Liebert LM, LM1, LM2 Installation, Operation And Maintenance Manual

Page 1
Surge
®
Suppression
Systems
LIEBERT LM SERIES SURGE PROTECTIVE DEVICE
TABLE OF CONTENTS
UNPACKING AND INSTALLATION....................................................................................... 2
Unpacking and Preliminary Inspection............................................................................. 2
Handling Considerations .................................................................................................... 2
Storage.................................................................................................................................. 2
Location Considerations..................................................................................................... 2
Door Closing Adjustments.................................................................................................. 2
ELECTRICAL CONNECTIONS .............................................................................................. 5
Voltage Rating & Source Configurations......................................................................... 5
Parallel Connection............................................................................................................. 5
System Grounding & Bonding........................................................................................... 9
OPERATION.............................................................................................................................. 10
TROUBLESHOOTING / REPAIR / MAINTENANCE........................................................... 12
Red LED on Door Illuminated & Green LED on Door Extinguished........................... 12
Display Blank – No Red or Green LEDs Illuminated on Door...................................... 12
Replacing Power Supply Board (Units with Counter or Audible Alarm Options)...... 13
Preventative Maintenance (Inspection and Cleaning)................................................... 13
LIMITED WARRANTY.............................................................................................................. 14
DECLARATION OF CONFORMITY....................................................................................... 16
FIGURE
Figure 1. Cabinet Data, Form C Contact and Wiring.................................................... 3
Figure 2. Voltage Ratings and Power Source Configurations..................................... 6
Figure 3. Typical Parallel Connections (without External Disconnect Switch) ......... 8
Figure 4. Typical Parallel Connections (with External Disconnect Switch)............... 8
Figure 5. Remote Monitor Panel...................................................................................... 11
Installation, Operation - 1 - LM Series and Maintenance Manual Rev 0, 5/99
Page 2
INSTALLATION, O
PERATION AND
MAINTENANCE MANUAL
TRANSIENT VOLTAGE SURGE SUPPRESSION
LM Series
Liebert
Page 3
TRANSIENT VOLTAGE SURGE SUPPRESSION
A World Leader in Computer Support Systems
Environment Control Power Protection Site Monitoring / Control
Liebert Cor poration designs, manufactures and markets complete systems for improve­ment of computer uptime and perfor­mance. The result is improved business operations, increased productivity and higher return on the computer investment. Lieber t Systems provide dependable environ­mental control and electrical power pro­tection, combined with centralized monitoring and control. This approach represents a single-source integrated computer support network. Based on over two decades of experience and over 80,000 installations world­wide, Liebert is committed to offering the highest quality products and services for applications requiring computer support.
Control Concepts Corporation
A Subsidiary of the Liebert Corporation 328 W ater Street, P.O . Box 1380 Binghamton, NY 13902 USA Tel: 607/724-2484
800/288-6169
Fax: 607-722-8713
While every precaution has been taken to ensure accuracy and completeness in this manual. Liebert Corporation assumes no responsibility, and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
©1999 Liebert Corporation All rights reserved throughout the world. Specifications subject to change without notice.
®Liebert and the Liebert logo are registered trademarks of Liebert Corporation.
Printed in U.S.A SL-22030 (5/99)
Page 4
Surge
®
Suppression
Systems
INSTALLATION INSTRUCTIONS FOR THE
LIEBERT LM SERIES SURGE PROTECTIVE DEVICE
The Liebert LM Series Surge Protective Device is a high quality, high energy surge current diversion system designed to protect sensitive equipment from damaging transient voltage surges. Proper installation is required for maximum system performance.
UNPACKING AND INSTALLATION
Unpacking and Preliminary Inspection
1. Inspect the shipping crate(s) for damage or signs of
mishandling before unpacking the unit.
2. Remove any securing bands and cardboard packing
and inspect the unit for any obvious shipping damages.
3. If any damage as a result of shipping is observed,
immediately file a claim with the shipping agency and forward a copy to your local Liebert Sales Representative.
Handling Considerations
Larger units are bolted to a shipping pallet to facilitate handling by forklift or pallet jack. Check the size and weight. Refer to the cabinet data furnished with the unit. Typical size and weights are referred to in Figure 1.
