to 20 minutes typical.
Output Voltage Distortion: Less than 4% total, not additive to input distortion.
oise Suppression:
N
120dB nor
Effi
ciency:
mal mode.
or 15-20 kVA, 91% for 30 kVA,
89% f
and 93% for 50-200 kVA at full load.
put Power Factor:
In
ardless of load power factor.
reg
Unbalanced Loads: Output voltage is within +5%, -2% with 100% load current unbalance.
Single Phase Protection: For loss of one input phase, output voltages remain within 6% and –4% up to 60%load.
Audible Noise: 55-63 dBa at 5 feet.
Monitored Parameters: Input and Output
Voltages; Output, Neutral and Ground Currents; Output Voltage THD; Output Current THD; K-Factor, Crest Factor; Output Power kVA, kW­Hours; Power Factor; Percent Load; Frequency.
Alarm Conditions: Output Over- and Under­voltages; Output Voltage THD; Output Overload; Neutral and Ground Overcurrents;
ransformer Overtemperature; Frequency
T Deviation; Phase Sequence Error; Phase Loss; Five Customer Specified Alarm Conditions.
ommon mode and
120dB c
>0.96 h
alf to full load,
aution has been taken to ensure accuracy and
ec
y pr
r
e
v
e e
l
Whi completeness in this literature, Liebert Corporation assumes no
lity, and disclaims all liability for damages resulting
i
ponsib
s
e
r
s
om u
r
f
© 2006 Liebert Corporation. All rights reserved throughout
orld. Specifications subject to change without notice.
the w
ame
All n of their respective owners.
ebert and the Liebert logo are registered trademarks
® Li of the Liebert Corporation.
SL-20199 (R07/06) Printed in USA
mation or for any errors or omissions.
or
f
f this in
e o
s referred to are trademarks or registered trademarks
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo
demarks and service marks of Emerson
a
e tr
ar Electric Co. ©2006 Emerson Electric Co.
Loading...