Storage
The unit should be stored in a clean, dry environment. Storage temperature range is -55ºC (-67ºF) to +85ºC (+185ºF). Care should be taken to avoid condensation. All packing and shipping materials should be left intact until the unit is ready for final installation. If the unit has been stored for an extended period of time, the unit should be cleaned and carefully inspected before placing into service.
Location Considerations
Environment – The unit is designed for operation indoors in
ambient temperatures of -40ºC (-40ºF) to +60ºC (+140ºF) with a relative humidity of 0% to 95% (non­condensing).
The unit is provided in a metallic industrial enclosure, which should not be installed in areas with excessive dust, corrosive vapors, flammable materials or explosive atmospheres.
The installer should perform the following steps to assure a quality installation. The entire installation manual should be read before starting installation. These instructions do not replace national or local electrical codes. Check applicable electrical codes to ensure compliance. Installation of the Liebert LM Series Surge Protective Device should only be performed by qualified personnel.
Audible Noise – The audible noise of the unit is less that 40
dBA at 5 feet, which allows its placement within almost any room if desired.
Service Clearances – Service clearance is needed only at the
front of the unit. Thirty-six inches (36in / 914mm) minimum is recommended.
Equipment Performance – For maximum system
performance, the unit must be located as close to the protected circuit as practical to minimize interconnecting wiring length.
For optimum transient surge protection, coordinated surge suppression should be applied at the service entrance and all other electrical connections to the building (telephone, CATV, etc.), at known surge generating loads within the building (large motors, arc welders, switched capacitors, etc.), as well as at sensitive electronic loads (such as computers, electronic appliances, solid state motor drives, etc.). For interconnected electronic loads (such as by way of data cabling), transient surge suppression should also be applied to the interconnecting wiring (data cables).
Mounting – Unit is intended to be wall mounted. Refer to
Figure 1 or unit submittal drawings for typical mounting dimensions and weight.
Door Closing Adjustments
Single Door (Wall Mounted) – If the surface on which the
enclosure is mounted is not flat, the door may not open and close properly. Also, if heavy equipment is mounted on a large door, the door may sag slightly. If the top of the door strikes the lip which extends around the body opening, place metal shims behind the mounting foot which is located at the bottom of the enclosure and closest to the door hinge. Place the shims between the mounting foot and the wall or mounting surface. Be sure all mounting screws are tightened securely.
Installation, Operation - 2 - LM Series and Maintenance Manual Rev 0, 5/99
Page 5
Surge
®
LM & LM1 Series Models with Options (Wt. 16 lbs.)
Suppression
Systems
LM & LM1 Series Models with No Options (Wt. 15 lbs.)
Installation, Operation - 3 - LM Series and Maintenance Manual Rev 0, 5/99
Figure 1. Cabinet Data, Form C Contact and Wiring
Page 6
Surge
®
Suppression
Systems
LM, LM1, & LM2 Series Models with Options (Wt. 35 lbs.)
Figure 1. Cabinet Data, Form C Contact and Wiring
Installation, Operation - 4 - LM Series and Maintenance Manual Rev 0, 5/99
Page 7
Surge
®
DANGER
!!
ELECTRICAL CONNECTIONS
Suppression
Systems
All electrical connections should be installed by a qualified (licensed) electrician only. All wiring must comply with the National Electrical Code (NEC) and applicable local codes.
VERIFY THAT ALL POWER CIRCUITS ARE DE-ENERGIZED AND LOCKED OUT BEFORE MAKING ELECTRICAL CONNECTIONS.
Voltage Ratings & Power Source Configurations
Before making connections to the unit, verify that the unit model number and nameplate voltage rating are appropriate for connection to the intended power source. See Figure 2 for voltage rating applications with typical power source configurations.
Surge Voltage Ratings – To obtain the suppression voltage
ratings (SVRs), as obtained by Underwriters Laboratory, Incorporated, in accordance with the Standard for
Safety, Surge Protective Devices (SPDs), Standard 1449,
Second Edition, dated August 15, 1996, marked on this
product, #8 AWG wire must be utilized to connect the LM series to your facilities’ power grid. Connections made with conductors other that #8 AWG may result in different SVRs.
Circuit Ampacity Limitations – This device has been
investigated by Underwriters Laboratories, Incorporated to withstand, without exposing live circuits or components on power sources, a voltage of two times (2x) the device ratings, and fault currents of up to 300,000 AIC, as described in the Standard for Safety,
Surge Protective Devices (SPDs), Standard 1449, Second Edition, dated August 15, 1996.
Parallel Connection (see Figures 3 and 4)
With parallel connection, the length of the wiring to the surge protective device (SPD) unit must be minimized for best performance. Wire lengths longer that 10 feet must be avoided.
To reduce the wiring impedance to surge currents, the phase, neutral (if required), and ground conductors are recommended to be twisted together and routed in the same raceway (conduit). Avoid any sharp bends in the conductors.
Wire Sizing – With parallel connection, the size of the
wiring to the SPD unit is independent of the protected circuit’s ampacity. Suggested wire size of the product is a number 8 gauge conductor minimum. Please reference Figure 1. NEC Articles 280-21 and 22 require surge arrestor connecting conductors to be at least #14 copper or #12 aluminum.
Overcurrent Protection – The SPD unit conducts
practically no current under normal operation and only conducts very short duration transient surge currents. The Liebert SPD units contain UL approved internal fusing to protect against device failure.
External overcurrent protection is not specifically required by NEC Article 280 nor is it desired since it impedes the performance of the surge protective device. If fusing is required, please consult factory for recommendations.
Disconnect Switch – SPD units must be connected to the
load side of the service disconnect, or load side of a protected circuit’s disconnecting means. For best performance, the SPD unit must be located very close to the circuit to be protected and minimum interconnecting wiring used.
A disconnect switch is sometimes used to facilitate servicing the SPD unit. However, use of a disconnect switch for the SPD unit impedes the transient surge suppressing performance of the unit. For maximum transient surge suppressor performance, no disconnect switch is recommended. If a disconnect switch is used, the location and wiring of the switch and SPD unit should minimize the interconnecting wiring (see Figure
4).
Installation, Operation - 5 - LM Series and Maintenance Manual Rev 0, 5/99
Models with a “R” suffix are equipped with an internal disconnect switch, which can be used to de-energize the unit’s transient surge suppressing components for servicing.
Page 8
Surge
Source Configurations
100
N/A
100
100N
LM (1 OR 2) 100N130
M100N130
120
208 or 240
120
120S
LM (1 OR 2) 120S100
M120S100
Split Single Phase, 3 W + G
Three Phase Delta, 3 W + G
Single Phase L-N, 2 W +G
Single Phase L-L, 2 W + G
®
Voltage Ratings & Power Source Configurations
Nominal Operating
Voltage
L – N L – L L – G
110 N/A 110 110N LM (1 OR 2) 110N130 M110N130 120 N/A 120 120N LM (1 OR 2) 120N150 M120N150 230 N/A 230 230N LM (1 OR 2) 230N275 M230N275 277 N/A 277 277N LM (1 OR 2) 277N320 M277N320 347 N/A 347 347N LM (1 OR 2) 347N420 M347N420
120 208 or 240 120 120S LM (1 OR 2) 120S100 M120S100 120 208 or 240 120 120S LM (1 OR 2) 120S101 M120S101
120 208 or 240 120 120S LM (1 OR 2) 120S200 M120S200 120 208 or 240 120 120S LM (1 OR 2) 120S201 M120S201 120 208 or 240 120 120S LM (1 OR 2) 120S111 M120S111
120 208 or 240 120 120S LM (1 OR 2) 120S101 M120S101 120 208 or 240 120 120S LM (1 OR 2) 120S200 M120S200 120 208 or 240 120 120S LM (1 OR 2) 120S201 M120S201 120 208 or 240 120 120S LM (1 OR 2) 120S111 M120S111
Model
Voltage
Code Unit Model Number*
Suppression
Systems
Replaceable Module Part Number
LM1, LM2
Module
Part Number*
Three Phase Delta Hi Leg, 4 W + G
Figure 2. Voltage Ratings and Power Source Configurations
* Replacement part numbers shown are for LM1 and LM2
Series only. Please contact factory for LM Series replacement part numbers.
N/A 208 208 208D LM (1 OR 2) 208D100 M280D100 N/A 208 208 208D LM (1 OR 2) 208D200 M280D200 N/A 208 208 208D LM (1 OR 2) 208D110 M280D110 N/A 240 240 240D LM (1 OR 2) 240D100 M240D100 N/A 240 240 240D LM (1 OR 2) 240D200 M240D200 N/A 240 240 240D LM (1 OR 2) 240D110 M240D110 N/A 480 480 480D LM (1 OR 2) 480D100 M480D100 N/A 480 480 480D LM (1 OR 2) 480D200 M480D200 N/A 480 480 480D LM (1 OR 2) 480D110 M480D110 120 240 120 240H LM (1 OR 2) 120H150 M120H150 208 240 208 240H LM (1 OR 2) 205H250 M120H150
Installation, Operation - 6 - LM Series and Maintenance Manual Rev 0, 5/99
Page 9
Surge
Source Configurations
120
208
120
120Y
LM (1 OR 2) 120Y100
M120Y100
N/A
208
120
120Y
LM (1 OR 2) 208Y130
M208Y130
Three Phase Wye, 3W+G
Three Phase Wye, 4 W + G
No Neutral
®
Voltage Ratings & Power Source Configurations
Nominal Operating
Voltage
L – N L – L L – G
120 208 120 120Y LM (1 OR 2) 120Y101 M120Y101 120 208 120 120Y LM (1 OR 2) 120Y200 M120Y200 120 208 120 120Y LM (1 OR 2) 120Y201 M120Y201 120 208 120 120Y LM (1 OR 2) 120Y111 M120Y111 277 480 277 277Y LM (1 OR 2) 277Y100 M277Y100 277 480 277 277Y LM (1 OR 2) 277Y101 M277Y101 277 480 277 277Y LM (1 OR 2) 277Y200 M277Y200 277 480 277 277Y LM (1 OR 2) 277Y201 M277Y201 277 480 277 277Y LM (1 OR 2) 277Y111 M277Y111 347 600 347 347Y LM (1 OR 2) 347Y100 M347Y100 347 600 347 347Y LM (1 OR 2) 347Y101 M347Y101 347 600 347 347Y LM (1 OR 2) 347Y200 M347Y200 347 600 347 347Y LM (1 OR 2) 347Y201 M347Y201 347 600 347 347Y LM (1 OR 2) 347Y111 M347Y111
N/A 400 230 230Y LM (1 OR 2) 400Y275 M400Y275 N/A 480 277 277Y LM (1 OR 2) 480Y320 M480Y320 N/A 600 347 347Y LM (1 OR 2) 600Y420 M600Y420
Model
Voltage
Code Unit Model Number*
Suppression
Systems
Replaceable Module Part Number
LM1, LM2
Module
Part Number*
Figure 2. Voltage Ratings and Power Source Configurations
* Replacement part numbers shown are for LM1 and LM2
Series only. Please contact factory for LM Series replacement part numbers.
Installation, Operation - 7 - LM Series
and Maintenance Manual Rev 0, 5/99
Page 10
Surge
®
*
*
*
Figure 3. Typical Parallel Connections (without External Disconnect Switch)
*If neutral is provided, a reliable neutral must be pulled to the SPD unit.
Suppression
Systems
Figure 4. Typical Parallel Connections (with External Disconnect Switch)
*If neutral is provided, a reliable neutral must be pulled to the SPD unit.
Installation, Operation - 8 - LM Series and Maintenance Manual Rev 0, 5/99
*
Page 11
Surge
®
Suppression
Systems
System Grounding & Bonding
The performance and safety of any SPD system is dependent on proper grounding and bonding. Grounding is required primarily for safety. Correct implementation also enhances equipment performance. Incorrect grounding can reduce or impede the SPD’s operation.
All electrical circuits to or from the SPD must include an equipment grounding conductor as required by the NEC and local codes.
An insulated grounding conductor is recommended in addition to any metallic raceway, which may be used as a grounding conductor. For parallel-connected SPD, the grounding conductor should be the same wire size as the associated power conductors.
When metallic raceways are used, adequate electrical continuity must be maintained at all raceway connections, particularly raceway terminations to the electrical enclosures.
The use of isolating bushings or other means to interrupt a metallic conduit run is a potential safety hazard and is not recommended.
Grounding Electrode – Contrary to popular belief, surge
protective devices do not discharge all surges to ground (earth). Surge protective devices divert the surge current back to its source to complete the electrical circuit.
In the case of lightning whose potential is developed with respect to the earth, the SPD diverts the surge current to the grounding electrode (earth connection). However, for most transient surges which are developed by switching loads, the SPD diverts the surge current back to its source without involving the grounding electrode.
For proper SPD performance, the service entrance grounding electrode system must comply with the NEC by having all available electrodes (building steel, metal water pipe, driven rods, concrete encased electrodes, etc.) properly bonded together and connected to the power system grounding.
The use of a separate grounding electrode to ground the SPD defeats the effectiveness of the SPD, is a potential safety hazard, may cause equipment damage, is an NEC violation (reference NEC 250-51 and 250-54), and is not recommended.
Installation, Operation - 9 - LM Series and Maintenance Manual Rev 0, 5/99
Page 12
Surge
®
SERIES
LM
SURGE COUNTER
TEST
ENABLE
OK
SERIES
LM
GREEN - OK
RED - SERVICE
OPERATION
Suppression
Systems
Liebert SPD Systems require little or no operator intervention after installation.
The units are provided with diagnostic indicators and alarms (optional) which assist in determining when the unit needs service (see Troubleshooting/Repair/Maintenance Section).
Each active surge current diverter module is equipped with a green and red LED. If the unit is energized and the green LED is off (and/or the red LED is on), the surge current diverter module is not fully functional and requires replacement. See the maintenance section of this manual for additional information.
System Monitor Panel – The unit may be equipped with
one or more of the following status indicators or alarms:
Summary Alarm Contact – Summary alarm Form C (1
N.O. and 1 N.C.) relay contacts are provided for remote indication of each failed surge current diverter module/s.
For standard units (LED only), access to the summary alarm contacts are provided via connection to the orange and yellow 18 gauge conductors, located on the inside of the panel (see Figure 1). For units with optional accessories, access to the summary alarm contacts are provided via contact terminals located on the printed circuit board mounted on the inside of the unit’s door (see Figure 1). Contacts are rated for 5 amps at 277 VAC maximum.
Transient Counter (optional) – A single transient counter is
provided for transient voltage surge monitoring. The counter totalizes surges monitored since the last counter reset.
The transient counter monitors line to ground transient voltages. The circuit totalizes all surges that deviate from the line sine wave envelope by more that 125 volts. The counter is AC coupled and rejects transients longer than 100 µs.
SURGE
SUPPRESSION
LM Standard Features
ALARM
DISABLE
DISABLE
SURGE
SUPPRESSION
LM Optional Features
Module Status Indicators – These indicators provide a
summary of the status of all surge current diverter modules. For normal conditions, the green “OK” LED is luminated and the red “Service” LED is extinguished. If one or more of the surge current diverter modules requires replacement, the green “OK” LED is turned off and the red “Service” LED illuminated.
Front Panel Counter Reset Disable / Enable Button
(provided on units with Transient Counters only) –
The counter is resettable from the counter reset switch. The front reset may be disabled internally to provide protection against tampering. To disable the front reset follow the procedure below:
1) Remove power from the unit, lock out and tag the
disconnect or circuit breaker.
2) Open door and verify power is off with a voltmeter.
3) Throw SWXI on the power supply board to the
disable position.
Audible Alarm (optional) – If one or more of the surge
current diverter modules requires replacement, an audible alarm is activated to draw attention to the fact that repair service is required to restore the system to normal operation. An audible alarm disable is provided to silence the alarm. The system will automatically reset itself after repair. The audible alarm switch and “Service” LED can be tested by depressing the “Test” switch on the system monitor panel.
and Maintenance Manual Rev 0, 5/99
Installation, Operation - 10 - LM Series
Page 13
Surge
®
Suppression
Systems
Remote Monitor Panel (optional) – A remote monitor
panel is available to provide unit status and alarm information at a location up to 500 feet away from the LM Series Surge Protection System. Operation of the Remote Monitor Panel is similar to the unit system monitor panel. The “Enable” position of the switch is the normal position, which allows audible alarm operation. The “Disable” switch position silences the audible alarm. The “Test” position tests the audible alarm and indicator lights.
The remote monitor panel requires and external source of power. Standard units are furnished with a six-foot power cord with a NEMA 5-15 plug for connection to a 120 VAC source. Control connections are required from the remote monitor panel to the power supply board in the LM Series Surge Protection System. Connections are made by way of two-conductor control cable fitted with “RCA” plugs on one end (see Figure 5), which is not furnished with the remote monitor panel.
Installation, Operation - 11 - LM Series and Maintenance Manual Rev 0, 5/99
Figure 5. Remote Monitor Panel
Page 14
Surge
®
DANGER
TROUBLESHOOTING / REPAIR / MAINTENANCE
4. Remove module, disconnecting conductors to the phase
terminal block (or disconnect), ground lug and neutral terminal block.
Suppression
Systems
ONLY QUALIFIED PERSONNEL SHOULD PERFORM MAINTENANCE ON THE SYSTEM.
HAZARDOUS VOLTAGES ARE PRESENT INSIDE THE UNIT DURING NORMAL OPERATIONS.
ELECTRICAL SAFETY PRE­CAUTIONS MUST BE FOLLOWED WHEN SERVICING THIS EQUIP­MENT.
TO PREVENT RISK OF ELECTRICAL SHOCK, TURN OFF AND LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE SERVICING UNIT.
(For any other problems not listed below, or if cause of the problem cannot be determined, please call Control Concepts at 800-288-6169 or 607-724-2484.)
5. Place new module in position and secure it.
6. Connect the conductors of the new module to the phase
switch terminal block (or disconnect), ground lug and neutral terminal block.
7. Reconnect customer wiring (or wiring from disconnect
to module, if disconnect is provided) in its original location as noted in step 3.
8. Restore power to unit. Assure that the green LED on
each module is illuminated and the red LED and alarm (if applicable) are off.
9. Replacement is now complete.
If (after replacement) green LEDs are not illuminated on all modules and the door, or if the red LED or alarm on the door are ON, disconnect power to the unit and recheck all connections. If problem is not apparent, contact the factory.
Display Blank – No Red or Green LEDs Illuminated on Door
Red LED on Door Illuminated & Green LED on Door Extinguished
1. Check power supply connections. Assure proper voltage
is being supplied to unit. If proper voltages are not being supplied, correct wiring to the unit and check the source of supply.
2. Check to see if any of the green LEDs on the internal
modules are extinguished. If so, replace module which contain modules with extinguished LEDs.
DISCONNECT POWER TO THE UNIT
BEFORE PROCEEDING
3. Remove customer wiring (or wiring from disconnect to
module, if disconnect is provided) identifying which color supply wire goes where for re-wiring purposes (i.e., red supply wire removed from Phase B, etc…).
1. Check supply connections. Assure proper voltage is
supplied to unit. If proper voltages are not being supplied, correct wiring to the unit and check the source of supply.
Note: If voltage supplied to unit is correct, contact factory for replacement parts.
Installation, Operation - 12 - LM Series and Maintenance Manual Rev 0, 5/99
Page 15
Surge
®
Suppression
Systems
Replacing Power Supply Board
Units with Counter or Audible Alarm Options
Equipment Needed:
Small flat blade screwdriver Large flat blade screwdriver
Parts Needed:
Replacement power supply board (contact factory for part) Tie wraps Marking tape
DISCONNECT POWER TO THE UNIT
BEFORE PROCEEDING
Procedure:
Note: The power supply board is located on the back side (inside) of the front door.
1. On the power supply board , use tie wraps to secure the
black, white, and green wires at terminal block TB#1.
4. Disconnect all wires from the power supply board.
Remove the four screws from the corners and remove the board.
5. Position the new power supply board and secure it using
the four screws.
6. Reconnect wires to all terminal positions.
7. Restore power to unit. Assure that the LED on each
module is illuminated. Assure green LED on door is illuminated and red LED and alarm (if applicable) are off.
8. Replacement is now complete.
If (after replacement) green LEDs are not illuminated on all modules and the door, or if the red LED or alarm on the door are ON, disconnect power to the unit and recheck all connections. If problem is not apparent, contact factory.
Preventative Maintenance (Inspection and Cleaning)
2. At terminal block TB#4, using tape, mark the wires from
1 – 6 depending on options.
3. Terminal block TB#3 is for customer wiring for remote
status indication. If there are wires connected to this terminal block, note each wires position so that they may be correctly replaced on new power supply board.
Periodic system inspections, cleaning, and connection checks are recommended to ensure reliable system performance and continued surge transient protection.
It is difficult to establish a schedule for preventative maintenance since conditions vary from site to site. Inspections for failed surge current diverter modules using available diagnostics should be done routinely (weekly or monthly).
Installation, Operation - 13 - LM Series and Maintenance Manual Rev 0, 5/99
Page 16
Surge
®
Suppression
Systems
LIMITED WARRANTY
This Warranty is given ONLY to purchasers who buy for commercial or industrial use in the ordinary course of each purchaser's business.
General:
Control Concepts' products are in our opinion the finest available. We take pride in our products and are pleased that you have chosen them. Under certain circumstances, we offer with our products the following Five-Year Warranty Against Defects in Material and Workmanship. Please read your Warranty carefully. This Warranty sets forth our responsibilities in the unlikely event of defect and tells you how to obtain performance under this Warranty.
FIVE YEAR LIMITED WARRANTY AGAINST DEFECTS IN MATERIAL AND WORKMANSHIP
CONTROL CONCEPTS PRODUCTS COVERED: LM Series Surge Suppression Products.
Terms of Warranty:
As provided herein, the Control Concepts product is warranted to be free of defects in material and workmanship for a period of five (5) years from the date of delivery of the product to User. The delivery date will be determined only from the Control Concepts bill of lading. If any of the Control Concepts products fail to conform to the warranty within the warranty period, Control Concepts, at its option, will furnish new or factory remanufactured parts for repair or replacement of that part.
Warranty Extends to First Purchaser for Use, Non-Transferable:
This Warranty is extended to the first person, firm, association or corporation for whom the Control Concepts product specified herein is originally installed for use in the United States (the "User"). This Warranty is not transferable or assignable without the prior written permission of Control Concepts.
Assignment of Warranties:
Control Concepts assigns to User any warranties which are made by manufacturers and suppliers of components of the Control Concepts product and which are assignable, but Control Concepts makes NO REPRESENTATIONS as to the effectiveness or extent of such warranties, assumes NO RESPONSIBILITY for any matters which may be warranted by such manufacturers or suppliers and extends no coverage under this warranty to such components.
Descriptions:
Control Concepts warrants for the period and on the terms of the Warranty set forth herein that the Control Concepts product will conform to the descriptions contained in Control Concepts' final invoices, orders and Control Concepts' product brochures. Control Concepts does not control the installation and use of any Control Concepts product. Accordingly, it is understood that the Descriptions are NOT WARRANTIES OF PERFORMANCE and NOT WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE.
Obtaining Performance Under This Warranty:
Within a reasonable time, but in no case to exceed thirty (30) days, after User's discovery of a defect, User shall contact Control Concepts and request a return authorization number. User shall ship the product, with proof of purchase, to Control Concepts freight prepaid. Control Concepts products shipped to Control Concepts without a return authorization number will be refused and returned freight collect to User at User's expense. Control Concepts products shipped by User to Control Concepts which have incurred freight damage due to User's improper packaging of the product will not be covered by this Warranty and any repairs or replacement parts, components or products needed will be invoiced in the full current price amount and returned freight collect to User.
Subject to the limitations specified herein, Control Concepts will repair or replace, at its option, without charge for Control Concepts labor or materials, subsequent to its inspection and F.O.B. Control Concepts' facility, the Control Concepts product shipped to Control Concepts with a return authorization number and warranted hereunder which does not conform to the Warranty. Replacement parts, components or products shipped to User prior to Control Concepts' receipt and inspection of the product claimed to be defective, shall be invoiced in the full current price amount and shipped freight collect F.O.B. Control Concepts' facility. Warranty coverage will be extended only after Control Concepts' receipt of the claimed defective product within thirty (30) days of shipment of any replacement parts, components or products, if applicable, Control Concepts' inspection discloses the claimed defect and the returned product shows no signs of treatment or use which would void the coverage of this Warranty.
Items Not Covered By Warranty:
THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY misuse, improper application, wrong or inadequate electrical current or connection, inadequate water or drain services, negligence, inappropriate on site operating conditions, corrosive atmosphere, repair by non-Control Concepts designated personnel, accident in transit, tampering, alterations, a change in location or operating use, exposure to the elements, Acts of God, theft or installation contrary to Control Concepts' recommendations or specifications, or in any event if the Control Concepts serial number has been altered, defaced or removed.
THIS WARRANTY DOES NOT COVER shipping costs, installation costs, circuit breaker resetting or maintenance or service items and further, except as provided herein, does NOT include labor costs or transportation charges arising from the replacement of the Control Concepts product or any part thereof or charges to remove same from any premises of the User.
THIS WARRANTY DOES NOT COVER DAMAGE OR DEFECT CAUSED BY use of the Control Concepts product in combination with any electrical or electronic components, circuits, systems, assemblies, or other materials not furnished by Control Concepts. Control Concepts does NOT warrant the suitability for use or the results of the Control Concepts product in combination with the products of others.
REPAIR OR REPLACEMENT OF A DEFECTIVE PRODUCT OR PART THEREOF DOES NOT EXTEND THE ORIGINAL WARRANTY PERIOD.
Installation, Operation - 14 - LM Series and Maintenance Manual Rev 0, 5/99
Page 17
Surge
®
Suppression
Systems
Limitations:
THIS WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE.
USER'S SOLE AND EXCLUSIVE REMEDY IS REPAIR OR REPLACEMENT OF THE CONTROL CONCEPTS PRODUCT AS SET FORTH
HEREIN.
IF USER'S REMEDY IS DEEMED TO FAIL OF ITS ESSENTIAL PURPOSE BY A COURT OF COMPETENT JURISDICTION, CONTROL
CONCEPTS' RESPONSIBILITY FOR PROPERTY LOSS OR DAMAGE SHALL NOT EXCEED ONE TIMES THE NET PRODUCT PURCHASE PRICE.
IN NO EVENT SHALL CONTROL CONCEPTS ASSUME ANY LIABILITY FOR INDIRECT, SPECIAL, INCIDENTAL, OR ECONOMIC
CONSEQUENTIAL DAMAGES OF ANY KIND WHATSOEVER, INCLUDING WITHOUT LIMITATION, LOST PROFITS, BUSINESS INTERRUPTION OR LOSS OF DATA, WHETHER ANY CLAIM IS BASED UPON THEORIES OF CONTRACT, NEGLIGENCE, STRICT LIABILITY, TORT OR OTHERWISE.
Miscellaneous:
NO SALESPERSON, EMPLOYEE OR AGENT OF CONTROL CONCEPTS IS AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS
WARRANTY. Warranty terms may be modified, if at all, only in a writing signed by a Control Concepts' officer.
This Warranty is effective as of the date of Control Concepts receipt of payment and supersedes all previous warranties. Control Concepts reserves the right
to supplement or change the terms of this Warranty in any subsequent warranty offering to User or others.
In the event that any provision of this Warranty should be or becomes invalid and/or unenforceable during the warranty period, the remaining terms and
provisions shall continue in full force and effect.
This Warranty is given in and is intended to be construed under the laws of the State of New York.
This Warranty represents the entire agreement between Control Concepts and User with respect to the subject matter herein and supersedes all prior or
contemporaneous oral or written communications, representations, understandings or agreements relating to this subject.
Installation, Operation - 15 - LM Series and Maintenance Manual Rev 0, 5/99
Page 18
Surge
®
Suppression
Systems
DECLARATION OF CONFORMITY
All models of the LM Series Surge Protective Devices are in compliance with the EMC Directive 89/336/EEC, conforming to EMC standard IEC 1000-4-4 and IEC 1000-4-5.
----- Office of the Vice-President of Engineering, Binghamton, NY USA, April 1998.
Installation, Operation - 16 - LM Series and Maintenance Manual Rev 0, 5/99